(ILSAS)
Interpretation of Protection
Schemes
Kursus: SSO
Bahagian Penghantaran,TNB.
Kandungan Subjek
1) Pengenalan
2) Objektif Subjek
3) Gambaran skim perlindungan ( Part 1 )
a) Overcurrent & Earth Fault
b) Transformer Differential, Restricted Earth Fault, Stand by
Earth Fault dan Transformer Guard
c) Distance Protection, Current Differential & Current
Comparison
d) Current Differential @ Current Comparison
e) Autoreclose & Syncronising
Pengenalan
SSO adalah orang pertama yang
menjadi mata dan telinga kepada
pihak NLDC dan jurutera tempatan
ketika berlaku kejadian tidak normal
di PMU.
OBJEKTIF - No 1.
OBJEKTIF - No 2.
Part 1
Transformer Protection
Transformer Protection
•Biased Differential (DIFF)
–Zone perlindungan adalah keseluruhan Transformer
• HV Restricted Earthfault (HV REF)
–Zone Perlindungan adalah bahagian HV transformer
–Sensitif kepada winding faults
• LV Restricted Earthfault (LV REF)
– Zone Perlindungan adalah bahagian LV transformer
–Sensitif kepada winding faults & Cable Tail
Transformer Protection
•Standby Eart fault Relay ( SBEF )
–CT terletak di Neutral Cable dan mengesab sebarang Eath Fault
melalui Transformer
–Stage 1 trips Bus Section and/or Bus Coupler
–Stage 2 trips HV & LV transformer feeders
–Bertindak Sebagai ‘Back Up’ Earth Fault relay kepada feeder
dengan mengasingkan busbar
Transformer Protection
•Transformer Guards
–Bucholz Relay - Tank & OLTC
–Pressure Relief Device
–HV and LV winding Temperature
–Oil Temperature
–Oil Level
POWER TRANSFORMER
BREAKER CT BREAKER
CT
REF
STAR
SBEF
INTERPOSING
CT
DELTA
DIFF
Distance Protection
( Skim Pelindungan Talian Atas )
Distance Protection
Zone 3 & Zone 3 Reverse
Zone 2
jX
Zone 1
A B
B
Distance Carrier Send & Receives
DEF Carrier Send & Receives
Aided trip A R
Normal Condition
- G.703 - G.703
- RS422 - RS422
(155Mbps)
Telecom Equipment Telecom Equipment
Auto Reclose
Auto Reclose
• Autoreclose relay
1. Penutupan CB secara Otomatik untuk menormalkan system
selepas pelantikan talian atas disebabkab oleh “Transient Fault”.
2. Autoreclosed in progress – Distance atau CD memberi isyarat
supaya Autoreclosed dimulakan oleh AR relay
3. Autoreclosed attempt – AR relay memberi isyarat supaya CB
ditutup
4. Autoreclosed Lockout – Proses AR tidak dibenarkan
Ib
Ia Station B
Geganti Diff.
R
I diff =Ia - Ib
Dawai Pandu
Busbar Protection
Busbar Protection
Busbar Protection
Kirchhoff’s law 1
I1 I2 I 1 + I2 + I3 + I4 = 0
Busbar I3 I4
protection
C
132/11 kV
Latihan Penghantaran - July 2005 Nik Nasharudin Nik Mohamad
Institut Latihan Sultan Ahmad Shah
(ILSAS)
Breaker Failure
Breaker Failure
Skim Kegagalan Pemutus Litar
Mengesan sebarang kegagalan yg
dialami oleh Pemutus Litar (CB)
Selamasa (time delay) : 150 ms
Menyebabkan kehilangan separuh drp
Busbar
Breaker Failure
Jenis:
-MK30
-MK20
DC System
Komponen-komponen Sistem
Arus Terus
• AC/DC Converter – Untuk menukar arus
ulang alik kepada arus terus.
• Papan Agihan Voltan Arus Terus –
Mengagih bekalan kepada radas-radas
yang memerlukannya.
Komponen-komponen Sistem
Arus Terus
• Sel-sel Bateri – Sumber bekalan arus
terus jika bekalan arus terus utama tiada.
