STANDAR SPLN S5.003-1: 2014


Lampiran Keputusan Direksi
PT PLN (PERSERO)   PT PLN (Persero) No. 0952.K/DIR/2014 

TELEINFORMASI DATA DAN TAMPILAN


UNTUK SISTEM OTOMASI GARDU INDUK
Bagian 1:
FUNGSI OPERASI

PT PLN (Persero)
Jl. Trunojoyo Blok M-1/135 Kebayoran Baru
Jakarta Selatan 12160

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 1/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 2/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

 
STANDAR SPLN S5.003-1: 2014
Lampiran Keputusan Direksi
PT PLN (PERSERO)   PT PLN (PERSERO) No. 0952. K/DIR/2014 

TELEINFORMASI DATA DAN TAMPILAN


UNTUK SISTEM OTOMASI GARDU INDUK
Bagian 1:
FUNGSI OPERASI

PT PLN (Persero)
Jl. Trunojoyo Blok M-1/135 Kebayoran Baru
Jakarta Selatan 12160

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 3/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 4/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

TELEINFORMASI DATA DAN TAMPILAN


UNTUK SISTEM OTOMASI GARDU INDUK
Bagian 1:
FUNGSI OPERASI

Disusun oleh :

Kelompok Bidang SCADA Standardisasi


dengan Keputusan Direksi
PT PLN (Persero)
No. 0448.K/DIR/2014 

Kelompok Kerja Standardisasi


Teleinformasi Data Untuk Sistem Otomasi Gardu Induk
dengan Keputusan Kepala
PT PLN (Persero) Puslitbang Ketenagalistrikan 
No. 0236.K/PUSLITBANG/2014 

Diterbitkan oleh :
PT PLN (Persero)
Jl. Trunojoyo Blok M -1/135, Kebayoran Baru
Jakarta Selatan 12160

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 5/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 6/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 7/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

Susunan Kelompok Bidang SCADA Standardisasi


Keputusan Direksi PT PLN (Persero)
No. 0448.K/DIR/2014

1. Ir. I Putu Riasa : Sebagai Ketua merangkap Anggota


2. Tri Hardimasyar,ST,MSc : Sebagai Sekretaris merangkap Anggota
3. Agus Harya Maulana, ST, MT : Sebagai Anggota
4. Novrizal Erdiyansyah, ST, MSc : Sebagai Anggota
5. Ir. Hesti Sayoga : Sebagai Anggota
6. Ir. Ruly Chaerul : Sebagai Anggota
7. Ir. Ridwan Nainggolan : Sebagai Anggota
8. A Sugeng Sugarjito,ST : Sebagai Anggota

9. Made Yusadana, ST, MSc : Sebagai Anggota


10. Denden Ruhdani, ST : Sebagai Anggota
11. Erwan Herdiyanto, ST, MSc : Sebagai Anggota
12. Muchsin Akuba Gani, ST : Sebagai Anggota
13. Akbar Patonangi, ST : Sebagai Anggota

Susunan Kelompok Kerja Standardisasi


Teleinformasi Data Untuk Sistem Otomasi Gardu Induk
Keputusan Kepala PT PLN (Persero) Puslitbang Ketenagalistrikan
No. 0236.K/PUSLITBANG/2014

1. Joko Pitoyo, ST : Sebagai Ketua merangkap Anggota


2. Tri Hardimasyar, ST, M.Sc : Sebagai Sekretaris merangkap Anggota
3. Suci Rositawati, ST : Sebagai Anggota
4. Lukman Hakim, ST : Sebagai Anggota
5. Ricci Fajar, ST : Sebagai Anggota
6. Riko Ramadhano Budiawan, ST : Sebagai Anggota
7. Amiruddin, ST : Sebagai Anggota
8. Lugito Nurwahono, ST : Sebagai Anggota
9. Novrizal Erdiansyah, ST,MSc : Sebagai Anggota

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 8/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

  SPLN S5.003-1: 2014

Daftar Isi

Daftar Isi ............................................................................................................................. i


Daftar Gambar ................................................................................................................... ii
Daftar Tabel...................................................................................................................... iii
Daftar LAMPIRAN ............................................................................................................. iv
Prakata ............................................................................................................................. v
1  Ruang Lingkup .............................................................................................................1  
2  Tujuan .......................................................................................................................... 1 
3   Acuan Normatif ............................................................................................................. 1 
4  Istilah dan Definisi ........................................................................................................ 2 
4.1   Alarm ................................................................................................................... 2 
4.2  Control center ...................................................................................................... 2 
   
4.3 Distribution control center  (DCC) ......................................................................... 2
4.4  Feeder colouring .................................................................................................. 2 
4.5  Gardu hubung...................................................................................................... 2 
4.6  Gardu induk ......................................................................................................... 2 
4.7  Gardu tengah....................................................................................................... 2 
4.8  Human Machine Interface (HMI) .......................................................................... 2 
4.9  Inter Distribution Control Center  (IDCC) ............................................................... 3 
4.10  Inter Regional Control Center  (IRCC) .................................................................. 3 
4.11  Maintenance Center  ............................................................................................ 3 
4.12  National Control Center  (NCC) ............................................................................ 3  
4.13  Operator .............................................................................................................. 3 
4.14  Regional Control Center  (RCC) ........................................................................... 3 
4.15  Regu pemeliharaan ............................................................................................. 3 
4.16  Remote station .................................................................................................... 3 
4.17  Sistem Otomasi Gardu Induk (SOGI) ................................................................... 3 
4.18  Supervisory Control and Data Acquisition (SCADA) ............................................ 3 
4.19  Telecontrol ........................................................................................................... 4 
4.20  Telesignal ............................................................................................................ 4 
4.21  Telemetering ........................................................................................................ 4 
5  Umum...........................................................................................................................4 
5.1  Fasilitas SCADA untuk SOGI ............................................................................... 4 
5.2  Teleinformasi data (TID) ...................................................................................... 4 
5.3  Struktur informasi................................................................................................. 4 
5.4  Simbol dan warna ................................................................................................ 5 
5.5  Tampilan HMI Fungsi Operasi ............................................................................. 5 
5.6  Gambar tipikal HMI Fungsi Operasi ..................................................................... 5 
5.7  Penjelasan gambar tipikal HMI Fungsi Operasi ................................................... 7  
6  Perbatasan Kebutuhan Teleinformasi Data .................................................................. 9 
6.1  Perbatasan Kebutuhan Teleinformasi Data antara IRCC dan RCC ..................... 9 
6.2  Perbatasan kebutuhan teleinformasi data antara RCC dan DCC ....................... 11 

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 9/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Daftar Gambar

Gambar 1. Tipikal HMI fungsi operasi................................................................................ 5 


Gambar 2. Topologi ........................................................................................................... 6 
Gambar 3. Single Diagram fungsi operasi ......................................................................... 7 
Gambar 4. Tipikal HMI fungsi operasi................................................................................ 8 
Gambar 5. Batas wewenang antara IRCC dengan RCC (Tipe-a) ...................................... 9 
Gambar 6. Batas wewenang antara IRCC dengan RCC (Tipe-b) .................................... 10 
Gambar 7. Batas wewenang antara RCC dengan DCC .................................................. 11 
Gambar 8. Konfigurasi SLD 1 ½ breaker ......................................................................... 18 
Gambar 9. Konfigurasi umum pada 1 ½ breaker  150 kV ................................................. 22 
Gambar 10. Konfigurasi umum pada double busbar ........................................................ 26 
Gambar 11. Konfigurasi umum pada single busbar ......................................................... 30 
Gambar 12. Interbus transformer (secondary side connected to 1½ breaker) ................ 34 
Gambar 13. Interbus transformer (secondary side connected to double busbar ) ............. 36 
Gambar 14. Interbus transformer (secondary side connected to single busbar ) ............. 38 
Gambar 15. Secondary side  terhubung 1½ breaker dilengkapi dhunt reaktor pada
kumparan tersier ............................................................................................................. 40 
Gambar 16. Secondary side connected to double busbar   dilengkapi shunt reaktor pada
kumparan tersier ............................................................................................................. 42 
Gambar 17. Secondary side connected to single busbar   dilengkapi shunt reaktor pada
kumparan tersier ............................................................................................................. 44 
Gambar 18. Bay  trafo tenaga pada konfigurasi 1½ breaker . ............................................ 46 
Gambar 19. Bay  trafo tenaga pada konfigurasi double busbar  ........................................ 48 
Gambar 20. Bay  trafo tenaga pada konfigurasi single busbar . ....................................... 50 
Gambar 21. Bay reaktor pada konfigurasi 1 ½ breaker.................................................... 52 
Gambar 22. Bay  reaktor pada konfigurasi double busbar  ................................................ 53 
Gambar 23. Bay  reaktor pada konfigurasi single busbar  ................................................. 54  
Gambar 24. Bay capasitor   pada konfigurasi double busbar . ............................................ 55 
Gambar 25. Bay capasitor   pada konfigurasi single busbar  .............................................. 56  
Gambar 26. Bay penghantar pada konfigurasi 1 ½ breaker . ............................................ 57 
Gambar 27. Bay   penghantar pada konfigurasi double busbar  ......................................... 58 
Gambar 28. Bay penghantar pada konfigurasi single busbar  .......................................... 60 
Gambar 29. Bay   penghantar paralel dengan reaktor pada konfigurasi double busbar  ..... 62 
Gambar 30. Bay  penghantar paralel dengan 1 reaktor pada konfigurasi 1½ breaker  ...... 63 
Gambar 31. Bay kopel pada konfigurasi double busbar ................................................... 65 
Gambar 32. Konfigurasi umum pada double busbar ........................................................ 70 
Gambar 33. Konfigurasi umum pada single busbar ........................................................ 73 
Gambar 34. Trafo 150/20 kV dan 70/20 kV tipe 1 ............................................................ 76 
Gambar 35. Trafo 150/20 kV dan 70/20 kV tipe 2 ............................................................ 77 
Gambar 36. Trafo 150/20 kV dan 70/20 kV tipe 3 ............................................................ 78 
Gambar 37. Generator pada konfigurasi double busbar  .................................................. 79 
Gambar 38. Generator pada konfigurasi single busbar .................................................... 80 
Gambar 39. Feeder  20 kV tipe 1 ..................................................................................... 81 
Gambar 40. Feeder  20 kV tipe 1 ..................................................................................... 83 
Gambar 41. Bus section 20 kV tipe 1 .............................................................................. 84 
Gambar 42. Bus section 20 kV tipe 2 .............................................................................. 85 
Gambar 43. Kopel ........................................................................................................... 86 
Gambar 44. Capacitor bay .............................................................................................. 87 

ii

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 10/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

