PT PLN (PERSERO)

PEMBANGKITAN DAN PENYALURAN SULAWESI

APPROVAL DAN EVALUASI SETTING PROTEKSI


PCS 9611 OVERCURRENT PROTECTION GI 150 kV PAMONA (EXT)
SISI 150 KV
Description
Merk Relay : NR
Type Relay : PCS 9611
S/N Relay :
Rated Current : 1 A (In)
CT Ratio : 150 / 1 A
Ihs 3 Phasa (Max) : 5,62 kA
Ihs 2 Phasa (Max) : 4,88 kA
Ihs 1 Phasa (Max) : 4,17 kA
Time Trip : 1,5 detik (pada Arus Hubung Singkat 2 phasa
maksimum di Bus Lokal)
System Data
No. Setting Item Proposal Setting Approval Setting Remark
1 Active_Grp 1 1
2 Opt_SysFreq 50 Hz 50 Hz
3 PrimayEquip_Name TRANS-2
4 Prot.I1n 150 A 150 A
5 Prot.I2n 1A 1 A
6 Measmt.I1n 150 A 150 A
7 Measmt.I2n 1A 1 A
8 Neu1.I1n 0A 0 A
9 Neu1.I2n 1A 1 A
10 Prot.U1n 150 kV 150 kV
11 Prot.U2n 110 V 110 V
12 Syn.U1n 150 kV 150
13 Syn.U2n 110 V 110
14 Opt_PwrDir 3 3

Phase Overcurrent Protection


No. Setting Item Proposal Setting Approval Setting Remark
1 50/51P.U2_VCE 5,00 V - V
2 50/51P.Upp_VCE 104,40 V - V
3 50/51P.En_VCE_CrossCtrl 0 0
4 50/51P.RCA 30,00 deg - deg
5 50/51P.En_VTS_Blk 0 0
6 50/51P.K_Hm2 0,15 -
7 50/51P.I_Rls_HmBlk 3,97 A - A
8 50/51P.Opt_Hm_Blk 2 -
9 50/51P1.I_Set 3,97 7,39 A

Page : 1/5 Dibuat Oleh Dievaluasi Oleh Disetujui oleh


Date : 07 Desember 2022 1. Andrian S.

2. Marwah R
Approval Setting Proteksi Trafo
Maizarah Purnamaningsih Yudha Verdiansyah
GI Pamona 150 kV
PT PLN (PERSERO) UIKL SULAWESI
PT PLN (PERSERO)
PEMBANGKITAN DAN PENYALURAN SULAWESI

APPROVAL DAN EVALUASI SETTING PROTEKSI


PCS 9611 OVERCURRENT PROTECTION GI 150 kV PAMONA (EXT)
SISI 150 KV
Description
Merk Relay : NR
Type Relay : PCS 9611
S/N Relay :
Rated Current : 1 A (In)
CT Ratio : 150 / 1 A
Ihs 3 Phasa (Max) : 5,62 kA
Ihs 2 Phasa (Max) : 4,88 kA
Ihs 1 Phasa (Max) : 4,17 kA
Time Trip : 1,5 detik (pada Arus Hubung Singkat 2 phasa
maksimum di Bus Lokal)
Phase Overcurrent Protection
No. Setting Item Proposal Setting Approval Setting Remark
10 50/51P1.t_Op 0,20 0,40
11 50/51P1.En_VCE 1 0
12 50/51P1.Opt_Dir 0 0
13 50/51P1.En_Hm_Blk 1 0
14 50/51P1.En 1 1
15 50/51P1.OutMap FFFF FFFF
16 50/51P2.I_Set Default A -
17 50/51P2.t_Op Default s -
18 50/51P2.En_VCE 0 -
19 50/51P2.Opt_Dir 0 -
20 50/51P2.En_Hm_Blk 0 -
21 50/51P2.En 0 0
22 50/51P3.I_Set 0,92 A 0,92 A
23 50/51P3.t_Op 0,30 s - s
24 50/51P3.En_VCE 0 0
25 50/51P3.Opt_Dir 0 0
26 50/51P3.En_Hm_Blk 1 0
27 50/51P3.En 1 1
28 50/51P3.OutMap FFFF FFFF
29 50/51P3.Opt_Curve 1 1
30 50/51P3.TMS 0,049 0,34
31 50/51P3.tmin 0,1 s 0,1 s
32 50/51P3.K 0,14 -
33 50/51P3.C 0,00 -
34 50/51P3.Alpha 0,02 -
35 50/51P4.I_Set 0 -

Page : 2/5 Dibuat Oleh Dievaluasi Oleh Disetujui oleh


Date : 07 Desember 2022 1. Andrian S.

