Anda di halaman 1dari 6

Nama : Yochanan Dili Forte Veyyavacca Paat

NIM : 1322136


TUGAS FISIKA BANGUNAN 1

1. MENGHITUNG TRANSMITAN DAN RESISTAN ELEMEN BANGUNAN BERLAPIS
Diketahui: - Sebuah bangunan memiliki struktur dinding bata dengan lapisan plester
- Tebal plester luar dan plester dalam masing masing (d plester) @ 2 cm
- Tebal batu bata (d bata) 8 cm
- Konduktivitas plester (k plester) 0,9 W/m
2
C
- Konduktivitas batu bata (k bata) 1,2 W/m
2
C
- Konduktan permukaan dalam dinding (f1) 8,12 W/m
2
C
Maka:
Resistan plester (R1 plester) =



=


= 0,022 m
2
C/W
Resistan Bata (R1 bata) =



=


= 0,067 m
2
C/W
Resistan Total = R1 plester + R1 bata + R1 plester
= 0,022 + 0,067 + 0,022
= 0,111 m
2
C/W

TRANSMITAN (U)
A. Dinding Barat (terlindungi)
fo = 10 W/m
2
C
Resistan dinding (R dinding barat) =

+ R total +

+ 0,111 +


= 0,334 W/m
2
C
Transmitan dinding (U dinding barat) =


= 2,994 W/m
2
C
B. Dinding Utara (normal)
fo = 18,9 W/m
2
C
Resistan dinding (R dinding utara) =

+ R total +

+ 0,111 +


= 0,123 + 0,111 + 0,052
= 0,287 W/m
2
C
Transmitan dinding (U dinding utara) =


= 3,484 W/m
2
C
C. Dinding Timur (terlindungi)
fo = 13,18 W/m
2
C
Resistan dinding (R dinding timur) =

+ R total +

+ 0,111 +


= 0,123 + 0,111 + 0,075
= 0,309 W/m
2
C
Trasmitan dinding (U dinding timur) =


= 3,236 W/m
2
C
D. Dinding Selatan (sangat terbuka)
fo = 13,18 W/m
2
C
Resistan dinding (R dinding selatan) =

+ R total +

+ 0,111 +


= 0,123 + 0,111 + 0,075
= 0,309 W/m
2
C
Trasmitan dinding (U dinding selatan) =


= 3,236 W/m
2
C

2. KENAIKKAN SUHU BENDA OLEH RADIASI MATAHARI
A. Dinding Barat
- Intensitas radiasi matahari untuk bagian barat (I) = 97 W/m
2
- Suhu dalam ruang (Ti) = 25C
- Suhu dalam ruang (To) = 30C
- Bilangan serap arbsorsi () cat putih = 0,58
- Sudut dating matahari () = 60
- Konduktan permukaan dinding bata bagian barat (fo) = 10 W/m
2
C

Maka, suhu permukaan yang terkena sinar matahari:

Ts = To + (I .

) C
I = I . cos
Ts = 30 + (97 . cos 60 .

)
= 30 + (97 .

. 0,058)
= 30 + 2,813
= 32,813 C

B. Dinding Utara
Konduktan permukaan dinding bata bagian barat (fo) = 18,9 W/m
2
C

Ts = To + (I.

) C
I = I cos
Ts = 30 + (97 . cos 60

)
= 30 + (97 .

. 0,030)
= 30 + 1,455
= 31,455 C

C. Dinding Timur
Konduktan permukaan dinding bata bagian timur (fo) = 13,18 W/m
2
C

Ts = To + (I.

) C
I = I cos
Ts = 30 + (97 . cos 60

)
= 30 + (97 .

. 0,044)
= 30 + 2,134
= 32,134 C

D. Dinding Selatan
Konduktan permukaan dinding bata bagian barat (F0) = 13,18 W/m
2
C

Ts = To + (I.

) C
I = I cos
Ts = 30 + (97 . cos 60

)
= 30 + (97 .

. 0,044)
= 30 + 2,134
= 32,134 C





3. PANAS YANG MENEMBUS ELEMEN BANGUNAN
A. Dinding Barat
U = 2,994 W/m
2
C
A = luas dinding total luas bukaan
= 48 m
2
19,2 m
2

= 28,8 m
2
T = 30 C 25 C = 5 C
Qc = A . U . T
= 28,8 m
2
. 2,994 W/m
2
C . 5 C
= 431,136 Watt

B. Dinding Utara
U = 3,484 W/m
2
C
A = 32 m
2
T = 30 C 25 C = 5 C
Qc = A . U . T
= 32 m
2
. 3,484 W/m
2
C . 5 C
= 557,44 Watt

C. Dinding Timur
U = 3,236 W/m
2
C
Luas dinding + bukaan = 48 m
2

Luas bukaan = 20% x 48
= 9,6 m
2

A = luas dinding total luas bukaan
= 48 m
2
- 9 ,6 m
2

= 38,4 m
2

t = 5 C
Qc = A . U . T
= 38,4 m
2
. 3,236 W/m
2
C . 5 C
= 621,312 Watt

D. Dinding Selatan
U = 3,236 W/m
2
C
A = 32 m
2
t = 5 C
Qc = A. U. T
= 32 m
2
. 3,236 W/m
2
C . 5 C
= 517,76 Watt





4. PANAS YANG MENEMBUS KACA
A. Dinding Barat
- Luas kaca (A) = luas bidang kaca dinding barat x luas dinding total
= 40% . 48 m
2
= 19,2 m
2

- Intensitas radiasi matahari bagian barat (I) = 97 W/m
2

- Sudut datang matahari () = 60
- Solar gaint factor () = 0,76

Qs = A . I .
= 19,2 m
2
. 97 W/m
2
. 0,76
= 1415,424 Watt

B. Dinding Timur
- Luas kaca (A) = luas bidang kaca dinding barat x luas dinding total
= 20% . 48 m
2
= 9.6 m
2

- Intensitas radiasi matahari untuk bagian barat (I) = 97 W/m
2

- Sudut datang matahari () = 60
- Solar gaint factor () = 0,76

Qs = A . I .
= 9.6 m
2
. 97 W/ m
2
. 0,76
= 707,712 Watt

5. ALIRAN UDARA UNTUK MEMBUANG PANAS (Q) DENGAN MEMPERTAHANKAN
VOLUME RUANG

- Jumlah orang (40)
- Lampu TL : 8 x 20 watt = 160 watt
- Komputer 200 watt
- LCD 400 watt
- Volume Ruang (V = 12 x 8 x 4 = 384 m
3
)

- Ti = 33C
- To = 25C (suhu yang diinginkan)

Rumus :
H = (40 x 150) + (8 x 20) + 200 + 400
= 6000 + 160 + 600
= 6760
N = H/(0,33 x V x (Ti-To)
= 6760/(0,33 x 384 x 5)
= 6760/633,6
= 10,66
Q = V . N/3600
= 384 x 10,66/3600
= 384 x 2,961
= 1.137,024

Keterangan :
Q = aliran udara untuk membuang panas
N = pergantian udara per jam
H = panas yang dipindahkan

Anda mungkin juga menyukai