• Pengecas Bateri – Memastikan cas pada
bateri sentiasa berada pada tahap yang
optima agar bateri dapat berfungsi apabila
diperlukan
Part 2
11kV
SBEF
OCEF
REF
BASIC PROTECTION SCHEME
DIFF
REF
275 kV
OCEF
132kV Main 1
OCEF
Main 2
T
OCEF
OCEF O/H
U/G
CD CD
O/H Main 2
T Main 1
OCEF 275 kV
132 kV
132 kV
Latihan Penghantaran - July 2005 Nik Nasharudin Nik Mohamad
Institut Latihan Sultan Ahmad Shah
(ILSAS)
11kV
SBEF
OCEF
REF
BASIC PROTECTION SCHEME
DIFF
REF PH-E
275 kV
OCEF
132kV Main 1
OCEF
Main 2
T
OCEF
OCEF O/H
U/G
CD CD
O/H Main 2
T Main 1
OCEF 275 kV
132 kV
132 kV
Latihan Penghantaran - July 2005 Nik Nasharudin Nik Mohamad
Institut Latihan Sultan Ahmad Shah
(ILSAS)
11kV
SBEF
OCEF
REF
BASIC PROTECTION SCHEME
DIFF
REF PH-PH
275 kV
OCEF
132kV Main 1
OCEF
Main 2
T
OCEF
OCEF O/H
U/G
CD CD
O/H Main 2
T Main 1
OCEF 275 kV
132 kV
132 kV
Latihan Penghantaran - July 2005 Nik Nasharudin Nik Mohamad
Institut Latihan Sultan Ahmad Shah
(ILSAS)
11kV
SBEF
OCEF
REF BASIC PROTECTION SCHEME
PH-E
DIFF
REF
275 kV
OCEF
132kV Main 1
OCEF
Main 2
T
OCEF
OCEF O/H
U/G
CD CD
O/H Main 2
T Main 1
OCEF 275 kV
132 kV
132 kV
Latihan Penghantaran - July 2005 Nik Nasharudin Nik Mohamad
Institut Latihan Sultan Ahmad Shah
(ILSAS)
11kV
SBEF
OCEF
REF BASIC PROTECTION SCHEME
PH-E
DIFF
REF
275 kV
OCEF
132kV Main 1
OCEF
Main 2
T
OCEF
OCEF O/H
U/G
CD CD
O/H Main 2
T Main 1
OCEF 275 kV
132 kV
132 kV
Latihan Penghantaran - July 2005 Nik Nasharudin Nik Mohamad
Institut Latihan Sultan Ahmad Shah
(ILSAS)
11kV PH-E
SBEF
OCEF
REF BASIC PROTECTION SCHEME
DIFF
REF
275 kV
OCEF
132kV Main 1
OCEF
Main 2
T
OCEF
OCEF O/H
U/G
CD CD
O/H Main 2
T Main 1
OCEF 275 kV
132 kV
132 kV
Latihan Penghantaran - July 2005 Nik Nasharudin Nik Mohamad
Institut Latihan Sultan Ahmad Shah
(ILSAS)
11kV
SBEF
OCEF
REF BASIC PROTECTION SCHEME
DIFF
REF
275 kV
OCEF
132kV Main 1
OCEF
Main 2
T
PH-E
OCEF
OCEF O/H
U/G
CD CD
O/H Main 2
T Main 1
OCEF 275 kV
132 kV
132 kV
Latihan Penghantaran - July 2005 Nik Nasharudin Nik Mohamad
Institut Latihan Sultan Ahmad Shah
(ILSAS)
11kV
SBEF
OCEF
REF BASIC PROTECTION SCHEME
DIFF
REF
275 kV
OCEF
132kV Main 1
OCEF
Main 2
T
OCEF
OCEF O/H
U/G
CD CD
O/H Main 2
PH-E
T Main 1
OCEF 275 kV
132 kV
132 kV
Latihan Penghantaran - July 2005 Nik Nasharudin Nik Mohamad
Institut Latihan Sultan Ahmad Shah
(ILSAS)
11kV
SBEF
OCEF
REF BASIC PROTECTION SCHEME
DIFF
REF
275 kV
OCEF
132kV Main 1
OCEF
Main 2
T
OCEF
OCEF O/H
U/G
CD CD
B/B Main/
Reserve
O/H Main 2
T Check Main 1
Zone
OCEF 275 kV
PH-E 132 kV
132 kV
Latihan Penghantaran - July 2005 Nik Nasharudin Nik Mohamad
Institut Latihan Sultan Ahmad Shah
(ILSAS)
11kV
SBEF
OCEF
REF BASIC PROTECTION SCHEME
DIFF
REF
275 kV
OCEF
132kV Main 1
OCEF
Main 2
T
PH-E
OCEF
OCEF O/H
U/G
CD CD
B/B Main/
Reserve
O/H Main 2
T Check Main 1
Zone
OCEF 275 kV
132 kV
132 kV
Latihan Penghantaran - July 2005 Nik Nasharudin Nik Mohamad
Institut Latihan Sultan Ahmad Shah
(ILSAS)
Part 3
3. Catatkan pelantikan CB
7. LED.(cara melapor)
i. Lampu pada geganti
ii. Nama geganti
iii. Identifikasi geganti
iv. Model
v. Nama feeder
vi. LED indication
8. LCD
i. SSO perlu biasakan bagaimana untuk rekod data dari
LCD
ii. SSO mesti buat salinan yang sama(exactly) dengan
paparan dari LCD (tanpa mengubah ayat)
iii. Stesen yang ada kemudahan SCS, SSO mesti mahir
membaca, mengambil data dan tahu untuk RESET.
9. SCS
i. Print out announciation window , senarai pelantikan
ii. Simpan dalam buku log dengan lengkapnya (digunakan
selepas normalize)
Menguji Kefahaman
Soalan-soalan:
1. Terdapat Kerosakan Kabel (daripada Transformer kepada
Earthing Transformer) di PMU 132/11kV. Terangkan:-
- Facia yang dijangkakan keluar
- Relay yang beroperasi
- Langkah-langkah SSO seterusnya
Kesimpulan