Prosedur Kalibrasi Differential Pressure Transmitter

Prepare by : Checked by : YS Approved by : Approved by :


Eko Sugianto Kiki Anugraha Arief Afandi
Prosedur Kalibrasi Differential Pressure Transmitter [REV.01]

Sistem : Orifice Gas Metering


Lokasi : CPP Gundih
Tag Number :-
Brand : Yokogawa
Model : EJX-110A
-----------------------------------------------------------------------------------------------------------------------------------------------------------
Referensi
1. Yokogawa EJX-110A Manual
2. Rosemount Hard CommunicatorManual
-----------------------------------------------------------------------------------------------------------------------------------------------------------
Peralatan
1. Obeng plus kecil
2. Kunci Pas
3. Multimeter Digital (Certified)
4. HART Communicator
5. Resistor 250 Ohm
6. Diff. Pressure Injector (Certified)
-----------------------------------------------------------------------------------------------------------------------------------------------------------
Prosedur kalibrasi Differential Pressure Transmitter harus digunakan sebelum melakukan proses kalibrasi. Proses
kalibrasi Differential. Pressure Transmitter dilakukan dengan 2 tahapan, yaitu tahap kalibrasi input sensor Diff.
Pressure Tansmitter dan tahap kalibrasi analog output Diff. Pressure Tansmitter.

Uraian masing-masing tahap dijelaskan sebagai berikut:

1. Kalibrasi Input Sensor Diff. Pressure Tansmitter


Tahapan ini meliputi (diagram alir - Lampiran A) :
 Memastikan bahwa stream yang akan dikalibrasi sedang tidak mengalirkan gas (valve stream tertutup). Jika
hanya ada satu stream, memastikan tidak ada kebocoran pada Diff. Pressure Transmitter Valve.
 Mengkoneksikan HART Communicator dan Multimeter seperti pada gambar Lampiran C.
 Melakukan tes input Diff. Pressure Tansmitter dengan menggunakan bantuan alat kalibrasi Diff. Pressure
Injector dengan memberikan actual Diff. Pressure (Zero, 25% of span, 50% of span, 75% of span dan full span).
 Melakukan pencatatan analog outpput (4-20mA) sebelum kalibrasi dengan step naik serta step turun.
 Melakukan setting Range (sesuai design proses di lapangan)
 Melakukan setting Zero (dengan memberikan actual Diff. Pressure zero dengan Diff. Pressure Injector )
 Melakukan setting Full Span (dengan memberikan actual Diff. Pressure full span dengan Diff. Pressure
Injector)
 Melakukan tes input Diff. Pressure transmitter dengan menggunakan bantuan alat kalibrasi Diff. Pressure
Injector dengan memberikan actual Diff. Pressure (Zero, 25% of span, 50% of span, 75% of span dan full span).
 Melakukan pencatatan analog outpput (4-20mA) hasil kalibrasi dengan step naik serta step turun.

2. Kalibrasi Analog Output Diff. Pressure Transmitter


Tahapan ini meliputi (diagram alir - Lampiran B) :
 Dengan menggunakan HART Communicator melakukan D/A Trim untuk Zero (4 mA).
 Menyamakan besaran 4 mA antara Diff. Pressure Transmitter dengan Multimeter Standard (Pembanding).
 Dengan menggunakan HART Communicator melakukan D/A Trim untuk Full Span (20 mA).
 Menyamakan besaran 20 mA antara Diff. Pressure Transmitter dengan Multimeter Standard (Pembanding).
 Melakukan pencatatan hasil kalibrasi (analog output / 4-20 mA) dengan step naik serta step turun.

PT. Yuan Sejati Page 2 of 5


Kompleks Fatmawati Mas Blok II No.221
Jl. RS Fatmawati No. 20, Jakarta 12430 Indonesia
Phone: +62 21 7654968, Fax: +62 21 7654967
www.yuansejati.co.id
Prosedur Kalibrasi Differential Pressure Transmitter [REV.01]

Lampiran A

Start

Current Stream N
Vlave Close?

Close Current Stream Valve


Y
Connect HART Communicator And
Multimeter Standard

Set Diff. Pressure Injector To Diff.


Pressure Transmitter Transducer Input

Set Diff. Pressure Injector To 25%, 50%,


75% And 100%
Set Up And Down

Record As Found

Set Calibration Range

Set Diff. Pressure Injector To Zero


And Adjust Zero Condition Using
HART Communication

Set Diff. Pressure Injector To Span


And Adjust Span Condition Using
HART Communication

Set Diff. Pressure Injector To 25%, 50%,


75% And 100%
Set Up And Down

Create Calibration Report

End

Gambar 1 : Diagram Alir A

PT. Yuan Sejati Page 3 of 5


Kompleks Fatmawati Mas Blok II No.221
Jl. RS Fatmawati No. 20, Jakarta 12430 Indonesia
Phone: +62 21 7654968, Fax: +62 21 7654967
www.yuansejati.co.id
Prosedur Kalibrasi Differential Pressure Transmitter [REV.01]

Lampiran B

Start

Current Stream N
Vlave Close?

Close Current Stream Valve


Y
Connect HART Communicator And
Multimeter Standard

Set Diff. Pressure Injector To Diff.


Pressure Transmitter Transducer Input

Set Diff. Pressure Injector To 25%, 50%,


75% And 100%
Set Up And Down

Record As Found

Set Calibration Range

Set Diff. Pressure Injector To Zero


Adjust D/A Trim Zero Condition Using
HART Communication

Set Diff. Pressure Injector To Span


Adjust D/A Trim Span Condition Using
HART Communication

Set Diff. Pressure Injector To 25%, 50%,


75% And 100%
Set Up And Down

Create Calibration Report

End

Gambar 2 : Diagram Alir B

PT. Yuan Sejati Page 4 of 5


Kompleks Fatmawati Mas Blok II No.221
Jl. RS Fatmawati No. 20, Jakarta 12430 Indonesia
Phone: +62 21 7654968, Fax: +62 21 7654967
www.yuansejati.co.id
Prosedur Kalibrasi Differential Pressure Transmitter [REV.01]

Lampiran C

Diff. Pressure Transmitter

Source [+] 250 Ohm

Source [-]
Barrier,
Arrester,
etc Fluks 744

HART Communicator Measure


Panel Side Field Side

Gambar 3 : Wiring Diagram

PT. Yuan Sejati Page 5 of 5


Kompleks Fatmawati Mas Blok II No.221
Jl. RS Fatmawati No. 20, Jakarta 12430 Indonesia
Phone: +62 21 7654968, Fax: +62 21 7654967
www.yuansejati.co.id

Anda mungkin juga menyukai