Anda di halaman 1dari 23

Motor A (Starting Y/Δ) ¿ 41.

8 A
KHA Setelah FK = FK Total =
0.4775
Poutput = 22 kW
= 87.5473 A
Pinput = 23.9391 kW
Dipilih penghantar NYFGbY 2 x (1 x 3core x 16mm2)
cos θ = 0.87
Sutrado dengan KHA 99 A.
RPM = 1460 min-1
b. Impedansi
Pinput 23.9391 kW
In = = Jarak motor – MCC = 16.5 m
√3 . V . cos θ √ 3 . 380 V .0 .87
−8
ρ .l 1.68. 10 Ωm .16.5 m
= 41.8 A R = =
A −6 2
16 .10 m
Pinput 23.9391kW
S = = = 0.0173 Ω
cos θ 0.87
= 27.5162 kVA L = 0.255 mH/km

Q = √ S 2−Pinput 2 = √ 27.51622−23.93912 XL = 2.π.f.L = 2 . π . 50Hz . 0.255mH/km . 0.0165km . 10-3

= 13.5669 kVAR = 0.0013 Ω

a. KHA dan Luas Penghantar Karena ada 2 tarikan, maka di paralel :


R 0.0173
KHA min. = 125 % x In = 125% x 41.8 A = 52.25 Rpar = = = 0.0087 Ω
2 2
A
XL 0.0013
Faktor Koreksi Suhu = 0.87 Xpar = = = 0.0007 Ω
2 2
Faktor Koreksi Kedalaman = 0.98 Z = R + jXL = 0.0087 + j0.0007
Faktor Koreksi Resistivitas Tanah =1 = 0.0087 ∠ 4.3647º Ω
Faktor Koreksi Grouping = 0.56 c. Drop Voltage
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.56 ΔV = √ 3 . Z . In = √ 3 . (0.0087 ∠ 4.3647º) Ω . 41.8 A
= 0.4775 = 0.629 ∠ 4.3647º V
0.6290
V% = x 100%
380
= 0.1655%

d. Kontaktor dan TOR


Motor B (Starting Y/Δ)
Rating kontaktor = In
Poutput = 160 kW
Dipilih kontaktor dengan tipe Star-Delta Starter
Pinput = 167.0146 kW
LC3D80M7A64 AC 3 dengan rating 80 A dari Schneider.
cos θ = 0.87
Setting TOR yang digunakan :
RPM = 1490 min-1
TOR = 1.43 x In x = 1.43 x 41.8 A
Pinput 167.0146 kW
= A In = =
√3 . V . cos θ √ 3 . 380 V .0 .87
Thermal Protection Range 30 – 40 A dengan tipe
= 292 A
LR3D3555.
Pinput 167.0146 kW
e. Pemutus S = =
cos θ 0.87
I CB min. = 1.15 x In = 1.15 x 41.8 A = 191.9708 kVA
= 48.07 A Q = √ S 2−Pinput 2 = √ 191.97082−167.01462
I CB max = KHA penghantar yang digunakan = 94.6515 kVAR
= 99 A a. KHA dan Luas Penghantar
Dipilih MCCB Compact NSX - LV429761 dari Schneider KHA min. = 125 % x In = 125% x 292 A = 365 A
dengan rating 50 A. Faktor Koreksi Suhu = 0.87
Faktor Koreksi Kedalaman = 0.98
Faktor Koreksi Resistivitas Tanah =1 = 0.0009 ∠ 59.7337º Ω
Faktor Koreksi Grouping = 0.68 c. Drop Voltage
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.68 ΔV = √ 3 . Z . In = √ 3 . (0.0009 ∠ 59.7337º) Ω . 292 A
= 0.5798 = 0.4425 ∠ 59.7337º V
¿ 292 A 0.4425
KHA Setelah FK = FK Total = V% = x 100%
0.5798 380
= 503.6497 A = 0.1165%
Dipilih penghantar NYFGbY 2 x (1 x 3core x 400mm2)
Sutrado dengan KHA 535 A.
b. Impedansi d. Kontaktor dan TOR
Jarak motor – MCC = 21 m Rating kontaktor = In
ρ .l 1.68. 10−8 Ωm .21 m Dipilih kontaktor dengan tipe Star-Delta Starter
R = =
A 400 .10−6 m2 LC3F330M7A64 AC 3 dengan rating 330 A dari
= 0.0009 Ω Schneider.
L = 0.229 mH/km Setting TOR yang digunakan :
XL = 2.π.f.L = 2 . π . 50Hz . 0.229mH/km . 0.0210km . 10-3 1 1
TOR = 1.43 x In x = 1.43 x 292 A x
= 0.0015 Ω √3 √3
Karena ada 2 tarikan, maka di paralel : = 241.0784 A