  SPLN S5.003-1: 2014

Gambar 45. Struktur informasi khusus (bay diameter) ..................................................... 95 


Gambar 46. Struktur informasi khusus (gardu induk 1½ breaker ) ....................................96 
Gambar 47. Simbol gambar ............................................................................................. 97 
Gambar 48. Tampilan status ............................................................................................ 98  

Daftar Tabel

Tabel 1. Daftar telesignal fungsi operasi .......................................................................... 12


Tabel 2. Daftar telemeasurement .....................................................................................16
Tabel 3. Daftar tap changer position ................................................................................17
Tabel 4. Daftar remote control .........................................................................................17
Tabel 5. Teleinformasi data untuk konfigurasi umum pada 1½ breaker ...........................19
Tabel 6.Teleinformasi data untuk konfigurasi umum pada 1½ breaker  ...........................23
Tabel 7. Teleinformasi data untuk konfigurasi umum pada double busbar .......................27
Tabel 8. Teleinformasi data untuk konfigurasi umum pada single busbar  ........................ 31
Tabel 9. Teleinformasi data untuk interbus transformer   (secondary side connected   to 1½
breaker ) ...........................................................................................................................35
Tabel 10. Teleinformasi data untuk interbus transformer   (secondary side connected to
double busbar) .................................................................................................................37
Tabel 11. Teleinformasi data untuk interbus transformer   (secondary side connected to
single busbar) ..................................................................................................................39
Tabel 12. Teleinformasi data untuk interbus transformer  (secondary side connected to 1½
breaker  dilengkapi shunt  reaktor pada kumparan tersier) ................................................ 41
Tabel 13.Teleinformasi data untuk interbus transformer   (secondary side connected to
double busbar   dilengkapi shunt  reaktor pada kumparan tersier) ...................................... 43

Tabel 14. Teleinformasi


single busbar  data  untuk
  dilengkapi shunt  reaktorinterbus transformer
pada kumparan (secondary
tersier) side connected 45
....................................... to 
Tabel 15. Teleinformasi data untuk bay trafo tenaga pada konfigurasi 1½ breaker  .......... 47
Tabel 16. Teleinformasi data untuk bay  trafo tenaga pada konfigurasi double busbar  ..... 49
Tabel 17. Teleinformasi data untuk bay  trafo tenaga pada konfigurasi single busbar  ....... 51
Tabel 18. Teleinformasi data untuk bay reaktor pada konfigurasi 1 ½ breaker  ................. 52
Tabel 19. Teleinformasi data untuk bay   reaktor pada konfigurasi double busbar  .............53
Tabel 20. Teleinformasi data untuk bay   reaktor pada konfigurasi single busbar  ............... 54
Tabel 21. Teleinformasi data untuk bay  kapasitor pada konfigurasi double busbar  .......... 55
Tabel 22. Teleinformasi data untuk bay  kapasitor pada konfigurasi single busbar  ........... 56
Tabel 23. Teleinformasi data untuk bay penghantar pada konfigurasi 1 ½ breaker  .......... 57
Tabel 24. Teleinformasi data untuk bay   penghantar pada konfigurasi double busbar  ...... 59
Tabel 25. Teleinformasi data untuk bay   penghantar pada konfigurasi single busbar  ........ 60
Tabel 26. Teleinformasi data untuk bay  penghantar serial dengan reaktor pada konfigurasi
double busbar ..................................................................................................................62
Tabel 27. Teleinformasi data untuk bay   penghantar paralel dengan 1 reaktor pada
konfigurasi 1½ breaker ....................................................................................................64
Tabel 28. Teleinformasi data untuk bay  kopel pada konfigurasi double busbar  ................ 65
Tabel 29. Daftar telesignal   distribusi ................................................................................ 66
Tabel 30. Daftar telemeasurement ...................................................................................68
Tabel 31. Daftar tap changer ...........................................................................................69
Tabel 32. Daftar remote control digital .............................................................................69
Tabel 33. Teleinformasi data untuk konfigurasi umum pada double busbar  .....................70
Tabel 34. Teleinformasi data untuk konfigurasi umum pada single busbar  ......................73

iii

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 11/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 35. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 1 .......................... 76
Tabel 36. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 2 .......................... 77
Tabel 37. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 3 .......................... 78
Tabel 38. Teleinformasi data untuk generator pada konfigurasi double busbar ............... 80
Tabel 39. Teleinformasi data untuk generator pada konfigurasi single busbar................. 81
Tabel 40. Teleinformasi data untuk feeder 20 kv tipe 1.................................................... 82
Tabel 41. Teleinformasi data untuk feeder   20 kv tipe 1.................................................... 83
Tabel 42. Teleinformasi data untuk bus section 20 kv tipe 1 ............................................ 84
Tabel 43.Teleinformasi data untuk bus section 20 kv tipe 2 ............................................. 85
Tabel 44. Teleinformasi data untuk kopel ........................................................................ 86
Tabel 45. Teleinformasi data untuk capasitor bay ............................................................ 87
Tabel 46. Struktur informasi ............................................................................................ 89
Tabel 47. Level tegangan ................................................................................................ 91
Tabel 48. Nama bay atau feeder ..................................................................................... 92
Tabel 49. Kode tegangan dari primer dan sekunder trafo ................................................ 93
Tabel 50. Kode nama peralatan/alarm/elemen ................................................................ 93
Tabel 51. Warna tampilan ............................................................................................... 99 

Daftar LAMPIRAN

LAMPIRAN 1. Daftar Teleinformasi ................................................................................. 12  


LAMPIRAN 2. Teleinformasi pada Berbagai Konfigurasi Gardu Induk ............................. 18 
LAMPIRAN 3. Daftar Teleinformasi (Distribusi) ............................................................... 66 
LAMPIRAN 4. Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi ................... 70 
LAMPIRAN 5. Struktur Informasi ..................................................................................... 89 

LAMPIRAN 6. Simbol dan Warna .................................................................................... 97 

iv

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 12/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

  SPLN S5.003-1: 2014

Prakata

Standar SCADA ini merupakan pedoman dalam rangka mengikuti perkembangan


teknologi SCADA dan Telekomunikasi.
Standar ini mencakup definisi, perangkat keras, perangkat lunak, kebutuhan teleinformasi
data, pengujian, kinerja, kajian kelayakan dalam pembangunan, operasi dan
pemeliharaan yang memiliki hubungan dengan sistem SCADA.
Standar ini terdiri dari dua bagian, yaitu:
1. S5.003-1: 2014 Teleinformasi Data dan Tampilan Untuk Sistem Otomasi Gardu Induk
Bagian 1: Fungsi Operasi
2. S5.003-2: 2014 Teleinformasi Data dan Tampilan Untuk Sistem Otomasi Gardu Induk
Bagian 2: Fungsi Pemeliharaan
Standar ini harus menjadi acuan dalam setiap perencanaan, pembangunan, operasi dan
pemeliharaan sistem SCADA di PT PLN (Persero) secara nasional.

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 13/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 14/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Teleinformasi Data dan Tampilan Untuk


Sistem Otomasi Gardu Induk
Bagian 1: Fungsi Operasi

1 Ruang Lingkup

Teleinformasi data terdiri dari telecontrol , telesignal dan telemetering . Sesuai dengan
perkembangan teknologi peralatan di Gardu Induk, teleinformasi data ini dibuat untuk
kepentingan operasi dan kebutuhan pemeliharaan pada Gardu Induk otomasi. Standar ini
dimaksudkan untuk menetapkan standar teleinformasi data yang diaplikasikan untuk
kebutuhan operasi sistem tenaga listrik dan mencakup sistem transmisi dan sistem
distribusi.
Standar ini, berlaku untuk sistem SCADA:
a. National Control Center , disingkat NCC;
b. Inter Regional Control Center , disingkat IRCC;
c. Regional Control Center , disingkat RCC;
d. Inter Distribution Control Center , disingkat IDCC;
e. Distribution Control Center , disingkat DCC.

2 Tujuan

Standar ini ditujukan untuk memberikan pedoman yang terarah dan seragam dalam
penerapan teleinformasi data dan tampilan HMI 1yste bagi penerapan gardu induk

otomasi yangpembangunan
acuan dalam mengutamakan mutu,SCADA
System keandalan
untukdan ekonomi.
Gardu Standarbaru
Induk otomasi ini dan
merupakan
1ystem
SCADA untuk penambahan bay   baru (migrasi RTU). Untuk bay   lama, tetap menggunakan
teleinformasi data fungsi operasi sesuai dengan SPLN S5.001: 2008 yang akan
disetarakan dengan TID untuk SOGI.