2. Marwah R
Approval Setting Proteksi Trafo
Maizarah Purnamaningsih Yudha Verdiansyah
GI Pamona 150 kV
PT PLN (PERSERO) UIKL SULAWESI
PT PLN (PERSERO)
PEMBANGKITAN DAN PENYALURAN SULAWESI

APPROVAL DAN EVALUASI SETTING PROTEKSI


PCS 9611 OVERCURRENT PROTECTION GI 150 kV PAMONA (EXT)
SISI 150 KV
Description
Merk Relay : NR
Type Relay : PCS 9611
S/N Relay :
Rated Current : 1 A (In)
CT Ratio : 150 / 1 A
Ihs 3 Phasa (Max) : 5,62 kA
Ihs 2 Phasa (Max) : 4,88 kA
Ihs 1 Phasa (Max) : 4,17 kA
Time Trip : 1,5 detik (pada Arus Hubung Singkat 2 phasa
maksimum di Bus Lokal)
Phase Overcurrent Protection
No. Setting Item Proposal Setting Approval Setting Remark
36 50/51P4.t_Op 0 -
37 50/51P4.En_VCE 0 -
38 50/51P4.Opt_Dir 0 -
39 50/51P4.En_Hm_Blk 0 -
40 50/51P4.En 0 -
41 50/51P4.OutMap 0 -
42 50/51P4.Opt_Curve 0 -
43 50/51P4.TMS 0 -
44 50/51P4.tmin 0 -
45 50/51P4.K 0 -
46 50/51P4.C 0 -
47 50/51P4.Alpha 0 -
48 50/51P5.I_Set 0 -
49 50/51P5.t_Op 0 -
50 50/51P5.En 0 -
51 50/51P6.I_Set 0 -
52 50/51P6.t_Op 0 -
53 50/51P6.En 0 -
54 50/51P.I_CCE 0 -
55 50/51P.En_CCE 0 -

Earth Fault Protection


No. Setting Item Proposal Setting Approval Setting Remark
1 50/51G.RCA -88 -
2 50/51G.En_VTS_Blk 1 -
3 50/51G.K_Hm2 0,15 -

Page : 3/5 Dibuat Oleh Dievaluasi Oleh Disetujui oleh


Date : 07 Desember 2022 1. Andrian S.

2. Marwah R
Approval Setting Proteksi Trafo
Maizarah Purnamaningsih Yudha Verdiansyah
GI Pamona 150 kV
PT PLN (PERSERO) UIKL SULAWESI
PT PLN (PERSERO)
PEMBANGKITAN DAN PENYALURAN SULAWESI