R 0.0009 Thermal Protection Range 200 – 330 A dengan tipe


Rpar = = = 0.0004 Ω
2 2 LR9F7575.
XL 0.0015 e. Pemutus
Xpar = = = 0.0008 Ω
2 2
I CB min. = 1.15 x In = 1.15 x 292 A
Z = R + jXL = 0.0004 + j0.0008
= 355.8 A
I CB max = KHA penghantar yang digunakan = 7.5915 kVAR
= 535 A a. KHA dan Luas Penghantar
Dipilih MCCB Compact NSX - LV432950 dari Schneider KHA min. = 125 % x In = 125% x 21.9 A = 23.375
dengan rating 500 A. A
Faktor Koreksi Suhu = 0.87
Faktor Koreksi Kedalaman = 0.98
Faktor Koreksi Resistivitas Tanah =1
Faktor Koreksi Grouping = 0.64
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.64
= 0.5457
Motor C (Starting Y/Δ) ¿ 23.375 A
KHA Setelah FK = FK Total =
0.5457
Poutput = 11 kW
= 40.1346 A
Pinput = 12.2494 kW
Dipilih penghantar NYFGbY 2 x (1 x 3core x 4mm 2)
cos θ = 0.85
Sutrado dengan KHA 50 A.
RPM = 1465 min-1
b. Impedansi
Pinput 12.2494 kW
In = = Jarak motor – MCC = 16.5 m
√3 . V . cos θ √3 . 380 V .0 .85
= 21.9 A ρ .l 1.68. 10−8 Ωm .16.5 m
R = =
A 4 . 10−6 m2
Pinput 12.2494 kW
S = =
cos θ 0.85 = 0.0693 Ω
= 14.4111 kVA L = 0.303 mH/km

Q = √ S 2−Pinput 2 = √ 14.41112−12.24942 XL = 2.π.f.L = 2 . π . 50Hz . 0.303mH/km . 0.0165km . 10-3


= 0.0016 Ω
Karena ada 2 tarikan, maka di paralel : Thermal Protection Range 17 – 25 A dengan tipe
R 0.0693 LR2D3522.
Rpar = = = 0.0347 Ω
2 2 e. Pemutus
XL 0.0016 I CB min. = 1.15 x In = 1.15 x 21.9 A
Xpar = = = 0.0008 Ω
2 2
= 25.185 A
Z = R + jXL = 0.0347+ j0.0008
= 0.0347 ∠ 1.2989º Ω I CB max = KHA penghantar yang digunakan

c. Drop Voltage = 50 A

ΔV = √ 3 . Z . In = √ 3 . (0.0347 ∠ 1.2989º) Ω . 21.9 A Dipilih MCCB Compact NSX - LV429741 dari Schneider

= 1.3147 ∠ 1.2989º V dengan rating 50 A.


1.3147
V% = x 100%
380
= 0.3460%

d. Kontaktor dan TOR


Rating kontaktor = In Motor D (Starting Y/Δ)
Dipilih kontaktor dengan tipe Star-Delta Starter Poutput = 15 kW
LC3D320AM7 AC 3 dengan rating 32 A dari Schneider. Pinput = 16.5563 kW
Setting TOR yang digunakan : cos θ = 0.85
1 1
TOR = 1.43 x In x = 1.43 x 21.9 A x RPM = 1460 min-1
√3 √3
Pinput 16.5563 kW
= 18.0809 A In = =
√3 . V . cos θ √3 . 380 V .0 .85
= 29.6 A = 0.0252 Ω
Pinput 16.5563 kW L = 0.269 mH/km
S = =
cos θ 0.85
XL = 2.π.f.L = 2 . π . 50Hz . 0.269mH/km . 0.0150km . 10-3
= 19.4780 kVA
= 0.0013 Ω
Q = √ S −Pinput
2 2
= √ 19.4780 −16.5563
2 2
Karena ada 2 tarikan, maka di paralel :
= 10.2607 kVAR R 0.0252
Rpar = = = 0.0126 Ω
2 2
a. KHA dan Luas Penghantar
XL 0.0013
KHA min. = 125 % x In = 125% x 29.6 A = 37 A Xpar = = = 0.0006 Ω
2 2
Faktor Koreksi Suhu = 0.87
Z = R + jXL = 0.0126 + j0.0006
Faktor Koreksi Kedalaman = 0.98
= 0.0126 ∠ 2.8809º Ω
Faktor Koreksi Resistivitas Tanah =1
c. Drop Voltage
Faktor Koreksi Grouping = 0.56
ΔV = √ 3 . Z . In = √ 3 . (0.0126 ∠ 28809°) Ω . 29.6 A
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.56
= 0.6468 ∠ 2.8809º V
= 0.4775
0.6468
¿ 37 A V% = x 100%
KHA Setelah FK = FK Total = 380
0.4775
= 0.1702%
= 61.9952 A
Dipilih penghantar NYFGbY 2 x (1 x 3core x 10mm2)
Sutrado dengan KHA 79 A. d. Kontaktor dan TOR
b. Impedansi Rating kontaktor = In
Jarak motor – MCC = 15 m Dipilih kontaktor dengan tipe Star-Delta Starter
−8
ρ .l 1.68. 10 Ωm .15 m LC3D320AM7 AC 3 dengan rating 32 A dari Schneider.
R = =
A 10. 10−6 m2
Setting TOR yang digunakan : cos θ = 0.9
1 1 RPM = 2950 min-1
TOR = 1.43 x In x = 1.43 x 29.6 A x
√3 √3
Pinput 58.8235 kW
= 24.4381 A In = =
√3 . V . cos θ √3 . 380 V .0 .9
Thermal Protection Range 17 – 25 A dengan tipe = 99.3 A
LR2D3522.
Pinput 58.8235 kW
S = =
e. Pemutus cos θ 0.9
I CB min. = 1.15 x In = 1.15 x 29.6 A = 65.3595 kVA

