Anda di halaman 1dari 4

FORM PEMELIHARAAN RUTIN INSTALASI LISTRIK

NAMA PROJECT Pemeliharaan Instalasi listrik


LOKASI Rumah Sakit Husada Utama
TANGGAL PEMERIKSAAN 30 Juli 2022

1. KUBIKEL 20 KV
Uraian Keterangan
Merk Schneider
No Serie CI-2020-W40-2-0001
SM 9605060
Name Plate (Function) Baik
Rated Voltage 20 kV
Rated Normal Current 630 A
Aux. Voltage 220 Volt
Anti Condensation Heater Voltage
Protection and Measurement Aux. Voltage
Opening Release Coil
 Visual Check Baik
Mechanical Components (Metals, Busbars, etc)
Electrical Component (CB, CT, VT, Relay etc)
 Mechanical Operation Test Baik
Main Switch
Earthing Switch
Interlock (Key, Door, Earthing etc)
Control Switch
 Measurement Of Main Circuit Contact Resistance Baik
 Verification Of Auxiriali Devices Operation Baik
Control Circuit
PENGUKURAN TAHANAN ISOLASI 1)
Kriteria≥1000 Ω/volt
Tegangan Uji Hasil Pengujian dan Pengukuran (Mega Ω)
R-G S-G T-G
Upper - Ground
200.000 200.000 200.000
R-G S-G T-G
Lower - Ground
200.000 200.000 200.000

2. TRAFO
Uraian Data Teknis Keterangan
Merk Trafindo
No Seri 173308231
Tahun Buatan 2017
Kapasitas ( kVA) 2500 kVA
Teg Primer (V) 20 kV
Teg Sekunder (V) 0,4 kV
Tangki utama Baik
Bushing Baik, tidak ada retak
Pentanahan Netral Baik, tersambung
Polaritas/Penandaaan urutan phasa Baik
Kekencangan Baut & mur Baik
Seal / Packing isolator Baik, tidak ada kebocoran olie
Ekspand - kran Baik dan berfungsi

PENGUJIAN KONEKSI ANTAR KUMPARAN


Kriteria Nilai = 0
Phasa-Phasa MΩ Phasa-Phasa MΩ
Kumparan R-S 0 Kumparan r–s 0
Primer S–T 0 Sekunder s –t 0
T-R 0 t-r 0

PENGUJIAN TAHANAN ISOLASI (MEGER TEST)


Kriteria≥1000 Ω/volt
Tegangan uji Terminal Test (Mega Ohm) Tegangan uji Terminal Test (Mega Ohm)
HV-E HV-LV LV-E
5000 V 1000 V
2000 2500 1000

3. LVMDP
Uraian Data Teknis Keterangan
Merk -
No Seri -
Tahun Buatan -
ACB /MCCB Schneider
Tegangan ACB/MCCB 400 Volt
Inominal ACB/MCCB 3200 ampere
Pembumian Baik

PENGUKURAN TAHANAN ISOLASI 1)


Kriteria≥1000 Ω/volt
Tegangan Uji 500 Volt Hasil Pengujian dan Pengukuran (Mega Ω)
R-G S-G T-G
Phasa - Ground
800 1000 1000
R- S S- T T- R
Phasa-phasa
1000 1000 1000

4.1. KABEL INCOMING KUBIKEL 20 KV


Uraian Data Teknis Keterangan
Merk Supreme
Line Feeder Incoming Kubikel 20 kV
Jenis N2XSY
Tegangan 24 KV
Panjang kabel , Ukuran penampang 20 Mtr, 50 mm
PENGUKURAN TAHANAN ISOLASI 1)
Kriteria≥1000 Ω/volt
Tegangan Uji 5000 V Hasil Pengujian dan Pengukuran (Mega Ω)
R-G S-G T-G
Phasa - Ground
12000 11000 12000
R- S S- T T- R
Phasa-phasa
15000 15000 15000

4.2. KABEL INCOMING TRAFO


Uraian Data Teknis Keterangan
Merk Voksel
Line Feeder Incoming Trafo
Jenis NFA2XSY-T
Ukuran penampang 150 mm
Panjang kabel 10 meter
PENGUKURAN TAHANAN ISOLASI 1)
Kriteria≥1000 Ω/volt
Tegangan Uji 5000 V Hasil Pengujian dan Pengukuran (Mega Ω)
R-G S-G T-G
Phasa - Ground
20000 21000 20000
R- S S- T T- R
Phasa-phasa
15000 15000 15000

Surabaya, 30 Juli 2022


Supervisor Teknik

Wiyanto

Anda mungkin juga menyukai