Relay CT OCR
Nominal Puncak
Merk Tipe Real
Hotel Bagan ABB REF 610 100 / 5 100 80 96
Sinaboi SCHNEIDER MICOM P122 100 / 5 100 80 96
Keterangan
OCR = 1,2 x In
GFR = 0,1 x In Disesuaikan dengan setting minimum GFR relay
OCR Instan = 4,0 x In
GFR Instan = Beban Puncak Supaya tidak berpotongan dengan kurva GFR biasa
Rata - rata gangguan GFR Instan
Hotel Bagan ABB REF 610 100 / 5 100 2.00 IEC SI 0.050
MICOM
Sinaboi SCHNEIDER 100 / 5 100 1.00 IEC SI 0.025
P122
OCR INSTAN GFR GFR INSTAN
Definite Definite
8.00 0.040 10% IEC SI 0.050 50% 0.040
Time Time
Definite Definite
5.00 0.040 0.10 IEC SI 0.050 1.00 0.040
Time Time