= 34.04 A Q = √ S 2−Pinput 2 = √ 65.35952−58.82352

I CB max = KHA penghantar yang digunakan = 28.4895 kVAR


a. KHA dan Luas Penghantar
= 79 A
KHA min. = 125 % x In = 125% x 99.3 A = 124.125 A
Dipilih MCCB Compact NSX - LV429751 dari Schneider
Faktor Koreksi Suhu = 0.87
dengan rating 50 A.
Faktor Koreksi Kedalaman = 0.98
Faktor Koreksi Resistivitas Tanah =1
Faktor Koreksi Grouping = 0.56
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.56
= 0.4775
¿ 99.3 A
KHA Setelah FK = FK Total =
0.4775
Motor E (Starting Y/Δ)
= 207.9773 A
Poutput = 55 kW
Dipilih penghantar NYFGbY 2 x (1 x 3core x 95mm2)
Pinput = 58.8235 kW
Sutrado dengan KHA 250 A.
b. Impedansi Rating kontaktor = In
Jarak motor – MCC = 21 m Dipilih kontaktor dengan tipe Star-Delta Starter
ρ .l −8
1.68. 10 Ωm .21 m LC3D115M7A64 AC 3 dengan rating 115 A dari Schneider.
R = =
A −6 2
95 .10 m Setting TOR yang digunakan :
= 0.0037 Ω 1 1
TOR = 1.43 x In x = 1.43 x 99.3 A x
L = 0.238 mH/km √3 √3
XL = 2.π.f.L = 2 . π . 50Hz . 0.238mH/km . 0.0210km . 10-3 = 81.9832A

= 0.0016 Ω Thermal Protection Range 60 – 100 A dengan tipe


Karena ada 2 tarikan, maka di paralel : LR9F5567.
R 0.0037 e. Pemutus
Rpar = = = 0.0019 Ω
2 2
I CB min. = 1.15 x In = 1.15 x 115 A
XL 0.0016
Xpar = = = 0.0008 Ω = 114.195 A
2 2
Z = R + jXL = 0.0019 + j0.0008 I CB max = KHA penghantar yang digunakan
= 0.0020 ∠ 22.9272° Ω = 205 A
c. Drop Voltage Dipilih MCCB Compact NSX - LV430832 dari Schneider
ΔV = √ 3 . Z . In = √ 3 . (0.0020 ∠ 22.9272°) Ω . 99.3 A dengan rating 50 A.
= 0.3468 ∠ 22.9272°V
0.3468
V% = x 100%
380
= 0.0913%

d. Kontaktor dan TOR Motor F (Starting Y/Δ)


Poutput = 75 kW = 254.7355 A
Pinput = 79.6178 kW Dipilih penghantar NYFGbY 2 x (1 x 3core x 120mm2)
cos θ = 0.87 Sutrado dengan KHA 280 A.
RPM = 1480 min-1 b. Impedansi

