Pemeliharaan Trafo Distribusi
Pemeliharaan Trafo Distribusi
Distribusi
TRANSFORMATOR
TRANSFORMATOR SEBAGAI SALAH SATU PERALATAN
LISTRIK PADA DASARNYA
DALAM PENGOPERASIANYA
MEMBUTUHKAN LEBIH SEDI-
KIT PEMELIHARAAN BILA DI-
BANDINGKAN PERALATAN YG
LAINYA.
LAINYA
BESAR TINGKAT PEMELIHARA-
AN DAN PEMERIKSAAN TERGAN
TUNG PADA SEBERAPA BESAR
KAPASITAS DARI TRAFO TSB,
TINGKAT PELAYANAN BEBAN,
PENEMPATAN INSTALASI DLM
SISTEM TEMP RUANG,
SISTEM, RUANG LINGKU
NGAN DAN KONDISI OPERASI. 2
www.themegallery.com
PROSES PERJALANAN TRAFO DARI PABRIKAN
SAMPAI KONSUMEN
PABRIKAN PERJALANAN
PEMASANGAN
PERJALANAN PLN/GUDANG
O
OPERASI
S PEMELIHARAAN
3
PEMERIKSAAN TRAFO SAAT BEROPERASI
HAL – HAL YANG PERLU DIPERHATIKAN SAAT
PEMERIKSAAN TRAFO DALAM KEADAAN OPERASI
PEMERIKSAAN FISIK
PEMERIKSAA PACKING TRAFO .
PEMERIKSAAN ASSESORIS TRAFO.
PEMERIKSAAN NAME PLATE .
PERIKSA VOLUME MINYAK PADA GE
LAS DUGA (OIL LEVEL).
PERIKSA BUSHING TRAFO TM/TR.
DLL.
PEMELIHARAAN TRANSFORMATOR
PEMERIKSAAN YANG SEKSAMA PERLU DILAKUKAN U/
MENJAMIN AGAR TRAFO SELALU BERADA DALAM
KONDISI BAIK.
1 PEMERIKSAAN
S OLI
O TRANSFORMATOR
S O O
1. PEMERIKSAAN LEVEL MINYAK TRAFO
DILAKUKAN UNTUK MENGETAHUI
VOLUME MINYAK.
2. PEMERIKSAAN TEMPERATUR MINYAK
TRAFO.
PEMERIKSAAN DAN PENGAMBILAN
MINYAK TRAFO
UNTUK PELAKSANAAN
PEMERIKSAAN MINYAK
TRAFO SEBAIKNYA 3
(TIGA) TAHUN PERTAMA
SETELAH TRAFO DI-
OPERASIKAN DAN SETIAP
TAHUN UNTUK TAHUN
BERIKUTNYA.
BERIKUTNYA
HATI-HATI
CARA MENGAMBIL
DAN MEMBAWANYA
PENGAMBILAN MINYAK
2. FUNGSI MINYAK TRAFO
a. MINYAK TRAFO BERFUNGSI UNTUK
MENGISOLASI TEGANGAN ANTARA
LILITAN DGN BESI, LILITAN DENGAN
BODI DAN ANTARA BAGIAN – BAGIAN
YANG BERTEGANGAN LAINYA
LAINYA.
S
PERALATAN PENGETESAN TEGANGAN
TEMBUS MINYAK TRAFO
12
2 BREATHER (SILICA GEL)
BREATHER BERFUNGSI SEBAGAI LUBANG PERNAPASAN
TRANSFORMATOR UNTUK MENJAGA TEKANAN DALAM
TANGKI.
BREATHER DILENGKAPI DENGAN SILICA GEL
UNTUK MENYERAP KANDUNGAN UAP AIR
DALAM TRAFO
TRAFO.
MISAL :
TERMINAL BUSHING.
GROUNDING TRAFO.
HATI HATI
HATI-HATI:
SEWAKTU MENGENCANGKAN
PENJEPIT BHUSING TRAFO AGAR
DIPERIKSA RING KARET (SIL)
(SIL).
JADWAL PEMERIKSAAN / PEMELIHARAAN
BERKALA TRANSFORMATOR
No PEMERIKSAAN MINGGU BULAN TAHUN 7.TAHUN
1 NOISE
1. NOISE,SUHU/TEMP
2. FISIK TRF,VALVE
BUSHING PACKING
BUSHING,PACKING
OIL LEVEL, FAN
BUCHOLZ RELAY
3. TEG TEMBUS OIL
BREATHER/SILICA
GARDU/LINGK TRF
4. BAGIAN DLM TRF :
WINDING
CORE, PENTANAH
LEAD WIRE
TAP CHANGER 15
LANGKAH KERJA
PEMELIHARAAN TRAFO DIST
1. PERSIAPKAN PERKAKAS KERJA UNTUK PEMELIHARAAN TRAFO.
2. BEBASKAN TRAFO DAN PERALATAN LAIN DARI TEGANGAN.