3 Acuan Normatif

Dokumen-dokumen referensi/acuan berikut sangat diperlukan dalam penggunaan standar


ini. Untuk referensi yang bertanggal, maka hanya terbitan tersebut yang berlaku
sedangkan referensi yang tidak bertanggal, yang berlaku adalah terbitan terakhir dari
dokumen referensi tersebut (termasuk amandemennya).
Dokumen normatif berikut berisi persyaratan-persyaratan yang menjadi referensi dalam
pembuatan standar SCADA: Teleinformasi Data Untuk Sistem Otomasi Gardu Induk.
a. SNI 04-7021.1.1-2004: 2004, Peralatan dan Sistem Telekontrol    –  Bagian 1:
Pertimbangan Umum – Seksi 1: Prinsip Umum; 
b. Keputusan Menteri Energi dan Sumberdaya Mineral Nomor: 150K/30/MEM/2004,
 Aturan Jaringan Sistem Tenaga Listrik Jawa-Madura-Bali ; 
c. SPLN S3.001: 2008 “Peralatan SCADA Sistem Tenaga Listrik”; 
d. SPLN T5.002-1: 2010 ”Pola Proteksi Saluran Transmisi Bagian 1 : Tegangan Tinggi
66 kV dan 150 kV”;  
e. SPLN T5.002-2: 2010”Pola Proteksi Saluran Transmisi Bagian 2 : Tegangan Ekstra
Tinggi 275 kV dan 500 kV”;  

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 15/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

f. IEC 61850-1 ” Communication networks systems in substations  – Part 1: Introduction


and overview ”; 
g. IEC 61850-2 ” Communication networks systems in substations – Part 2: Glossary ”; 
h. IEC 61850-3 ” Communication networks systems in substations  –  Part 3: General
Requirement ”; 

4 Istilah dan Definisi

4.1 A l a r m

Perubahan kondisi dari peralatan atau System yang telah terdeteksi sebelumnya   karena
fungsi yang tidak dilakukan oleh operator/dispatcher , atau kegagalan peralatan untuk
merespon secara benar. Indikasi alarm berupa audible atau visual , atau keduanya. 

4.2 C o n t r o l c e n t er
Pusat kendali pengoperasian sistem tenaga listrikdimana master station ditempatkan.

4.3 D i s t r i b u t i o n c o n t r o l c e n t er  
 (DCC)

Pusat kendali jaringan distribusi.

4.4 F ee d e r c o l o u r i n g

Pewarnaan penyulang pada jaringan tenaga listrik dalam kondisi bertegangan.

4.5 Gardu hubung

Gardu yang mempunyai fungsi utama melakukan manuver antar feeder.

4.6 Gardu induk

Gardu yang mempunyai fungsi sebagai pusat pembagi beban.

4.7 Gardu tengah

Gardu yang merupakan titik tengah beban atau titik tengah feeder.

4.8 Hum an Mach ine Interface 


 (HMI)

Perangkat dimana pengguna berinteraksi dengan system  SCADA. HMI menyediakan


fasilitas dimana pengguna dapat memberikan input kepada system  dan system  dapat
memberikan output kepada pengguna.

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 16/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

4.9 In t e r D i s t r i b u t i o n C o n t r o l C e n t e r   (IDCC)

Pusat kendali yang terhubung dengan beberapa distribution control center .

4.10 Inter Regio nal Contro l Center 


 (IRCC)

Pusat kendali yang terhubung dengan beberapa regional control center .

4.11 Maintenance Center

Workstation di luar control center   yang digunakan untuk keperluan pemeliharaan.

4.12 National Contro l Center 


 (NCC)

Pusat kendali yang terhubung dengan beberapa inter regional control center .

4.13 Operator

Petugas yang mengawasi dan mengeksekusi secara lokal peralatan di gardu induk.

4.14 Region al Contr ol Center 


 (RCC)

Pusat kendali jaringan transmisi tegangan tinggi.

4.15 Regu pemeliharaan

Petugas yang melakukan pemeliharaan pada instalasi sistem tenaga listrik.

4.16 Remote station

Stasiun yang dipantau, atau diperintah dan dipantau oleh master station, yang terdiri dari
gateway , IED, HMI lokal, RTU, dan meter energi.

4.17 Sistem Otomasi Gardu Induk (SOGI)


Sistem untuk mengelola, mengendalikan, dan proteksi system tenaga listrik. Hal ini dapat
dicapai dengan mengambil informasi real time dari system, didukung oleh aplikasi local
dan remote control yang handal dan proteksi system  tenaga listrik. Sebuah Substation
 Automation terdiri dari local intelligence, komunikasi data dan supervisory control , serta
monitoring .

4.18 S u p e r v i s o r y C o n t r o l a n d D at a A c q u i s i t i o n   (SCADA)

Sistem yang mengawasi dan mengendalikan peralatan proses yang tersebar secara
geografis. [ IEC 870-1-3 ]

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 17/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

4.19 T e l e c o n t r o l

Kendali peralatan operasional jarak jauh menggunakan transmisi informasi dengan teknik
telekomunikasi. [IEV 371-01-01]
CATATAN: Telekontrol dapat berisi kombinasi perintah, alarm, indikasi, metering /pengukuran,
proteksi dan fasilitas tripping , tidak menggunakan pesan suara. 

4.20 Telesignal

Pengawasan status dari peralatan operasional dalam jarak tertentu dengan menggunakan
teknik telekomunikasi seperti kondisi alarm, posisi switch atau posisi katup. [IEV 371-01-
04]

4.21 Telemetering

Transmisi nilai variabel yang diukur dengan menggunakan teknik telekomunikasi. [IEV
371-01-03]

5 Umum

5.1 Fasilitas SCADA untuk SOGI

Setiap pembangunan gardu induk yang baru dan penambahan bay baru pada gardu induk
lama harus dapat dipantau dari control center   dan dilakukan pengujian sebelum
diintegrasikan ke system transmisi atau system distribusi tenaga listrik.

5.2 Teleinformasi data (TID)

Standar ini membedakan teleinformasi data untuk transmisi dan distribusi. Teleinformasi
data untuk Sistem Otomasi Gardu Induk (SOGI) dapat dilihat pada pada LAMPIRAN 1.
Daftar Teleinformasi. 

Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi maka
master station dapat digunakan untuk fungsi RCC dan DCC. Dalam hal ini teleinformasi
yang digunakan mengacu pada teleinformasi data transmisi dan distribusi.

Teleinformasi data untuk sistem SOGI ditampilkan pada Master Station, Maintenance
Center   dan HMI (Human Machine Interface) lokal pada gardu induk setempat.
Konfigurasi workstation di luar control center  yang difungsikan untuk Maintenance Center  
dan juga HMI (Human Machine Interface) lokal yang bertempat di Gardu Induk setempat,
menampilkan kebutuhan teleinformasi data fungsi pemeliharaan. Untuk Dispatcher   pada
control center , ditampilkan kebutuhan teleinformasi data fungsi operasi.

5.3 Struktur informasi

Event dan alarm merupakan pemberitahuan kepada dispatcher   atau operator tentang
kejadian pada peralatan sistem tenaga listrik yang tampil di monitor dan disimpan di data
historikal. Struktur informasi event   dan alarm SCADA dapat dilihat pada LAMPIRAN 5.
Struktur Informasi. 

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 18/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

5.4 Simbol dan warna


Simbol dan warna diperlukan untuk penyajian diagram system tenaga listrik pada monitor
dan layar tayang. Simbol dan warna untuk tiap jenis dan kondisi peralatan bersifat system
dan dipilih sedemikian rupa sehingga jenis dan kondisi peralatan tersebut mudah dikenali
oleh regu pemeliharaan dan operator . Simbol dan warna dapat dilihat pada  LAMPIRAN 6.
Simbol dan Warna. 

5.5 Tampilan HMI Fungsi Operasi


Tampilan pada HMI fungsi operasi harus diatur agar seragam. Eksekusi manuver  
peralatan harus dapat dilakukan dengan cara yang mudah dan cepat dengan maksimal 3
langkah yaitu:
1. Klik peralatannya.
2. Pilih tombol Close atau Open 
3. Execute atau Cancel. 
Kategori tampilan yang harus ada pada HMI Fungsi Operasi adalah:
1. Single Line Diagram Gardu Induk sesuai dengan TID SOGI Fungsi Operasi:
a. Single Line Diagram untuk Tegangan Ekstra Tinggi
b. Single Line Diagram untuk Tegangan Tinggi.
c. Single Line Diagram untuk Tegangan Menengah.
d. Single Line Diagram untuk Daya Pemakaian Sendiri.
e. Overview   keseluruhan SLD Gardu Induk, diusahakan untuk ditampilkan dalam
1 layar.
2. Pengukuran keseluruhan Gardu Induk sesuai TID SOGI Fungsi Operasi
a. Tabel Measurement realtime.
b. Log sheet   pengukuran.
3. Event list   yang dapat dilakukan proses filter dan diekspor ke dalam bentuk

database
4.  Alarm list (Oracle dan/atau SQL dan/atau
  yang dapat dilakukan prosesSpreadsheet 
filter dan )diekspor ke dalam bentuk
database (Oracle dan/atau SQL dan/atau Spreadsheet )
5. Simbol.

5.6 Gambar tipikal HMI Fungsi Operasi

5.6.1 Umum
Lambang PLN Dummy CB Nama Gardu Induk & Level Tegangan Hari + Tanggal + Jam

Na ma Us er Lo cal/Remote Print Jenis Alarm

Ikon Baterai

Catatan: Isi tampilan untuk bagian header kelengkapan informasinya harus


mengikuti informasi yang ada pada lay out ini, sedangkan penempatan
informasinya adalah bebas tergantung masing-masing aplikasi HMI.