APPROVAL DAN EVALUASI SETTING PROTEKSI


PCS 9611 OVERCURRENT PROTECTION GI 150 kV PAMONA (EXT)
SISI 150 KV
Description
Merk Relay : NR
Type Relay : PCS 9611
S/N Relay :
Rated Current : 1 A (In)
CT Ratio : 150 / 1 A
Ihs 3 Phasa (Max) : 5,62 kA
Ihs 2 Phasa (Max) : 4,88 kA
Ihs 1 Phasa (Max) : 4,17 kA
Time Trip : 1,5 detik (pada Arus Hubung Singkat 2 phasa
maksimum di Bus Lokal)
Earth Fault Protection
No. Setting Item Proposal Setting Approval Setting Remark
4 50/51G.3I0_Rls_HmBlk 0,23 -
5 50/51G1.Opt_3I0 cal cal
6 50/51G1.3I0_Set 0,2 A -
7 50/51G1.t_Op 0,2 s -
8 50/51G1.Opt_Dir 0 -
9 50/51G1.En_Hm_Blk 1 -
10 50/51G1.En 1 0
11 50/51G1.OutMap FFFF FFFF
12 50/51G2.RCA Default -
13 50/51G2.En_VTS_Blk 0 -
14 50/51G2.K_Hm2 Default -
15 50/51G2.3I0_Rls_HmBlk Default -
16 50/51G2.Opt_3I0 Default -
17 50/51G2.3I0_Set Default -
18 50/51G2.t_Op Default -
19 50/51G2.Opt_Dir Default -
20 50/51G2.En_Hm_Blk 0 -
21 50/51G2.En 0 -
22 50/51G2.OutMap 0 -
23 50/51G3.RCA -88 deg -
24 50/51G3.En_VTS_Blk 1 0
25 50/51G3.K_Hm2 0 -
26 50/51G3.3I0_Rls_HmBlk 0 -
27 50/51G3.Opt_3I0 Cal Cal
28 50/51G3.3I0_Set 0,05 A 0,385 A
29 50/51G3.t_Op 0s -

Page : 4/5 Dibuat Oleh Dievaluasi Oleh Disetujui oleh


Date : 07 Desember 2022 1. Andrian S.

2. Marwah R
Approval Setting Proteksi Trafo
Maizarah Purnamaningsih Yudha Verdiansyah
GI Pamona 150 kV
PT PLN (PERSERO) UIKL SULAWESI
PT PLN (PERSERO)
PEMBANGKITAN DAN PENYALURAN SULAWESI

APPROVAL DAN EVALUASI SETTING PROTEKSI


PCS 9611 OVERCURRENT PROTECTION GI 150 kV PAMONA (EXT)
SISI 150 KV
Description
Merk Relay : NR
Type Relay : PCS 9611
S/N Relay :
Rated Current : 1 A (In)
CT Ratio : 150 / 1 A
Ihs 3 Phasa (Max) : 5,62 kA
Ihs 2 Phasa (Max) : 4,88 kA
Ihs 1 Phasa (Max) : 4,17 kA
Time Trip : 1,5 detik (pada Arus Hubung Singkat 2 phasa
maksimum di Bus Lokal)
Earth Fault Protection
No. Setting Item Proposal Setting Approval Setting Remark
30 50/51G3.Opt_Dir 0 0
31 50/51G3.En_Hm_Blk 1 0
32 50/51G3.En 1 1
33 50/51G3.OutMap FFFF FFFF
34 50/51G3.Opt_Curve 1 1
35 50/51G3.TMS 0 0,74
36 50/51G3.tmin 0s 0 s
37 50/51G3.K 0 -
38 50/51G3.C 0 -
39 50/51G3.Alpha 0 -
40 50/51G4.RCA Default deg -
41 50/51G4.En_VTS_Blk 0 -
42 50/51G4.K_Hm2 Default 0
43 50/51G4.3I0_Rls_HmBlk Default -
44 50/51G4.Opt_3I0 Default -
45 50/51G4.3I0_Set Default A -
46 50/51G4.t_Op Default s -
47 50/51G4.Opt_Dir 0 -
48 50/51G4.En_Hm_Blk 0 -
49 50/51G4.En 0 -
50 50/51G4.OutMap 0 -
51 50/51G4.Opt_Curve Default -
52 50/51G4.TMS Default -
53 50/51G4.tmin Default -
54 50/51G4.K Default -
55 50/51G4.C Default -
56 50/51G4.Alpha Default -

CT & VT Circuit Supervision


No. Setting Item Proposal Setting Approval Setting Remark
1 CTS.3I0_Set 1 -
2 CTS.3U0_Set 0 -
3 CTS.En 0 0
4 VTS.I_Set 0 -
5 VTS.I2_Set 0 -
6 VTS.En 0 0
7 VTS.En_SynVT 3 -

Page : 4/5 Dibuat Oleh Dievaluasi Oleh Disetujui oleh


Date : 07 Desember 2022 1. Andrian S.

2. Marwah R
Approval Setting Proteksi Trafo
Maizarah Purnamaningsih Yudha Verdiansyah
GI Pamona 150 kV
PT PLN (PERSERO) UIKL SULAWESI