Pinput 79.6178 kW Jarak motor – MCC = 21 m


In = =
√3 . V . cos θ √ 3 . 380 V .0 .87 ρ .l 1.68. 10−8 Ωm .21 m
R = =
= 139 A A −6 2
120 . 10 m
Pinput 79.6178 kW = 0.0029 Ω
S = =
cos θ 0.87 L = 0.233 mH/km
= 91.5148 kVA XL = 2.π.f.L = 2 . π . 50Hz . 0.233mH/km . 0.0210km . 10-3
Q = √ S 2−Pinput 2 = √ 91.51482−79.61782 = 0.0015 Ω
= 45.1215 kVAR Karena ada 2 tarikan, maka di paralel :
a. KHA dan Luas Penghantar R 0.0029
Rpar = = = 0.0015 Ω
2 2
KHA min. = 125 % x In = 125% x 139 A = 173.75
XL 0.0016
A Xpar = = = 0.0008 Ω
2 2
Faktor Koreksi Suhu = 0.87
Z = R + jXL = 0.0015 + j0.0008
Faktor Koreksi Kedalaman = 0.98
= 0.0017 ∠ 27.3499°Ω
Faktor Koreksi Resistivitas Tanah =1
c. Drop Voltage
Faktor Koreksi Grouping = 0.64
ΔV = √ 3 . Z . In = √ 3 . (0.0017 ∠ 27.6123°)Ω . 139 A
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.64
= 0.3994 ∠ 27.6123°V
= 0.5457
0.3994
¿ 139 A V% = x 100%
380
KHA Setelah FK = FK Total =
0.5457
= 0.1051%

d. Kontaktor dan TOR Motor G (Starting Y/Δ)


Rating kontaktor = In Poutput = 90 kW
Dipilih kontaktor dengan tipe Star-Delta Starter Pinput = 95.2381 kW
LC3D150M7A64 AC 3 dengan rating 150 A dari Schneider. cos θ = 0.88
Setting TOR yang digunakan : RPM = 1480 min-1
1 1
TOR = 1.43 x In x = 1.43 x 139 A x Pinput 95.2381 kW
√3 √3 In =
√3 . V . cos θ
=
√ 3 . 380 V .0 .88
= 114.7599 A
= 164 A
Thermal Protection Range 90 – 150 A dengan tipe Pinput 95.2381 kW
S = =
LR9F5569. cos θ 0.88
e. Pemutus = 108.2251 kVA
I CB min. = 1.15 x In = 1.15 x 139 A Q = √ S 2−Pinput 2 = √ 108.22512−95.23812
= 159.85 A = 51.4041 kVAR
I CB max = KHA penghantar yang digunakan a. KHA dan Luas Penghantar
KHA min. = 125 % x In = 125% x 164 A = 205 A
= 280 A
Faktor Koreksi Suhu = 0.87
Dipilih MCCB Compact NSX - LV431752 dari Schneider
Faktor Koreksi Kedalaman = 0.98
dengan rating 220 A.
Faktor Koreksi Resistivitas Tanah =1
Faktor Koreksi Grouping = 0.68
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.68 ΔV = √ 3 . Z . In = √ 3 . (0.0015 ∠ 33.1777°)Ω . 139 A
= 0.5798 = 0. 4276 ∠ 33.1777° V
¿ 164 A 0.4276
KHA Setelah FK = FK Total = V% = x 100%
0.5798 380
= 282.8718 A = 0.1125%
Dipilih penghantar NYFGbY 2 x (1 x 3core x 150mm2)
Sutrado dengan KHA 315 A. d. Kontaktor dan TOR
b. Impedansi Rating kontaktor = In
Jarak motor – MCC = 22.5 m Dipilih kontaktor dengan tipe Star-Delta Starter
−8
ρ .l 1.68. 10 Ωm .22.5 m LC3F185M7A64 AC 3 dengan rating 185 A dari Schneider.
R = =
A 150. 10−6 m2 Setting TOR yang digunakan :
= 0.0025 Ω 1 1
TOR = 1.43 x In x = 1.43 x 164 A x
L = 0.233 mH/km √3 √3
XL = 2.π.f.L = 2 . π . 50Hz . 0.233mH/km . 0.0225km . 10-3 = 135.4002 A
= 0.0016 Ω Thermal Protection Range 90 – 150 A dengan tipe
Karena ada 2 tarikan, maka di paralel : LR9F5569.
R 0.0025 e. Pemutus
Rpar = = = 0.0013 Ω
2 2
I CB min. = 1.15 x In = 1.15 x 164 A
XL 0.0016
Xpar = = = 0.0008 Ω = 188.6 A
2 2
Z = R + jXL = 0.0013 + j0.0008 I CB max = KHA penghantar yang digunakan
= 0.0015 ∠ 33.1777°Ω = 315 A
c. Drop Voltage
Dipilih MCCB Compact NSX - LV431752 dari Schneider Faktor Koreksi Suhu = 0.87
dengan rating 220 A. Faktor Koreksi Kedalaman = 0.98
Faktor Koreksi Resistivitas Tanah =1
Faktor Koreksi Grouping = 0.68
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.68
= 0.5798
¿ 85.4 A
KHA Setelah FK = FK Total =
0.5798
Motor H (Starting Y/Δ)
= 147.3003 A
Poutput = 45 kW
Pinput = 48.3351 kW Dipilih penghantar NYFGbY 2 x (1 x 3core x 50mm2)
Sutrado dengan KHA 165 A.
cos θ = 0.86
b. Impedansi
RPM = 1470 min-1
Jarak motor – MCC = 22.5 m
Pinput 48.3351 kW
In = = ρ .l −8
1.68. 10 Ωm .22.5 m
√3 . V . cos θ √3 . 380 V .0 .86 R = =
A 50 .10−6 m2
= 85.4 A
= 0.0076 Ω
Pinput 48.3351 kW
S = =
cos θ 0.86 L = 0.247 mH/km
= 56.2036 kVA XL = 2.π.f.L = 2 . π . 50Hz . 0.247mH/km . 0.0225km . 10-3