Gambar 1. Tipikal HMI fungsi operasi

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 19/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

5.6.2 Topologi

4
1 2 3
4. Control Centre BUS - A

BUS - B

4
1 2 3
3.HMI SOGI BUS - A

BUS - B

4
1 2 3
2. Relay & Control Panel
(Urutan Panel di Ruang BUS - A
Kontrol GI)
BUS - B

4
1 2 3
1. Switchyard BUS - A

BUS - B

Gambar 2. Topologi

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 20/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

5.6.3 Contoh Single line diagram fungsi operasi

Di atas SLD ada:


1. Dummy CB
2. Kontrol Disable/Enable (Diganti menjadi Local Remote)
3.
4. Nama
KondisiGIalarm Baterai (dlm bentuk ikon), RTU, Komunikasi,
5. Kondisi GI (General Interrogation, In service atau Out service)
6. Jenis-jenis alarm (Emergency, Critical, General, Limit violation, Station )
7. Hari, tanggal, jam.

Lambang PLN Dummy CB Nama Gardu Induk & Level Tegangan Hari + Tanggal + Jam

Nama User Local/Remote Print Jenis Alarm

BAY
GENERATOR

Ikon Baterai P LFC


Q (Po,Pr,N)
V

P
Q
I

L/R
BAY
KOPEL

BB - A 150 kV

150 kV
BB - B

L/R
L/R L/R L/R

P
Q P
Q P
Q
150/70 kV
150/20 kV
V V
I I
Catatan :
1. arah panah pada bay menunjukan arah
pengiriman daya

BAY BAY BAY BAY


TRANSMISI TRAFO IBT REAKTOR
TENAGA

Gambar 3. S ingle Diagram  fungsi operasi

5.7 Penjelasan gambar tipikal HMI Fungsi Operasi


    Alarm gangguan rectifier dan baterai ditampilkan dalam bentuk ikon (bisa berupa
ikon baterai atau aki). Peletakannya dilakukan di sudut kiri atas. Ukurannya 2x
gambar CB. Ikon tersebut akan blinking apabila terjadi gangguan.
   Posisi kontrol GI dalam mode local   atau remote secara general harus ditampilkan
di bagian atas.
   “Dummy  CB” adalah indikasi dan soft button dummy circuit breaker .
   Tampilan overview   adalah tampilan yang menampilkan keseluruhan SLD dengan
level tegangan yang sama, misalnya tampilan keseluruhan SLD 500 kV, SLD 150

kV, SLD 66 kV dan SLD 20 kV.

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 21/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

   Untuk bay   yang sedang dalam posisi interlock (PMT dan PMS) dipersyaratkan
menampilkan gambar gembok untuk menginformasikan status tersebut ke
dispatcher . Contohnya dapat dilihat pada gambar berikut:
BB - A 150 kV

BB - B 150 kV

L/R
L/R

Gembok
L/R
berwarna kuning

Gambar 4. Tipikal HMI fungsi operasi

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 22/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

6 Perbatasan Kebutuhan Teleinformasi Data

Teleinformasi data yang dikirim ke/dari suatu control center   ditentukan oleh
kewenangannya dalam operasi sistem, sehingga dibutuhkan adanya batas yang jelas
antara kewenangan IRCC dan RCC serta RCC dan DCC. Berikut ini dijelaskan
perbatasan kebutuhan teleinformasi data antara IRCC dan RCC serta antara RCC dan
DCC.

6.1 Perbatasan Kebutuhan Teleinformasi Data antara IRCC dan RCC

Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC adalah di titik pelayanan
tegangan ekstra tinggi atau tegangan tinggi yang ditentukan, dan atau seperti Gambar 55
dan Gambar 66.

a. Bila sisi sekunder IBT terhubung dengan konfigurasi double busbar

BUSBAR TET/TT

IRCC

RCC

BUSBAR TT

 
Gambar 5. Batas wewenang antara IRCC dengan RCC (Tipe-a)

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 23/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

b. Bila sisi sekunder IBT terhubung dengan konfigurasi 1½ Breaker  

BUSBAR TET/TT

BUSBAR
TT

IRCC

RCC

BUSBAR
TT

 
Gambar 6. Batas wewenang antara IRCC dengan RCC (Tipe-b)

10

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 24/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

6.2 Perbatasan kebutuhan teleinformasi data antara RCC dan DCC

Perbatasan kebutuhan teleinformasi data antara RCC dan DCC di gardu induk ditunjukan
pada Gambar 77.

BUSBAR TT

L/R

P
Q
V
I

RCC

DCC

BUSBAR TM

 
Gambar 7. Batas wewenang antara RCC dengan DCC

Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi (belum
dipisahkan antara fungsi RCC dan DCC) maka perbatasan kebutuhan teleinformasi data
dapat mengacu pada perbatasan fungsi RCC dan DCC atau disesuaikan dengan SOP
yang berlaku di daerah tersebut.  

11

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 25/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

LAMPIRAN 1. Daftar Teleinformasi

1-1: Telesignal 
 

Tabel 1. Daftar telesignal fungsi operasi

Indikasi Sumber Bagian Jumlah Event


No Kode Fungsi Implementasi
TSS/TSD H/LN D/B/G/P F/C A/I

1 AQR  Automatic power factor active Generator, TSS H B C I


Circuit breaker auto reclose
2 AR OHL feeder, TSS LN B C A
success
Circuit breaker auto reclose
3 ARL OHL feeder, TSS LN B C A
lock out
4 ARO  Auto reclose on/off OHL feeder, TSD LN B C I
 Automatic voltage regulator
5 AVR Generator, TSS H B C I
on/off
IBT 150/70 sisi 150,
6 AVRAM  Avr Auto/ manual  TRF 150(70)/20 sisi TSD LN D C I
150(70),
Bus coupler,
Bus section,
OHL feeder,
Cable feeder,
IBT 500(275)/150 sisi 150,
IBT 150/70 sisi 150,
7 BF Bay fault IBT 150/70 sisi 70, TSS LN B C A
TRF 150(70)/20 sisi
150(70),
Capacitor,
Reactor,
Diameter,
Gen transf,
Bus coupler,
Bus section,
OHL feeder,
Cable feeder,
IBT 500(275)/150 sisi 150,
IBT 150/70 sisi 150,
Bus isolator switch
8 BI IBT 150/70 sisi 70, TSD H D C I
closed/opened
TRF 150(70)/20 sisi
150(70),
TRF 150(70)/20 sisi 20,
Capacitor,
Reactor,
Gen Transf,

9 BP Busbar protection  Busbar, TSS LN B C A

Bus coupler,
Bus section,
OHL feeder,
Cable feeder,
IBT 500(275)/150 sisi 150,
IBT 150/70 sisi 150,
10 BRF Breaker fault IBT 150/70 sisi 70, TSS LN B C A
TRF 150(70)/20 sisi
150(70),
Capacitor,
Reactor,
Diameter,
Gen transf, 

11 BUAL Building alarm Gardu induk, TSS H G C A

Bus coupler,
Bus section,
Ohl feeder,
12 CB Circuit breaker closed/opened TSD H D C I
Cable feeder,
IBT 500(275)/150 sisi 150,
IBT 150/70 sisi 150,

12

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 26/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Indikasi Sumber Bagian Jumlah Event


No Kode Fungsi Implementasi
TSS/TSD H/LN D/B/G/P F/C A/I
IBT 150/70 sisi 70,
TRF 150(70)/20 sisi
150(70),
TRF 150(70)/20 sisi 20,
Capacitor,
Reactor,
Diameter,
13 COM Communication faulty Gardu induk, TSS LN P C A

14 CSO Check synchronizing override Gardu induk, TSD LN B C I

Bus coupler,
Check synchronizing in OHL feeder,
15 CSP TSS LN B C A
 progress Cable feeder,
IBT 150/70 sisi 70,
OHL feeder,
16 DEF Directional earth fault TSS LN B F A
Cable feeder, 
Diameter isolator switch
17 DI Diameter, TSD H D C I
closed/opened
OHL feeder,
18 DISZ1 Distance protection zone 1 Cable feeder, TSS LN B F A
OHL feeder,
19 DISZ2 Distance protection zone 2 TSS LN B F A
Cable feeder,
OHL feeder,
20 DISZ3 Distance protection zone 3 TSS LN B F A
Cable feeder,
OHL feeder,
21 DISZ4 Distance protection zone 4 TSS LN B F A
Cable feeder,
22 DTT Direct transfer trip OHL feeder, TSS LN P C A

Busbar,
23 ES Earth switch closed/opened OHL feeder, TSD H D C I
CABLE feeder,

24 GOV Free acting governor active Generator, TSS H B C I

25 GRM Genset ready/maintenance Gardu induk, TSD H G C I

26 GTT Generator transformer trip Gen transf, TSS H B C A

27 GUC Generator unit run/stop Generator, TSD H P C I

28 IEDF Ied bay level faulty Gardu induk, TSS LN G C A


OHL feeder,
29 LCD Line current differential TSS LN B F A
Cable feeder,

Load freq available/not


30 LFA Generator,blok, TSD H P C I
available

31 LFC Load freq control on/off switch Generator,blok, TSD H P C I


Generator,
32 LFF Load freq control unit failure TSS H B C I
blok,

33 LFR Load freq request on/off Generator,blok, TSD H P C I

OHL feeder,
Cable feeder,
Line isolator switch
34 LI Capacitor, TSD H D C I
closed/opened
Reactor,
Gen transf,

35 LOR Lock out relay trip Gardu Induk, TSS LN B C A

13

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 27/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Indikasi Sumber Bagian Jumlah Event


