Anda di halaman 1dari 15

WORKING REPORT

No : 496/GBU-ASS/WR-SUJ/VIII/18

TO : FROM :
Bpk. Gito / Bpk. Budi PT. Genindo Berkat Utama
COMPANY : DATE:
PT. Sentra Usahatama Jaya 06 Agustus 2018
PHONE NUMBER : TOTAL NO PAGES INCLUDING COVER

ADDRESS : SENDER’S REFERENCE NUMBER :


Kawasan Industri Krakatau Steel, Cilegon 0

Subject : Laporan Pekerjaan Major Overhaull Unit Genset no. 1 PT. Sentra
Usahatama Jaya.
Pelaksaanaan : Tgl 3 - 7 Juli 2018. 9 – 16 Juli 2018. 23, 25, 26 Juli 2018
Teknisi : Aris Setiawan, Puji Mulyanto, Purwanto, Septo Waluyo.

Hasil laporan :

1. Spesifikasi Genset

UNIT DG TYPE GENSET S/N


1 Mitsubishi S16R-PTA-S 16178

2. Resume Pekerjaan
2.1. Service Maintenance Genset
Pekerjaan yang dilakukan :
 Selasa, Tgl 03 Juli 2018
- Menguras Air Radiator
- Melepas Kabel Battery
- Melepas Bagian Cylinder Head
- Melepas Cover Rocker Arm
- Melepas Bagian Cylinder Head 8 buah

 Rabu, Tgl 04 Juli 2018


- Melepas Bagian Cylinder Head 8 buah
- Melepas Unit Water Pump
- Melepas Piston 16 buah
- Melepas Liner 8 buah
- Melepas Oil Pan
 Kamis, Tgl 05 Juli 2018
- Melepas Liner 8 buah
- Melepas Main Bearing 4 buah
- Membersihkan (Clean Up) Water Pump
- Membersihkan (Clean Up) Liner + Piston + Cylinder Head
- Membersihkan (Clean Up) Crank Case
- Membersihkan (Clean Up) Liner 16 buah

 Jumat, Tgl 06 Juli 2018


- Membersihkan (Clean Up) Piston + Conrod
- Membersihkan (Clean Up) Cylinder Head
- Membersihkan (Clean Up) Rocker Case
- Membersihkan (Clean Up) Cover Oil Pan
- Membongkar dan membersihkan (Repair & Clean Up) Cylinder Head

 Sabtu, Tgl 07 Juli 2018


- Membongkar Cylinder Head
- Instal Piston 100%
- Membersihkan (Clean Up) Cylinder Head
- Instal Valve 80%
- Membersihkan (Clean Up) Cylinder Head
 Senin, Tgl 09 Juli 2018
- Instal Valve
- Membongkar Nozzle (Terjadi Kerusakan pada Body Holder Nozzle 16 Pcs Rusak)
- Mengganti Coupling Turbo
- Membersihkan (Clean Up) Baut Cylinder Head
- Instal Main Bearing 4 Unit
 Selasa, Tgl 10 Juli 2018
- Instal Main Bearing
 Service Generator
- Melepas Kabel Power
- Melepas Exciter Stator
- Melepas Unit Generator dari Engine Unit
- Membersihkan (Clean Up) Unit Generator
- Melepas Rotor dari Stator

 Rabu, Tgl 11 Juli 2018


- Menginstal Liner
- Menginstal Piston
 Service Generator
- Membersihkan (Clean Up) Unit Generator
- Revarnis Unit Generator
- Reheating Unit Generator
- Mengganti Bearing FAG 6315ZZ
 Kamis, Tgl 12 Juli 2018
- Memasang Cylinder Head
- Memasang Manipold Exhaust
 Service Generator
- Memasang Unit Generator to Engine
- Mager Test Unit
- Memasang Kabel Power

 Jumat, Tgl 13 Juli 2018


- Memasang Manipold Exhaust
- Memasang Cover Rocker Case

 Sabtu, Tgl 14 Juli 2018


- Memasang Rocker Arm
- Memasang Oil Pan
- Memasang Filter Udara
- Memasang Cover Manipold Exhaust

 Senin, Tgl 16 Juli 2018


- Memasang Motor Stater
- Adjust Valve
- Pengisian Air Radiator
- Pengecekan Kebocoran Engine (OK)
- Membersihkan (Clean Up) Area

 Kamis, Tgl 23 Agustus 2018


- Membersihkan (Clean Up) Body Nozzle 7 Bh

 Jumat, Tgl 24 Agustus 2018


- Memasang Seat Pipe
- Memasang Nozzle 100%
- Memasang Filter Oli
- Memasang Filter Oli By Pass
- Memasang Filter Solar
- Memasang Filter Water Sparator
- Memasang Cover Radiator
 Sabtu, Tgl 25 Agustus 2018
- Pengisian Oli
- Pemeriksaan Kesiapan Genset
- Membersihkan (Clean Up) Genset
- Test Running Tanpa Beban
- Pemeriksaan Parameter Genset

 Minggu, 26 Agustus 2018


- Test Load Genset No 1 di beban
18% = 229 Kw
42% = 519 Kw
74% = 914 Kw
82% = 1010 Kw
- Report terlampir pada lembar Load
(Genset No.1- S/N = 16178, kondisi baik/ Normal ) Hour meter : 7204,47
No RINCIAN STANDAR HASIL KETERANGAN
1 Test lamp Menyala Menyala Normal
2 Engine 1500 Rpm/ 1496 Rpm/ Normal
Speed/Frequensi 50 Hz 49,9 Hz
3 Engine Oil Pressure 5-9,5 (Bar) 7,37 Bar Normal
At Rated speed
4 Coolant Temperature 70 – 90 ºC 44 ºC Normal
5 Battery Voltage 24 – 30 Volt 26,5 Volt Normal
6 Belt tension 10 – 15 mm 10 mm Normal

3. Kesimpulan
- Genset dalam kondisi Baik / Normal
- Genset dalam posisi Standby / Auto
- Test Running baik

4. Saran.
- Perlu dilakukan pengecekan secara berkala
1 . Cek level solar di tank harian
2. Katup / valve solar masuk dan keluar dalam posisi terbuka
Project : PT. Sentra Usahatama Jaya

Lokasi : Cilegon, Serang

Pekerjaan : Repair Generator Genset Mitsubishi No. 1


Project : PT. Sentra Usahatama Jaya

Lokasi : Cilegon, Serang

Pekerjaan : Major Overhaull Unit Genset no. 1