B) SUMBER Mata Air (Sistim Perpompaan) Ke

C = Sisa Tekan 10 m
B = Elevasi Desa + 40 m, dpl
DESA TAVER

Hstatik 350 m

A =+ 6 m,dpl (sumber)
SUMBER AIR MATA

1) MENGHITUNG DIMENSI PIPA


Q = KAPASITAS RENCANA 1.0 lt/det
CHw = KOEFISIEN KEKASARAN 120
HL = HEAD LOOS DALAM PIPA ? m
L = PANJANG PIPA 350 m
DIA = DIAMETER PIPA ? m
FAKTOR SATUAN 0.2785

Q = 0,2785 CHw x DIA 2,63 x (HL/L)0,54


Q = 0,2785 X 120 X DIA2,63 X H0,54/(L)0,54

TRIAL RUN DIAMETER DIDAPATKAN HEAD LOSS (HL)


Q L DIA HL v
KETERANGAN
lt/det m mm Inc mka m/det
1.0 350 500 20 0.0 0.01
1.0 350 400 16 0.0 0.01
1.0 350 300 12 0.0 0.01
1.0 350 250 10 0.0 0.02
1.0 350 200 8 0.0 0.03
1.0 350 150 6 0.0 0.06
1.0 350 100 4 0.1 0.13
1.0 350 75 3 0.4 0.23
1.0 350 50 2 3.2 0.51
1.0 350 38 1.5 12.1 0.51 PILIH *)
1.0 350 25 1 93.1 0.51

*) PILIH YANG PALING MENGUNTUNGKAN :


- BIAYA (BAHAN DAN KONSTRUKSI)
- OPERASI DAN PEMELIHARAAN, DLL
2) MENGHITUNG DAYA POMPA ( Dp )
egl
HL hgl HL
Hsisa tekan C = Sisa Tekan 3 m (Rencana)
B = Elevasi Desa + 40 m,dpl

Hp
Hstatic 350 m

A = 3 m,dpl (SUMBER)

Dp = Q x Ro x g x Hp / E

Q = KAPASITAS 1.0 l/det


~ 0.001 m3/det
Ro = MASA JENIS AIR 1000 kg/m3
g = GRAFITASI 9.8 m/det2
Hp = HEAD POMPA ? mka
E = EFFISIENSI POMPA 85 %
HLpipa= 12.1 mka (lihat perhitungan dimensi pipa)

a) HEAD POMPA

Hp = Hstatic + Hsisa tekan + HLpipa


Hp = ( Elev.Desa - ElevSumber) + Hst + HLpipa (mka)
Hp = 52.11 mka
62.54
b) DAYA POMPA

Dp = Q Ro g Hp * E

Dp = 601 Watt
Dp = 0.6 KW
B) SUMBER Mata Air (Sistim Perpompaan) Ke
C = Sisa Tekan 10 m
B = Elevasi Desa + 20 m, dpl
DESA TAVER

Hstatik 1000 m

A = + 17 m,dpl (sumber)
SUMBER AIR MATA

1) MENGHITUNG DIMENSI PIPA


Q = KAPASITAS RENCANA 1.0 lt/det
CHw = KOEFISIEN KEKASARAN 120
HL = HEAD LOOS DALAM PIPA 34.6 m
L = PANJANG PIPA 1000 m
DIA = DIAMETER PIPA 50 m
FAKTOR SATUAN 0.2785

Q = 0,2785 CHw x DIA 2,63 x (HL/L)0,54


Q = 0,2785 X 120 X DIA2,63 X H0,54/(L)0,54

TRIAL RUN DIAMETER DIDAPATKAN HEAD LOSS (HL)


Q L DIA HL v
KETERANGAN
lt/det m mm Inc mka m/det
1.0 1000 500 20 0.0 0.01
1.0 1000 400 16 0.0 0.01
1.0 1000 300 12 0.0 0.01
1.0 1000 250 10 0.0 0.02
1.0 1000 200 8 0.0 0.03
1.0 1000 150 6 0.0 0.06
1.0 1000 100 4 0.3 0.13
1.0 1000 75 3 1.3 0.23
1.0 1000 50 2 9.1 0.51
1.0 1000 38 1.5 34.6 0.51 PILIH *)
1.0 1000 25 1 266.0 0.51

*) PILIH YANG PALING MENGUNTUNGKAN :


- BIAYA (BAHAN DAN KONSTRUKSI)
- OPERASI DAN PEMELIHARAAN, DLL
2) MENGHITUNG DAYA POMPA ( Dp )
egl
HL hgl HL
Hsisa tekan C = Sisa Tekan 3 m (Rencana)
B = Elevasi Desa + 20 m,dpl

Hp
Hstatic 1000 m

A = 5 m,dpl (SUMBER)

Dp = Q x Ro x g x Hp / E

Q = KAPASITAS 1.0 l/det


~ 0.001 m3/det
Ro = MASA JENIS AIR 1000 kg/m3
g = GRAFITASI 9.8 m/det2
Hp = HEAD POMPA ? mka
E = EFFISIENSI POMPA 85 %
HLpipa= 34.6 mka (lihat perhitungan dimensi pipa)

a) HEAD POMPA

Hp = Hstatic + Hsisa tekan + HLpipa


Hp = ( Elev.Desa - ElevSumber) + Hst + HLpipa (mka)
Hp = 52.61 mka
63.13
b) DAYA POMPA

Dp = Q Ro g Hp * E

Dp = 607 Watt
Dp = 0.6 KW