No Kode Fungsi Implementasi
TSS/TSD H/LN D/B/G/P F/C A/I
Bus Coupler,
OHL feeder,
Cable feeder,
IBT 500(275)/150 sisi 150,
IBT 150/70 sisi 150,
IBT 150/70 sisi 70,
36 LRBCU Local/Remote for bcu TRF 150(70)/20 sisi TSD LN B C I
150(70),
TRF 150(70)/20 sisi 20,
Capacitor,
Reactor,
Diameter,
Gen transf, 

37 LRHMI Local/Remote for local hmi Gardu Induk, TSD LN G C I

Bus coupler,
OHL feeder,
Cable feeder,
38 OCGF Over current ground fault TSS LN B C A
Capacitor,
Reactor,
Diameter,
39 OCPT Oil cable pressure trip Cable feeder, TSS H B F A

40 PSO Power station operated Generator,blok, TSD H P C I

41 RA Reaktor alarm Reactor, TSS LN B C A

42 RT Reaktor trip Reactor, TSS LN B C A

43 SF Supply failure Gardu induk, TSS H B C A


Software interlocking by
44 SIB Gardu induk, TSD LN B C I
 passed

45 SLF Station level faulty Gardu induk, TSS LN P C A

OHL feeder,
46 SOTF Switch on to fault TSS LN B C A
Cable feeder, 

IBT 150/70 sisi 150,


47 TCH Tap changer high limit TRF 150(70)/20 sisi TSS H B C A
150(70),

IBT 150/70 sisi 150,


48 TCIP Tap changer in progress TRF 150(70)/20 sisi TSS H B C A
150(70),

IBT 150/70 sisi 150,


49 TCL Tap changer low limit TRF 150(70)/20 sisi TSS H B C A
150(70),

IBT 150/70 sisi 150,


50 TEA Temperature alarm TRF 150(70)/20 sisi TSS LN B C A
150(70),

14

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 28/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Indikasi Sumber Bagian Jumlah Event


No Kode Fungsi Implementasi
TSS/TSD H/LN D/B/G/P F/C A/I
IBT 150/70 sisi 150,
51 TRA Transformer  alarm TRF 150(70)/20 sisi TSS LN B C A
150(70),
IBT 150/70 sisi 150,
Transformer back up
52 TRBPT TRF 150(70)/20 sisi TSS LN B C A
 protection trip 150(70),
IBT 150/70 sisi 150,
Transformer main protection
53 TRMPT TRF 150(70)/20 sisi TSS LN B C A
trip
150(70),
OHL feeder,
54 TTR Teleprotection trip receive TSS LN P C A
Cable feeder,
OHL feeder,
55 TTT Teleprotection trip transmit TSS LN P C A
Cable feeder,
Bus Coupler,
OHL feeder,
56 UFRT Under frequency relay trip TSS LN B C A
Cable feeder,
TRF 150(70)/20 sisi 20,
57 UT Unit trip Generator, TSS H B C A

58 VACF VAC failure  Gardu induk, TSS H G C A

59 VDCF VDC failure  Gardu induk, TSS H G C A


OHL feeder,
Cable feeder,
60 VRT Voltage relay trip TRF 150(70)/20 sisi 20, TSS LN B C A
Capacitor,
Reactor, 
61 VS Voltage status Busbar, TSS LN B C I

KETERANGAN:
 A =  Alarm (audible alarm, flashing display, etc)
I = Indikasi (normal condition)
TSS = Telesignal single
TSD = Telesignal double
H = Hardwiring

LN
D =
= Logical
per Network
Device (peralatan)
B = per Bay
G = per GI
P = per Pembangkit
F = per Fasa
C = Common

15

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 29/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

 
1-2: Telemeasurement 

Tabel 2. Daftar telemeasurement

Sumber Bagian Jumlah


No Kode Fungsi Implementasi H/LN D/B/G/P F/C

Busbar,
1 F Frekuensi Ohl feeder, H G C
Cable feeder, 

Bus Coupler,
Bus Section,
OHL Feeder,
2 I Arus Cable Feeder, H B F
IBT 500(275)/150 sisi 150,
IBT 150/70 sisi 150,
IBT 150/70 SISI 70,
Gen Transf,

OHL Feeder,
Cable Feeder,

3 P Daya Aktif IBT 500(275)/150


IBT SISI 150,
150/70 SISI 70, LN B C
TRF 150(70)/20 SISI 20,
Gen Transf,
Generator

Generator,
4 POAQ Real Power Setting
Blok
H D C

Generator,
5 PRAQ Max Power Variation Setting
Blok
H D C

OHL Feeder,
Cable Feeder,
IBT 500(275)/150 SISI 150,
IBT 150/70 SISI 70,
6 Q Daya Reaktif
TRF 150(70)/20 SISI 20,
LN B C

Kapasitor,
Reaktor,
Gen Transf,
Generator

Busbar,
Ohl feeder,
7 V Tegangan
Cable feeder,
H B F
IBT 150/70 sisi 70,
Generator,

KETERANGAN:
Logical Node pada TM apabila nilai didapat melalui perhitungan beberapa parameter.
Hardwiring pada TM apabila nilai didapat melalui pengukuran dari sinyal masukan.
* Per fasa untuk single phase.

16

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 30/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

1-3: T ap C h a n g e r P o s i t i o n

Tabel 3. Daftar t a p c h a n g e r p o s i t i o n

Sumber Bagian Jumlah


No Kode Fungsi Implementasi
H/LN  D/B/G/P F/C

1 TPI Tap position indication Trafo, IBT H B C/F*

KETERANGAN:
* Per fasa untuk single phase.

1-4: R e mo t e C o n t r o l

Tabel 4. Daftar r e m o t e c o n t r o l

No Kode Fungsi Implementasi Indikasi Sumber Bagian Jumlah


RCD/RCA H/LN  D/B/G/P F/C

Remote station,
Gardu induk,
Busbar,
Bus coupler, 
Bus section, 
Ohl feeder, 
Cable feeder,
IBT 500(275)/150 sisi 150,
1 ARO  Auto reclose on/off IBT 150/70 sisi 150, RCD LN P C
IBT 150/70 sisi 70,
TRF 150(70)/20 sisi 150(70),
TRF 150(70)/20 sisi 20,
Capacitor,
Reactor,
Diameter,
Gen transf,
Generator,
Blok, 

IBT 150/70 SISI 150,


2 AVRAM AVR auto/manual   RCD LN D C
TRF 150(70)/20 sisi 150(70),

Bus coupler,
Bus section,
Ohl feeder,
Cable feeder,
Ibt 150/70 sisi 150,
3 CB Circuit breaker closed/opened RCD H D C
Ibt 150/70 sisi 70,
Trf 150(70)/20 sisi 150(70),
Trf 150(70)/20 sisi 20,
Capacitor,
Reactor,
Diameter,

GENERATOR,
4 N Load freq control n_level RCA H P C
BLOK,

GENERATOR,
5 POOP Real power set point RCA H P C
BLOK,

GENERATOR,
6 PROP Max power variation set point RCA H P C
BLOK,

IBT 150/70 SISI 150,


7 TC Tap changer raise/lower RCD LN D C
TRF 150(70)/20 SISI 150(70),

17

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 31/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

LAMPIRAN 2. Teleinformasi pada Berbagai Konfigurasi Gardu Induk

TA-01: Konfigurasi Umum Pada 1½ Breaker GITET

KONFIGURASI UMUM PADA 1½ BREAKER GITET TA-01

BAY REAKTOR BAY GENERATOR

P
Q
V

P
Q Q
I
BUSBAR-A

L/R L/R

L/R L/R

L/R L/R

BUSBAR-B
V

L/R

P P
Q Q
V V
I L/R
I

BAY FEEDER BAY IBT

 
Gambar 8. Konfigurasi SLD 1 ½ breaker

18

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 32/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 5. Teleinformasi data untuk konfigurasi umum pada 1½ breaker

Group Bay Data No Kode Fungsi Tipe Jmlh

BUAL Building alarm  A  1 

COM Communication faulty  A  1 


IEDF Ied bay level faulty  A  1 
LOR Lock out relay trip  A  1 
TSS SLF Station level faulty  A  1 
SF Supply failure  A  1 
VACF VAC failure  A  1 
GARDU
VDCF VDC failure  A  1 
INDUK
CSO Check synchronizing override I 1
DCB Dummy circuit breaker closed/opened I 1
TSD GRM Genset ready/maintenance I 1)*
LRHMI Local/remote for local hmi I 1
SIB I 1
CSO Software interlocking override
Check synchronizing by passed 1
RCD
DCB Dummy circuit breaker closed/opened 1
F Frekuensi 2
TM
V Tegangan 2
MPUF IED MPU faulty  A 2
BUSBAR BP Busbar protection  A 1
TSS
VS Voltage status I 2 
VTMT Voltage transformer MCB trip  A  2 
TSD ES Earth switch closed/opened I 2 
BF Bay fault  A  1
BRF Breaker fault  A  1
DTT Direct transfer trip  A  1 
CCP Circulating current protection trip  A  1 
TSS
CBF Circuit breaker failure trip  A 1 
OCGF Over current ground fault  A 1
DIAMETER SZP Short zone protection trip  A  1 
DI Diameter isolator switch closed/opened I 6
TSD CB Circuit breaker closed/opened I 3
LRBCU Local remote for BCU I 3
RCD CB Circuit breaker closed/opened 3
F Frekuensi 1
V Tegangan 1
I Arus 1
TM P Daya aktif 1
Q Daya reaktif 1
 AMF  Amperes fault 8
BF Bay fault  A  1
BRF Breaker fault  A  1
CSP Check synchronizing in progress I 1
 ARL Circuit breaker auto reclose lock out I 1
 AR Circuit breaker auto reclose success I 1
CBF Circuit breaker failure trip  A  1
DTT Direct transfer trip  A  1