Q = √ S 2−Pinput 2 = √ 56.20362−48.33512 = 0.0017 Ω

= 28.6804 kVAR Karena ada 2 tarikan, maka di paralel :


R 0.0076
a. KHA dan Luas Penghantar Rpar = = = 0.0038 Ω
2 2
KHA min. = 125 % x In = 125% x 85.4 A = 106.75
A
XL 0.0017 = 98.21 A
Xpar = = = 0.0009 Ω
2 2
I CB max = KHA penghantar yang digunakan
Z = R + jXL = 0.0038 + j0.0009
= 0.0039 ∠ 13.0092° Ω = 165 A
Dipilih MCCB Compact NSX - LV430832 dari Schneider
c. Drop Voltage
dengan rating 150 A.
ΔV = √ 3 . Z . In = √ 3 . (0.0039 ∠ 13.0092°) Ω . 85.4 A
= 0.5739 ∠ 13.0092°V
0.5739
V% = x 100%
380
= 0.1510%

Motor I (Starting Y/Δ)


d. Kontaktor dan TOR
Poutput = 5.5 kW
Rating kontaktor = In
Pinput = 6.2714 kW
Dipilih kontaktor dengan tipe Star-Delta Starter
LC3D115M7A64 AC 3 dengan rating 115 A dari Schneider. cos θ = 0.88

Setting TOR yang digunakan : RPM = 1455 min-1


1 1 Pinput 6.2714 kW
TOR = 1.43 x In x = 1.43 x 85.4 A x In = =
√3 √3 √3 . V . cos θ √ 3 . 380 V .0 .88
= 70.5072 A = 10.8 A
Thermal Protection Range 60 – 100 A dengan tipe Pinput 6.2714 kW
S = =
cos θ 0.88
LR9F5567.
= 7.1266 kVA
e. Pemutus
Q = √ S 2−Pinput 2 = √ 7.12662−6.2714 2
I CB min. = 1.15 x In = 1.15 x 85.4 A
= 3.3849 kVAR R 0.1848
Rpar = = = 0.0924 Ω
2 2
a. KHA dan Luas Penghantar
XL 0.0017
KHA min. = 125 % x In = 125% x 10.8 A = 13.5 A Xpar = = = 0.0009 Ω
2 2
Faktor Koreksi Suhu = 0.87 Z = R + jXL = 0.0924 + j0.0009
Faktor Koreksi Kedalaman = 0.98 = 0.0924 ∠ 0.5273°Ω
Faktor Koreksi Resistivitas Tanah =1
c. Drop Voltage
Faktor Koreksi Grouping = 0.64
ΔV = √ 3 . Z . In = √ 3 . (0.0924 ∠ 0.5273°) Ω . 10.8 A
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.64
= 1.7285 ∠ 0.5273°V
= 0.5457 1.7285
V% = x 100%
¿ 10.8 A 380
KHA Setelah FK = FK Total =
0.5457
= 0.4549%
= 19.7924 A
Dipilih penghantar NYFGbY 2 x (1 x 3core x 1.5mm 2)
d. Kontaktor dan TOR
Sutrado dengan KHA 30 A.
Rating kontaktor = In
b. Impedansi
Dipilih kontaktor dengan tipe Star-Delta Starter
Jarak motor – MCC = 16.5 m
LC3D180AM7 AC 3 dengan rating 18 A dari Schneider.
−8
ρ .l 1.68. 10 Ωm .16.5 m
R = = Setting TOR yang digunakan :
A −6 2
1.5. 10 m
1 1
= 0.1848 Ω TOR = 1.43 x In x = 1.43 x 10.8 A x
√3 √3
L = 0.328 mH/km = 8.9166 A
XL = 2.π.f.L = 2 . π . 50Hz . 0.328mH/km . 0.0225km . 10 -3
Thermal Protection Range 7 – 10 A dengan tipe LRD14L.
= 0.0017 Ω
e. Pemutus
Karena ada 2 tarikan, maka di paralel :
I CB min. = 1.15 x In = 1.15 x 10.8 A = 27.5162 kVA
= 12.42 A Q = √ S 2−Pinput 2 = √ 27.51622−23.93912
I CB max = KHA penghantar yang digunakan = 13.5669 kVAR
a. KHA dan Luas Penghantar
= 30 A
KHA min. = 125 % x In = 125% x 41.8 A = 52.25
Dipilih MCCB Compact NSX - LV429742 dari Schneider
A
dengan rating 25 A.
Faktor Koreksi Suhu = 0.87
Faktor Koreksi Kedalaman = 0.98
Faktor Koreksi Resistivitas Tanah =1
Faktor Koreksi Grouping = 0.56
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.56
= 0.4775
¿ 41.8 A
KHA Setelah FK = FK Total =
Motor J (Starting Y/Δ) 0.4775

