Pendingin PLTU
AFRIZAL FAJAR BASKORO
SISWA OJT PT. INDONESIA POWER
ANGKATAN XX
Sistem Pendingin PLTU
M
To Klorin Plant dan BOP
M Condenser Side A
CWP System
M
H M
→
CWP Desal Debris M
1A Pump Filter
Bar TBS
M
M M
Screen 1A ←
M
M
H
M Collector
→
M M
CWP Ball
1B M M ← Strainer
Bar TBS
M M
Screen 1B
M M ← M
←
M
M M
Cooling
M
Pump
M M ← To
M M Shippon Well
Electric
Filter ← M Condenser Side B
M
M M
← Debris M
M M Filter
M
←
M M
←
M M
Collector
←
Screen Wash Pump Ball
Strainer
OCCW System M M
←
M
M
Electric OCCW Pump A
M Filter M M M M M
→ Heat
To
Exchanger To Shippon Well
OCCW Pump B
M
M M A Outfall
Drain
→ M M
Heat
Exchanger
B
M Vacum M
Pump HE
M M
Vacum
Pump HE
2.2 CCCW System
Sistem air pendingin bantu ini menggunakan media air demin
sebagai bahan baku untuk pendinginan. Sistem air pendingin
ini digunakan untuk mendinginkan peralatan bantu pada
PLTU, yaitu:
PeralatanTurbin Peralatan Boiler
•Condensate Pump Motor Cooler A-B
•BFPT Booster Mechanical Sealing Cooler A-B •Instrument Air Compressor A-C
•MDBFP Booster Mechanical Sealing Cooler A •Service Air Compressor A-C
•MDBFP Working Oil Cooler
•MDBFP Lubrication Oil Cooler •Ash Hopper Valve Cooler A-B
•MDBFP Mechanical Sealing Cooler A-B •Mill Oil Lubrication Station A-F
•Condensate Pump Bearing Cooler A-B •Sealing Air Fan Bearing Cooler A-B
•BFPT Lubrication Oil Cooler A-D
•Turbine Lubrication Oil Cooler A-B •Sample Cooler (Sampling Rack
•EH Oil Cooler A-B Cooler)
•Condensate Pump Mechanical Sealing Water
A-B •Ash Handling System Air Compressor
•Steam Room Bypass Station Cooler •PAF Bearing Cooling A-B
•Exciter Air Cooler A-B
•Generator Hydrogen Cooler A-D •FDF Oil Lubrication Station A-B
•Generator Stator Cooler A-B •IDF Oil Lubrication Station A-B
•Oil Seal Cooler On Generator Air Side A-B •Air Heater Oil Station A-D
•Oil Seal Cooler On Generator Hydrogen Side
A-B
Expansion Tank
CCCW Pump
CCCW Booster Pump
Heat Exchanger
CCCW System
PAF Bearing Cooling Exciter Air Cooler
Air Heater Oil Lubrication Station Oil Seal Cooler Generator Air Side
Expansion Sealing Air Fan Bearing Cooler Oil Seal Cooler Generator Hydrogen Side
Tank
Sample Cooler BFTP Lubrication Oil Cooler
Sealing Air Fan Bearing Cooler Steam Room Bypass Station Cooler
→
CCCW Pump B
Heat Exchanger
B
Start CWP
Breaker 6.3 KV motor Outlet MOV kondensor ±25%
CWP ON dan Remote
Inlet MOV full open
Pastikan SWP, TBS,
Start CWP dari DCS
Cooling Water Pump
Running Pastikan indikator motor
berwarna merah
Gate valve outfall open
Pastikan di local CWP normal
Oil level cooling upper
bearing CWP >50% Mengatur bukaan control
valve outlet kondensor hingga
Level Hidraulic
pressure header 0.10 - 0.15
discharge CWP >75%
MPa
Breaker 400V untuk MOV
inlet & outlet Kondensor
ON dan Remote
Monitoring CWP