DEF Directional earth fault  A  1


DISZ1 Distance protection zone 1  A  1

19

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 33/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Group Bay Data No Kode Fungsi Tipe Jmlh

DISZ2 Distance protection zone 2  A  1


DISZ3 Distance protection zone 3  A  1
DISZ4 Distance protection zone 4  A  1
BAY FEEDER TSS LCD Line current differential  A  1
OCPT Oil cable pressure trip (Cable feeder)  A  1
OCGF Over current ground fault  A  1
SOTF Switch on to fault  A  1
TTR Teleprotection trip receive  A  1
TTT Teleprotection trip transmit  A  1
UFRT Under frequency relay trip  A  1
VRT Voltage relay trip  A  1
 ARO  Auto reclose on/off I  1
ES Earth switch closed/opened I  1
TSD
LI Line isolator switch closed/opened I  1

LRBCU Local/remote for BCU I  1


TC TPI Tap position indication I 1
I Arus 1
P Daya aktif 1
TM Q Daya reaktif 1
V Tegangan 1
BF Bay fault  A  1
BRF Breaker fault  A  1
CSP Check synchronizing in progress I  1
TCH Tap changer high limit I  1
TCIP Tap changer in progress I  1
TSS I  1
BAY IBT TCL
TEA Tap changer low
Temperature limit
alarm  A  1
TRA Transformer alarm  A 1
TRBPT Transformer back up protection trip  A 1
TRMPT Transformer main protection trip  A 1
VRT Voltage relay trip  A 1
 AVRAM  AVR auto/manual I 1
CB Circuit breaker closed/opened I 1
TSD
LI Line isolator switch closed/opened I  2
LRBCU Local/remote for BCU I 1
CB Circuit breaker closed/opened
RCD  AVRAM  AVR auto/manual
TC Tap changer raise/lower
TM Q Daya reaktif 1
BF Bay fault  A  1
OCGF Over current ground fault  A  1
BAY TSS RA Reaktor alarm  A  1
REAKTOR RT Reaktor trip  A 1
CB Circuit breaker closed/opened I 1
TSD ES Earth switch closed/opened I 1
LI Line isolator switch closed/opened I 1
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
TM PRAQ Max power variation setting 1

20

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 34/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Group Bay Data No Kode Fungsi Tipe Jmlh

POAQ Real power setting 1


V Tegangan 1
 AQR  Automatic power factor active I 1
I 1
 AVR
BF  Automatic
Bay fault voltage regulator on/off  A 1
BAY CSP Check synchronizing in progress I 1
GENERATOR GTT Generator transformer trip  A 1
TSS GOV Governor free I 1
LFF Load freq control unit failure  A 1
UT Unit trip  A 1
VRT Voltage relay trip  A 1
ES Earth switch closed/opened I  1
GUC Generator unit run/stop I  1
TSD LI Line isolator switch closed/opened I  1
LFA Load freq available/not available I  1
LFC Load freq control on/off switch I  1
LFR Load freq request on/off I 1
KETERANGAN:
 A =  Alarm
I = Indikasi
Rincian Teleinformasi diatas adalah rincian per bay  
* GRM untuk Genset di Control Center  

21

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 35/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TA-02: Konfigurasi Umum Pada 1 ½ Breaker 150 kV

TA-02

KONFIGURASI UMUM PADA 1½ BREAKER 150 KV

BAY REAKTOR BAY GENERATOR

P
Q
V

P
Q Q
I
BUSBAR - A

L/R L/R

L/R L/R L/R

L/R L/R L/R

BUSBAR - B
V

L/R
P P P
Q Q Q
V V V
I I I
L/R

BAY TRANSMISI BAY IBT BAY TRAFO TENAGA

Gambar 9. Konfigurasi umum pada 1 ½ breaker 


 150 kV

22

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 36/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 6.Teleinformasi data untuk konfigurasi umum pada 1½ breaker

Group Bay Data No Kode Fungsi Tipe Jmlh

BUAL Building alarm  A  1 


COM Communication faulty  A  1 
IEDF IED bay level faulty  A  1 
LOR Lock out relay trip  A  1 
TSS SLF Station level faulty  A  1 
SF Supply failure  A  1 
VACF VAC failure  A  1 
GARDU
VDCF VDC failure  A  1 
INDUK
CSO Check synchronizing override I 1
DCB Dummy circuit breaker closed/opened I 1
TSD GRM Genset ready/maintenance I 1)*
LRHMI Local/remote for local hmi I 1
SIB Software interlocking by passed I 1

RCD CSO Check synchronizing override 1


DCB Dummy circuit breaker closed/opened 1
F Frekuensi 2
TM
V Tegangan 2
MPUF IED MPU faulty  A 2
BUSBAR BP Busbar protection  A 1
TSS
VS Voltage status I 2 
VTMT Voltage transformer MCB trip  A  2 
TSD ES Earth switch closed/opened I 2 
BF Bay fault  A  1
BRF Breaker fault  A  1

DTT Direct transfer trip  A  1 


CCP Circulating current protection trip  A  1 
TSS
CBF Circuit breaker failure trip  A 1 
OCGF Over current ground fault  A 1
DIAMETER
SZP Short zone protection trip  A  1 
DI Diameter isolator switch closed/opened I 6
TSD CB Circuit breaker closed/opened I 3
LRBCU Local remote for BCU I 3
RCD CB Circuit breaker closed/opened 3
F Frekuensi 1
V Tegangan 1

TM I Arus 1
1
P Daya aktif
Q Daya reaktif 1
 AMF  Amperes fault 8
BF Bay fault  A  1
BRF Breaker fault  A  1
CSP Check synchronizing in progress I 1
 ARL Circuit breaker auto reclose lock out I 1
 AR Circuit breaker auto reclose success I 1
CBF Circuit breaker failure trip  A  1
DTT Direct transfer trip  A  1
DEF Directional earth fault  A  1
DISZ1 Distance protection zone 1  A  1
DISZ2 Distance protection zone 2  A  1

23

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 37/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Group Bay Data No Kode Fungsi Tipe Jmlh

DISZ3 Distance protection zone 3  A  1


DISZ4 Distance protection zone 4  A  1
BAY FEEDER TSS LCD Line current differential  A  1
OCPT Oil cable pressure trip (Cable feeder)  A  1
OCGF Over current ground fault  A  1
SOTF Switch on to fault  A  1
TTR Teleprotection trip receive  A  1
TTT Teleprotection trip transmit  A  1
UFRT Under frequency relay trip  A  1
VRT Voltage relay trip  A  1
 ARO  Auto reclose on/off I  1
ES Earth switch closed/opened I  1
TSD
LI Line isolator switch closed/opened I  1
LRBCU Local/remote for BCU I  1

TC TPI Tap position indication I 1


I Arus 1
P Daya aktif 1
TM Q Daya reaktif 1
V Tegangan 1
BF Bay fault  A  1
BRF Breaker fault  A  1
CSP Check synchronizing in progress I  1
TCH Tap changer high limit I  1
TCIP Tap changer in progress I  1
TSS
TCL Tap changer low limit I  1
BAY IBT
 A  1
TEA
TRA Temperature alarm
Transformer alarm  A 1
TRBPT Transformer back up protection trip  A 1
TRMPT Transformer main protection trip  A 1
 AVRAM  AVR auto/manual I 1
CB Circuit breaker closed/opened I 1
TSD
LI Line isolator switch closed/opened I  2
LRBCU Local/remote for BCU I 1
CB Circuit breaker closed/opened
RCD  AVRAM  AVR auto/manual
TC Tap changer raise/lower
TC TPI Tap position indication I 1
I Arus 1
P Daya aktif 1
TM Q Daya reaktif 1
V Tegangan 1
BF Bay fault  A  1
BRF Breaker fault  A  1
TCH Tap changer high limit I  1
TCIP Tap changer in progress I  1
BAY I  1
TCL Tap changer low limit
TRAFO
TSS TEA Temperature alarm  A  1
TENAGA
TET Temperature trip  A  1
TRA Transformer alarm  A  1
TRBPT Transformer back up protection trip  A  1

24

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 38/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Group Bay Data No Kode Fungsi Tipe Jmlh

TRMPT Transformer main protection trip  A  1


UFRT Under frequency relay trip  A  1
VRT Voltage relay trip  A  1
I 1
 AVRAM
ES  AVR
Earthauto/manual
switch closed/opened I 1
TSD
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for BCU I 1
 AVRAM  Avr auto/manual 1
RCD
TC Tap changer raise/lower 1
TM Q Daya reaktif 1
BF Bay fault  A  1
OCGF Over current ground fault  A  1
BAY TSS RA Reaktor alarm  A  1
REAKTOR RT Reaktor trip  A 1
CB Circuit breaker closed/opened I 1
TSD ES Earth switch closed/opened I 1
LI Line isolator switch closed/opened I 1
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
TM PRAQ Max power variation setting 1
POAQ Real power setting 1
V Tegangan 1
 AQR  Automatic power factor active I 1
 AVR  Automatic voltage regulator on/off I 1
BF Bay fault  A 1
BAY CSP Check synchronizing in progress I 1
GENERATOR GTT Generator transformer trip  A 1
TSS
GOV Governor free I 1
LFF Load freq control unit failure  A 1
UT Unit trip  A 1
ES Earth switch closed/opened I  1
GUC Generator unit run/stop I  1
TSD LI Line isolator switch closed/opened I  1
LFA Load freq available/not available I  1
LFC Load freq control on/off switch I  1
LFR Load freq request on/off I 1
KETERANGAN:
 A =  Alarm
I = Indikasi
Rincian Teleinformasi diatas adalah rincian per bay  

25

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 39/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TA-03: Konfigurasi Umum Pada D o u b l e B u s b a r

