PETUNJUK PENGOPERASIAN PANEL JIKA KONDISI PLN

PADAM / PHASA FAILUR DAN GENZET TIDAK MERESPON

1. PINDAHKAN POSISI SELECTOR SWITCH DI PANEL


INCOMING PLN KE POSISI “OFF”
2. PINDAHKAN POSISI SELECTOR SWITCH DI PANEL
INCOMING GENSET KE POSISI “MANUAL”
3. HIDUPKAN GENZET SECARA MANUAL SESUAI
PETUNJUK (SOP)
4. TEKAN PUSH BUTTON ON CB GENZET PADA PANEL
INCOMING GENZET ( LISTRIK AKAN DI SUPLAY
GENSET )

KONDISI PLN KEMBALI NORMAL ( TUNGGU ± 15 MENIT )


1. TEKAN PUSH BUTTON OFF CB GENZET PADA
INCOMING GENZET
2. PINDAHKAN POSISI SELECTOR SWITCH DIPANEL
INCOMING PLN KE POSISI “AUTO” ( LISTRIK AKAN
KEMBALI DISUPLAY PLN )
3. MATIKAN GENSET SECARA MANUAL
4. PINDAHKAN POSISI SELECTOR SWITCH DIPANEL
INCOMING GENZET KE POSISI “AUTO”