Dy1
Dy1
GFR TIDAK BEKERJA
Pribadi Kadarisman
KONDUKTOR JARINGAN 20KV PUTUS DI SISI BEBAN
KHUSUS KONDUKTOR PUTUS SATU FASA DI SISI BEBAN UNTUK
NETRAL MELALUI NGR, TRAFO DISTRIBUSI CORE TYPE
SUMBER BEBAN
Dy1
G
R R R R
G S S
S S
NORMAL FASA T TRAFO DIST.
PUTUS GROUND
Pribadi Kadarisman
KONDUKTOR JARINGAN 20KV PUTUS DI SISI BEBAN
KHUSUS KONDUKTOR PUTUS SATU FASA DI SISI BEBAN UNTUK
NETRAL MELALUI NGR, TRAFO DISTRIBUSI CORE TYPE
G
R R R R
G S S
S S
FASA T DI TRAFO DISTR. MENJADI NORMAL FASA T TRAFO DIST.
BERIMPIT DENGAN POTENSIAL PUTUS GROUND
GROUND AKIBATNYA t t
BELITAN T–R BERTEGANGAN G–R
BELITAN S–T BERTEGANGAN S–G
r
SEHINGGA MENGGESER VEKTOR r
TEGANGAN r–G = 127 VOLT, s s G
TEGANGAN t–G = 127 VOLT DAN
TEGANGAN s–G = 220 VOLT
Pribadi Kadarisman
KONDUKTOR JARINGAN 20KV PUTUS DI SISI BEBAN
KHUSUS KONDUKTOR PUTUS SATU FASA DI SISI BEBAN UNTUK
NETRAL MELALUI NGR, TRAFO DISTRIBUSI CORE TYPE
G S S
S S
FASA T DI TRAFO DISTR. MENJADI NORMAL FASA T TRAFO DIST.
TERGANTUNG AKIBATNYA PUTUS TERGANTUNG
BELITAN T–R BERTEGANGAN ½ VRS t
BELITAN S–T BERTEGANGAN ½ VSR t
TEGANGAN T–G SEBESAR ½ VRG
N N r
SELANJUTNYA MENGGESER r
TEGANGAN r-G =110 VOLT, s s
G G
TEGANGAN t-G= 110 VOLT DAN
TEGANGAN s–G=220 VOLT
Pribadi Kadarisman
KONDUKTOR JARINGAN 20KV PUTUS DI SISI BEBAN
KHUSUS KONDUKTOR PUTUS SATU FASA DI SISI BEBAN UNTUK
NETRAL SOLIDLY GROUNDED, TRAFO DISTRIBUSI CORE TYPE
SUMBER BEBAN
YNyn
FR
FS FR+FS
FR+FS G G
Pribadi Kadarisman
KONDUKTOR JARINGAN 20KV PUTUS DI SISI BEBAN
KHUSUS KONDUKTOR PUTUS SATU FASA DI SISI BEBAN UNTUK
NETRAL SOLIDLY GROUNDED, TRAFO DISTRIBUSI CORE TYPE
YNyn
T T t T t
G
g g
N
R R R
r r
G G g G g
S S
s s
S
FLUKS NORMAL NORMAL FASA T TRAFO DIST.
FASA T ”TRAFO 1 FASA” PUTUS GROUND
TIDAK MENDAPAT PASOKAN,
BAIK TERHUBUNG SINGKAT R r S s T G t
KE GROUND ATAU TIDAK FR FS
SISI SEKUNDER Vt-g TIDAK
BERTEGANGAN
ALIRAN FLUKS FASA R DAN S
”TRAFO 1 FASA” TIDAK
MEMBUAT INDUKSI TEGANG-
AN KE BELITAN FASA T
g
Pribadi Kadarisman
KONDUKTOR JARINGAN 20KV PUTUS DI SISI BEBAN
KHUSUS KONDUKTOR PUTUS SATU FASA DI SISI BEBAN UNTUK NETRAL
SOLIDLY GROUNDED, TRAFO DISTRIBUSI SHELL TYPE
DARI URAIAN INI, UNTUK TRAFO DISTR. SHELL TYPE, YANG MENGALAMI
KONDUKTOR PUTUS, MENYENTUH TANAH ATAU TIDAK LEBIH AMAN
Pribadi Kadarisman
KONDUKTOR JARINGAN 20KV PUTUS DI SISI BEBAN
MENGURANGI KEMUNGKINAN PUTUSNYA KONDUKTOR JARINGAN
DISTRIBUSI.
Pribadi Kadarisman
KONDUKTOR JARINGAN 20KV PUTUS DI SISI BEBAN
MENGURANGI KEMUNGKINAN PUTUSNYA KONDUKTOR JARINGAN
DISTRIBUSI.
Pribadi Kadarisman
KONDUKTOR JARINGAN 20KV PUTUS DI SISI BEBAN
MENGURANGI DAMPAK PUTUSNYA KONDUKTOR JARINGAN DISTRIBUSI
YANG MEMBAHAYAKAN MAHLUK HIDUP.
Dy1
SAMBUNGAN
Dy1
GFR BEKERJA
Pribadi Kadarisman
TERIMA KASIH