TA-03

KONFIGURASI UMUM PADA DOUBLE BUSBAR


BAY REAKTOR BAY GENERATOR

P
Q
V

P
Q Q
I
BAY KOPEL

L/R L/R L/R

BUSBAR - A

BUSBAR - B

L/R L/R L/R

L/R
P P P
Q Q Q
V V V
I I I

BAY FEEDER BAY TRAFO TENAGA BAY IBT

 
Gambar 10. Konfigurasi umum pada d o u b l e b u s b a r

26

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 40/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 7. Teleinformasi data untuk konfigurasi umum pada d o u b l e b u s b a r

Group Bay Data No Kode Fungsi Tipe Jmh

BUAL Building alarm  A 1


COM Communication faulty  A 1
IEDF IED bay level faulty  A 1
LOR Lock out relay trip  A 1
TSS SLF Station level faulty  A 1
SF Supply failure  A 1
VACF VAC failure  A 1
VDCF VDC failure  A 1
GARDU
INDUK CSO Check synchronizing override I 1
Dummy circuit breaker
DCB I 1
closed/opened
TSD
GRM Genset ready/maintenance I 1)*
LRHMI Local/remote for local hmi I 1
SIB Software interlocking by passed I 1
CSO Check synchronizing override 1
RCD Dummy circuit breaker
DCB 1
closed/opened
F Frekuensi 2
TM
V Tegangan 2
BP Busbar protection  A 1
BUSBAR
TSS VS Voltage status I 2 
VTMT Voltage transformer MCB trip  A  2 
TSD ES Earth switch closed/opened I 2 
TM I  Arus 1
BF Bay fault  A 1
BRF Breaker fault  A 1
CSP Check Synchronizing In Progress  A 1
TSS
OCGF Over current ground fault  A 1
KOPEL
UFRT Under frequency relay trip  A 1
BI Bus isolator switch closed/opened I 2
TSD CB Circuit breaker closed/opened I 1
LRBCU Local remote for BCU I 1
RCD CB Circuit breaker closed/opened 1
 AMF  Amperes fault 8
F Frekuensi 1
I Arus 1
TM P Daya aktif 1
Q Daya reaktif 1
V Tegangan 1
 AR Circuit breaker auto reclose success I 1
 ARL Circuit breaker auto reclose lock out I 1
BF Bay fault  A 1
BRF Breaker fault  A 1
CSP Check synchronizing in progress I 1
DEF Directional earth fault  A 1
BAY DISZ1 Distance protection zone 1  A 1
FEEDER DISZ2 Distance protection zone 2  A 1
TSS
DISZ3 Distance protection zone 3  A 1
DISZ4 Distance protection zone 4  A 1

27

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 41/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Group Bay Data No Kode Fungsi Tipe Jmh

DTT Direct transfer trip  A 1


LCD Line current differential  A 1
OCGF Over current ground fault  A 1
OCPT** Oil cable pressure trip  A 1
SOTF Switch on to fault  A 1
TTR Teleprotection trip receive  A 1
TTT Teleprotection trip transmit  A 1
UFRT Under frequency relay trip  A 1
VRT Voltage relay trip  A 1
 ARO  Auto reclose on/off I 1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
TSD
ES Earth switch closed/opened I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCD CB Circuit breaker closed/opened I 1
TC TPI Tap position indication I 1
I Arus 1
P Daya aktif 1
TM
Q Daya reaktif 1
V Tegangan 1
BF Bay fault  A 1
BRF Breaker fault  A 1
CSP Check synchronizing in progress I 1
TCH Tap changer high limit  A 1

TSS TCIP Tap changer in progress I


 A 1
1
TCL Tap changer low limit
BAY IBT
TEA Temperature alarm  A 1
TRA Transformer alarm  A 1
TRBPT Transformer back up protection trip  A 1
TRMPT Transformer main protection trip  A 1
 AVRAM  Avr auto/manual I 1
BI Bus isolator switch closed/opened I 2
TSD
CB Circuit breaker closed/opened I 1
LRBCU Local/remote for bcu I 1
 AVRAM  Avr auto/manual 1
RCD CB Circuit breaker closed/opened 1
TC Tap changer raise/lower 1
TC TPI Tap position indication I 1
P Daya aktif 1
TM
Q Daya reaktif 1
BF Bay fault  A  1
BRF Breaker fault  A  1
TCH Tap changer high limit  A  1
TCIP Tap changer in progress I  1
TCL Tap changer low limit  A  1
BAY TEA Temperature alarm  A  1
TRAFO TSS TRA Transformer alarm  A  1
TENAGA TRBPT Transformer back up protection trip  A  1
TRMPT Transformer main protection trip  A  1

28

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 42/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Group Bay Data No Kode Fungsi Tipe Jmh

UFRT Under frequency relay trip  A  1


VRT Voltage relay trip  A  1
 AVRAM  AVR auto/manual I 1
BI Bus isolator switch closed/opened I 2
TSD CB Circuit breaker closed/opened I 2
LRBCU Local remote for BCU I 1
 AVRAM  AVR auto/manual 1
RCD CB Circuit breaker closed/opened 1
TC Tap changer raise/lower 1
TM Q Daya reaktif 1
BF Bay fault  A 1
BRF Breaker fault  A 1
OCGF Over current ground fault  A 1
TSS
RA Reaktor alarm  A 1
RT Reaktor trip  A 1
BAY VRT Voltage relay trip  A 1
REAKTOR BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
TSD
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCD CB Circuit breaker closed/opened 1
I Arus 1
P Daya aktif 2
POAQ Real power setting 1
TM
PRAQ Max power variation setting 1
Q Daya reaktif 2
V Tegangan 1
 AQR  Automatic power factor active I 1
 AVR  Automatic voltage regulator on/off I 1
BF Bay fault  A 1
BRF Breaker fault  A 1
TSS
GOV Free acting governor active I 1
GTT Generator transformer trip  A 1
LFF Load freq control unit failure  A 1
UT Unit trip  A 1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
GUC Generator unit run/stop I 1
LFA Load freq available/not available I 1
TSD LFC Load freq control on/off switch I 1
BAY
LFR Load freq request on/off I 1
GENERATOR
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for bcu I 1
PSO Power station operated I 1
N Load freq control n_level 1
RCA POOP Real power set point 1
PROP Max power variation set point 1
RCD LFR Load freq request on/off 1

KETERANGAN:
*)
  = GRM untuk Genset contro center  

29

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 43/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

 A =  Alarm 
I = Indikasi
Rincian Teleinformasi diatas adalah rincian per bay  

TA-04: Konfigurasi Umum Pada S i n g l e B u s b a r  


 

TA-04

KONFIGURASI UMUM PADA SINGLE BUSBAR

BAY REAKTOR BAY GENERATOR

P
Q
V

P
Q Q
I

L/R L/R

BUSBAR

L/R L/R L/R

L/R
P P P
Q Q Q
V V V
I I I

BAY TRANSMISI BAY TRAFO TENAGA BAY IBT

 
Gambar 11. Konfigurasi umum pada s i n g l e b u s b a r

30

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 44/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 8. Teleinformasi data untuk konfigurasi umum pada s i n g l e b u s b a r

Group Bay Data No Kode Fungsi Tipe Jmh

BUAL Building alarm  A 1


COM Communication faulty  A 1
IEDF Ied bay level faulty  A 1
LOR Lock out relay trip  A 1
TSS SLF Station level faulty  A 1
SF Supply failure  A 1
VACF VAC failure  A 1
VDCF VDC failure  A 1
GARDU
INDUK CSO Check synchronizing override I 1
Dummy circuit breaker
DCB I 1
closed/opened
TSD
GRM Genset ready/maintenance I 1)*
LRHMI Local/remote for local hmi I 1
SIB Software interlocking by passed I 1
CSO Check synchronizing override 1
RCD Dummy circuit breaker
DCB 1
closed/opened
F Frekuensi 1
TM
V Tegangan 1
BP Busbar protection  A 1
BUSBAR
TSS VS Voltage status I 1 
VTMT Voltage transformer MCB trip  A  1 
TSD ES Earth switch closed/opened I 1 
 AMF  Amperes fault 8
F Frekuensi 1
I Arus 1
TM
P Daya aktif 1
Q Daya reaktif 1
V Tegangan 1
 AR Circuit breaker auto reclose success I 1
 ARL Circuit breaker auto reclose lock out I 1
BF Bay fault  A 1
BRF Breaker fault  A 1
CSP Check synchronizing in progress I 1
DEF Directional earth fault  A 1
DISZ1 Distance protection zone 1  A 1
DISZ2 Distance protection zone 2  A 1
DISZ3 Distance protection zone 3  A 1
DISZ4 Distance protection zone 4  A 1
BAY DTT Direct transfer trip  A 1
FEEDER LCD Line current differential  A 1
OCGF Over current ground fault  A 1
TSS
OCPT** Oil cable pressure trip  A 1
SOTF Switch on to fault  A 1
TTR Teleprotection trip receive  A 1
TTT Teleprotection trip transmit  A 1
UFRT Under frequency relay trip  A 1
VRT Voltage relay trip  A 1
TSD  ARO  Auto reclose on/off I 1

31

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 45/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Group Bay Data No Kode Fungsi Tipe Jmh

BI Bus isolator switch closed/opened I 1


CB Circuit breaker closed/opened I 1
ES Earth switch closed/opened I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCD CB Circuit breaker closed/opened I 1
TC TPI Tap position indication I 1
I Arus 1
P Daya aktif 1
TM
Q Daya reaktif 1
V Tegangan 1
BF Bay fault  A 1
BRF Breaker fault  A 1
CSP Check synchronizing in progress I 1