Poutput = 22 kW = 87.5473 A

Pinput = 23.9391 kW Dipilih penghantar NYFGbY 2 x (1 x 3core x 16mm2)


Sutrado dengan KHA 99 A.
cos θ = 0.87
b. Impedansi
RPM = 1460 min-1
Jarak motor – MCC = 16.5 m
Pinput 23.9391 kW
In = = ρ .l 1.68. 10−8 Ωm .16.5 m
√3 . V . cos θ √ 3 . 380 V .0 .87 R = =
A 16 .10−6 m2
= 41.8 A
= 0.0173 Ω
Pinput 23.9391kW
S = = L = 0.255 mH/km
cos θ 0.87
XL = 2.π.f.L = 2 . π . 50Hz . 0.255mH/km . 0.0165km . 10-3 = 34.5105 A
= 0.0013 Ω Thermal Protection Range 30 – 40 A dengan tipe
Karena ada 2 tarikan, maka di paralel : LR3D3555.

R 0.0173 e. Pemutus
Rpar = = = 0.0087 Ω
2 2 I CB min. = 1.15 x In = 1.15 x 41.8 A
XL 0.0013
Xpar = = = 0.0007 Ω = 48.07 A
2 2
Z = R + jXL = 0.0087 + j0.0007 I CB max = KHA penghantar yang digunakan

= 0.0087 ∠ 4.3647º Ω = 99 A
c. Drop Voltage Dipilih MCCB Compact NSX - LV429761 dari Schneider
ΔV = √ 3 . Z . In = √ 3 . (0.0087 ∠ 4.3647º) Ω . 41.8 A dengan rating 50 A.
= 0.629 ∠ 4.3647º V
0.6290
V% = x 100%
380
= 0.1655%

d. Kontaktor dan TOR


Motor K (Starting Y/Δ)
Rating kontaktor = In
Poutput = 110 kW
Dipilih kontaktor dengan tipe Star-Delta Starter
Pinput = 116.0338 kW
LC3D80M7A64 AC 3 dengan rating 80 A dari Schneider.
cos θ = 0.9
Setting TOR yang digunakan :
RPM = 1460 min-1
1 1
TOR = 1.43 x In x = 1.43 x 41.8 A x
√3 √3
Pinput 116.0338 kW ρ .l −8
1.68. 10 Ωm .15 m
In = = R = =
√3 . V . cos θ √3 . 380 V .0 .9 A −6 2
240. 10 m
= 196 A = 0.0011 Ω
Pinput 116.0338 kW L = 0.232 mH/km
S = =
cos θ 0.9
XL = 2.π.f.L = 2 . π . 50Hz . 0.232mH/km . 0.0150km . 10-3
= 128.9264 kVA
= 0.0011 Ω
Q = √ S 2−Pinput 2 = √ 128.92642−116.0338
Karena ada 2 tarikan, maka di paralel :
= 56.1977 kVAR R 0.0011
Rpar = = = 0.0005 Ω
a. KHA dan Luas Penghantar 2 2

KHA min. = 125 % x In = 125% x 196 A = 245 A XL 0.0011


Xpar = = = 0.0005 Ω
2 2
Faktor Koreksi Suhu = 0.87
Z = R + jXL = 0.0005 + j0.0005
Faktor Koreksi Kedalaman = 0.98
= 0.0008 ∠ 46.1682ºΩ
Faktor Koreksi Resistivitas Tanah =1
c. Drop Voltage
Faktor Koreksi Grouping = 0.68
ΔV = √ 3 . Z . In = √ 3 . (0.0008 ∠ 46.1682º) Ω . 196 A
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.68
= 0.5798 = 0.2574 ∠ 46.1682º V

¿ 196 A 0.2574
KHA Setelah FK = FK Total = V% = x 100%
0.5798 380
= 338.0663 A = 0.0677%

Dipilih penghantar NYFGbY 2 x (1 x 3core x 240mm2)


Sutrado dengan KHA 415 A. d. Kontaktor dan TOR

b. Impedansi Rating kontaktor = In

Jarak motor – MCC = 15 m


Dipilih kontaktor dengan tipe Star-Delta Starter Poutput = 11 kW
LC3F265M7A64 AC 3 dengan rating 265 A dari Pinput = 12.2494 kW
Schneider. cos θ = 0.85
Setting TOR yang digunakan : RPM = 1465 min-1
1 1
TOR = 1.43 x In x = 1.43 x 196 A x Pinput 12.2494 kW
√3 √3 In =
√3 . V . cos θ
=
√3 . 380 V .0 .85
= 161.8197 A
= 21.9 A
Thermal Protection Range 132 – 220 A dengan tipe Pinput 12.2494 kW
S = =
LR9F5571. cos θ 0.85
e. Pemutus = 14.4111 kVA

I CB min. = 1.15 x In = 1.15 x 196 A Q = √ S 2−Pinput 2 = √ 14.41112−12.24942


= 225.4 A = 7.5915 kVAR

I CB max = KHA penghantar yang digunakan a. KHA dan Luas Penghantar


KHA min. = 125 % x In = 125% x 21.9 A = 23.375
= 415 A
A
Dipilih MCCB Compact NSX - LV432750 dari Schneider
Faktor Koreksi Suhu = 0.87
dengan rating 320 A.
Faktor Koreksi Kedalaman = 0.98
Faktor Koreksi Resistivitas Tanah =1
Faktor Koreksi Grouping = 0.64
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.64
= 0.5457
¿ 23.375 A
Motor L (Starting Y/Δ) KHA Setelah FK = FK Total =
0.5457
= 40.1346 A = 0.3145%
Dipilih penghantar NYFGbY 2 x (1 x 3core x 4mm 2)
Sutrado dengan KHA 50 A. d. Kontaktor dan TOR
b. Impedansi Rating kontaktor = In
Jarak motor – MCC = 15 m Dipilih kontaktor dengan tipe Star-Delta Starter
ρ .l 1.68. 10−8 Ωm .15 m LC3D320AM7 AC 3 dengan rating 32 A dari Schneider.
R = =
A −6 2
4 . 10 m Setting TOR yang digunakan :
= 0.0630 Ω 1 1
TOR = 1.43 x In x = 1.43 x 21.9 A x
L = 0.303 mH/km √3 √3
XL = 2.π.f.L = 2 . π . 50Hz . 0.303mH/km . 0.0150km . 10-3 = 18.0809 A

= 0.0014 Ω Thermal Protection Range 17 – 25 A dengan tipe


LR2D3522.
Karena ada 2 tarikan, maka di paralel :
e. Pemutus
R 0.0630
Rpar = = = 0.0315 Ω
2 2 I CB min. = 1.15 x In = 1.15 x 21.9 A
XL 0.0014 = 25.185 A
Xpar = = = 0.0007 Ω
2 2
I CB max = KHA penghantar yang digunakan
Z = R + jXL = 0.0315 + j0.0007
= 0.0315 ∠ 1.2989º Ω = 50 A

c. Drop Voltage Dipilih MCCB Compact NSX - LV429751 dari Schneider

ΔV = √ 3 . Z . In = √ 3 . (0.0315 ∠ 1.2989º) Ω . 21.9 A dengan rating 50 A.

= 1.1952 ∠ 1.2989º V
1.1952
V% = x 100%
380
= 0.0460 Ω
L = 0.255 mH/km
XL = 2.π.f.L
a. Penghantar Cabang 2
KHA min. = (1.25 x In motor C) + In motor I = 2 . π . 50Hz . 0.255mH/km . 0.0438km . 10-3
= (1.25 x 21.9 A) + 10.8 A = 0.0035 Ω
= 38.175 A Z = R + jXL = 0.0460 + j0.0035
Faktor Koreksi Suhu = 0.87 = 0.0461 ∠ 4.3647º Ω
Faktor Koreksi Kedalaman = 0.98 Drop Voltage
Faktor Koreksi Resistivitas Tanah =1 ΔV = √ 3 . Z . In = √ 3 . (0.0461 ∠ 4.3467º) Ω . 38.175 A
Faktor Koreksi Grouping = 0.64
= 3.0498 ∠ 4.3467º V
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.64
3.0498
= 0.5457 V% = x 100%
380
KHA min . = 0.8026%
KHA Setelah FK =
FK Total
38.175 A
= b. Penghantar Cabang 1
0.5457
= 69.9606 A KHA min. = In motor D + In motor E + In motor F

Dipilih penghantar NYFGbY 1 x 4core x 16mm2 Sutrado + In motor G + In motor H + In motor

dengan KHA 89 A. L

Jarak Antar SSDB – SDB = 43.8 m + KHA min. cabang 2


= 29.6 A + 99.3 A + 139 A + 164 A +
ρ .l 1.68. 10−8 Ωm . 43.8 m
R = =
A −6 2
16 .10 m 85.4 A + 21.9 A + 38.175 A
= 577.375 A R 0.0032
Rpar = = = 0.0011 Ω
3 3
Faktor Koreksi Suhu = 0.87
XL 0.0033
Faktor Koreksi Kedalaman = 0.98 Xpar = = = 0.0011 Ω
3 3
Faktor Koreksi Resistivitas Tanah =1
Z = R + jXL = 0.0011 + j0.0011
Faktor Koreksi Grouping = 0.56
= 0.0015 ∠ 46.1682º Ω
Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.56
= 0.4775
Drop Voltage
KHA min .
KHA Setelah FK = ΔV = √ 3 . Z . In
FK Total
577.375 A = √ 3 . (0.0015 ∠ 46.1682°) Ω . 577.375 A
=
0.4775 = 1.5364 ∠ 46.1682º V
= 1209.2737 A
1.5364
V% = x 100%
Dipilih penghantar NYFGbY 3 x (1 x 4core x 240mm ) 2
380
Sutrado dengan KHA 1245 A. = 0.4043%
Jarak Antar SDB – MCC = 45.6 m
ρ .l −8
1.68. 10 Ωm . 45.6 m c. Penghantar Cabang Utama
R = =
A 240 .10−6 m2 Stotal beban = 752.2757 kVA
= 0.0032 Ω (perhitungan di bagian Transformator)
L = 0.269 mH/km Cadangan 20 % = 20% x 752.2757 kVA
XL = 2.π.f.L = 150.4551 kVA
= 2 . π . 50Hz . 0.269mH/km . 0.0456km . 10-3 Stotal = Stotal beban + Cadangan 20%
= 0.0033 Ω = 752.2757 kVA + 150.4551 kVA
Karena ada 3 tarikan, maka di paralel : = 902.7309 kVA
Tegangan LV trafo = 380 V XL = 2.π.f.L
S total x 1000 = 2 . π . 50Hz . 0.264mH/km . 0.008km . 10-3
Arus sisi LV =
√ 3 .V LV Trafo = 0.0001 Ω
902.7309 kVA x 1000 Karena ada 8 tarikan, maka di paralel :
=
√3 . 380V R 0.0011
= 1371.5577 A Rpar = = = 0.0001 Ω
8 8
Faktor Koreksi Suhu = 0.87 XL 0.0001
Xpar = = = 0.00001 Ω
Faktor Koreksi Kedalaman = 0.98 8 8

Faktor Koreksi Resistivitas Tanah =1


Faktor Koreksi Grouping = 0.71 Z = R + jXL = 0.0001 + j0.000001

Faktor Koreksi Total = 0.87 x 0.98 x 1 x 0.71 = 0.0001 ∠ 3.4301º Ω

= 0.6053 Drop Voltage


Arus LV Trafo ΔV = √ 3 . Z . In
KHA Setelah FK =
FK Total = √ 3 . (0.0001 ∠ 3.4301º) Ω . 1371.5577 A
1371.5577 A = 0.3332 ∠ 3.4301º V
=
0.6053
0.3332
= 2265.7417 A V% = x 100%
380
Dipilih penghantar NYY 8 x 3 x (1 x 1 Core x 120mm²) = 0.0877%
Sutrado disusun secara trifoil dengan KHA 2550 A.
Jarak MCC – Trafo =8m
ρ .l 1.68. 10−8 Ωm .8 m
R = =
A 120 .10−6 m2
= 0.0011 Ω
L = 0.267 mH/km

Anda mungkin juga menyukai