TCH Tap changer high limit  A 1


TCIP Tap changer in progress I 1
TSS
TCL Tap changer low limit  A 1
BAY IBT
TEA Temperature alarm  A 1
TRA Transformer alarm  A 1
TRBPT Transformer back up protection trip  A 1
TRMPT Transformer main protection trip  A 1
 AVRAM  Avr auto/manual I 1
BI Bus isolator switch closed/opened I 1
TSD
CB Circuit breaker closed/opened I 1
LRBCU Local/remote for bcu I 1

 AVRAM  Avr auto/manual 1


RCD CB Circuit breaker closed/opened 1
TC Tap changer raise/lower 1
TC 1 TPI Tap position indication I 1
P Daya aktif 1
TM
Q Daya reaktif 1
BF Bay fault  A 1
BRF Breaker fault  A 1
TCH Tap changer high limit  A 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit  A 1
TSS TEA Temperature alarm  A 1
BAY TRA Transformer alarm  A 1
TRAFO TRBPT Transformer back up protection trip  A 1
TENAGA TRMPT Transformer main protection trip  A 1
UFRT Under frequency relay trip  A 1
VRT Voltage relay trip  A 1
 AVRAM  AVR auto/manual I 1
BI Bus isolator switch closed/opened I 1
TSD
CB Circuit breaker closed/opened I 2
LRBCU Local remote for BCU I 1
 AVRAM  AVR auto/manual 1
RCD CB Circuit breaker closed/opened 1
TC Tap changer raise/lower 1
BAY TM Q Daya reaktif 1

32

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 46/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Group Bay Data No Kode Fungsi Tipe Jmh


REAKTOR BF Bay fault  A 1
BRF Breaker fault  A 1
OCGF Over current ground fault  A 1
TSS
 A
RA
RT Reaktor
Reaktor alarm
trip  A 1
1
VRT Voltage relay trip  A 1
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
TSD
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCD CB Circuit breaker closed/opened 1
I Arus 1
P Daya aktif 2
POAQ Real power setting 1
TM
PRAQ Max power variation setting 1
Q Daya reaktif 2
V Tegangan 1
 AQR  Automatic power factor active I 1
 AVR  Automatic voltage regulator on/off I 1
BF Bay fault  A 1
BRF Breaker fault  A 1
TSS
GOV Free acting governor active I 1
GTT Generator transformer trip  A 1
BAY LFF Load freq control unit failure  A 1
GENERATOR UT Unit trip  A 1
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
GUC Generator unit run/stop I 1
LFA Load freq available/not available I 1
TSD LFC Load freq control on/off switch I 1
LFR Load freq request on/off I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for bcu I 1
PSO Power station operated I 1
N Load freq control n_level 1
RCA POOP Real power set point 1
PROP Max power variation set point 1
RCD LFR Load freq request on/off 1
KETERANGAN:
 A =  Alarm
I = Indikasi
Rincian Teleinformasi diatas adalah rincian per bay  
* = GRM untuk Genset control center  

33

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 47/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-01: In t e r b u s T r a n s f o r me r  
 

(Seco nd ary Sid e Conn ected to 1½Br eaker )

TB-01
INTERBUS TRANSFORMER
Secondary Side Connected to 1½ Breaker 
BUSBAR (IRCC)

L/R

P
BUSBAR - A
Q
V
I
}

Dioperasikan dari IRCC

Download to RCC
Dioperasikan dari RCC
BUSBAR - B

Gambar 12. Interbus tran sform er (secondary side co nnected to 1½breaker)

34

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 48/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 9. Teleinformasi data untuk i n t e r b u s t r a n s f o r m e r  


 (s e c o n d a r y s i d e c o n n e c t e d   to 1½
breaker  )

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indication I 1


I Arus 1
P Daya aktif 1
TM Q Daya reaktif 1
V Tegangan 1
BF Bay fault  A  1
BRF Breaker fault  A  1
CSP Check synchronizing in progress I  1
TCH Tap changer high limit I  1
TCIP Tap changer in progress I  1
TSS
 
TCL Tap changer low limit I 1
TEA Temperature alarm  A  1
TRA Transformer alarm  A 1
TRBPT Transformer back up protection trip  A 1
TRMPT Transformer main protection trip  A 1
 AVRAM  AVR auto/manual I 1
ES Earth switch closed/opened I 2
TSD
LI Line isolator switch closed/opened I  2
LRBCU Local/remote for bcu I 1
 AVRAM  Avr auto/manual 1
RCD
TC Tap changer raise/lower 1

35

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 49/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-02: In t e r b u s T r a n s f o r me r

(S e c o n d a r y S i d e C o n n e c t ed t o D o u b l e B u s b a r ) 

TB-02
INTERBUS TRANSFORMER
Secondary Side Connected to Double Busbar 
BUSBAR (IRCC or RCC)

L/R

}
Q
V
I

Operation Responsibility
L/R by IRCC or RCC

Operation Responsibility Download to RCC


BUSBAR - A by RCC

BUSBAR - B

Gambar 13. I n t er b u s t r a n s f o r m e r (s e c o n d a r y s i d e c o n n e c t e d t o d o u b l e b u s b a r )  

36

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 50/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 10. Teleinformasi data untuk i n t e r b u s t r a n s f o r m e r  


 (s e c o n d a r y s i d e c o n n e c t e d t o
double bus bar)

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indication I 1


I Arus 1
P Daya aktif 1
TM Q Daya reaktif 1
V Tegangan 1
BF Bay fault  A  1
BRF Breaker fault  A  1
CSP Check synchronizing in progress I  1
TCH Tap changer high limit I  1
TCIP Tap changer in progress I  1
TSS
TCL Tap changer low limit I  1
TEA Temperature alarm  A  1

TRA Transformer alarm  A 1


TRBPT Transformer back up protection trip  A 1
TRMPT Transformer main protection trip  A 1
 AVRAM  AVR auto/manual I 1
BI Bus isolator switch closed/opened I 2-4*)
CB Circuit breaker closed/opened I 2
TSD CSO Check synchronizing override I 1
ES Earth switch closed/opened I 2
LI Line isolator switch closed/opened I  1-0*)
LRBCU Local/remote for bcu I 1
 AVRAM  Avr auto/manual 1

RCD CB Circuit breaker closed/opened I 2


1
TC Tap changer raise/lower
KETERANGAN:
*)
 = (Primary Side Connected to 1½ Breaker) –(Primary Side Connected to Double Busbar)

37

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 51/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-03: Interbus Transformer

(Secondary Side Connected to Single Busbar)

TB-03
INTERBUS TRANSFORMER
Secondary Side Connected to Single Busbar 
BUSBAR (IRCC or RCC)

L/R

}
Q
V
I

Operation Responsibility
by IRCC or RCC

L/R

Operation Responsibility Download to RCC


BUSBAR by RCC

Gambar 14. I n t er b u s t r a n s f o r m e r (s e c o n d a r y s i d e c o n n e c t e d t o s i n g l e b u s b a r )  

38

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 52/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 11. Teleinformasi data untuk i n t e r b u s t r a n s f o r m e r  


 (s e c o n d a r y s i d e c o n n e c t e d t o
s i n g l e b u s b a r )   

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indication I 1


I Arus 1
P Daya aktif 1
TM Q Daya reaktif 1
V Tegangan 1
BF Bay fault  A  1
BRF Breaker fault  A  1
CSP Check synchronizing in progress I  1
TCH Tap changer high limit I  1
TCIP Tap changer in progress I  1
TSS
TCL Tap changer low limit I  1
TEA Temperature alarm  A  1

TRA Transformer alarm  A 1


TRBPT Transformer back up protection trip  A 1
TRMPT Transformer main protection trip  A 1
 AVRAM  AVR auto/manual I 1
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
TSD CSO Check synchronizing override I 1
ES Earth switch closed/opened I 2
LI Line isolator switch closed/opened I  1-0*)
LRBCU Local/remote for bcu I 1
 AVRAM  Avr auto/manual 1

RCD CB Circuit breaker closed/opened I 2


1
TC Tap changer raise/lower
KETERANGAN:
*)
 = (Primary Side Connected to 1½ Breaker) –(Primary Side Connected to Double Busbar )

39

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 53/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-04: Interbus Transformer

(Secondary Side Connected to 1½ Breaker Dilengkapi Shunt Reaktor Pada


Kumparan Tersier)

INTERBUS TRANSFORMER TB-04

Secondary Side Connected to 1½ Breaker 


Dilengkapi Shunt Reaktor Pada Kumparan Tersier 
BUSBAR (IRCC)

L/R
Q

}
P
Q
V
I
BUSBAR - A

Operation Responsibility
by IRCC

Operation Responsibility Download to RCC


by RCC
BUSBAR - B

 
Gambar 15. S ec o n d a r y s i d e   terhubung 1½ breaker dilengkapi d h u n t reaktor pada kumparan
tersier

40

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 54/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 12. Teleinformasi data untuk i n t e r b u s t r a n s f o r m e r  


 (s e c o n d a r y s i d e c o n n e c t ed t o  
 1½
 dilengkapi s h u n t  
breaker   reaktor pada kumparan tersier)

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indication I 1


I Arus 1
P Daya aktif 1
TM Q Daya reaktif 2
V Tegangan 1
BF Bay fault  A  1
BRF Breaker fault  A  1
CSP Check synchronizing in progress I  1
OCGF Over current ground fault  A 1
RA Reaktor alarm  A 1
RT Reaktor trip  A 1
TCH Tap changer high limit I  1
TSS
TCIP Tap changer in progress I  1
TCL Tap changer low limit I  1
TEA Temperature alarm  A  1
TRA Transformer alarm  A 1
TRBPT Transformer back up protection trip  A 1
TRMPT Transformer main protection trip  A 1
VRT Voltage relay trip  A 1
 AVRAM  AVR auto/manual I 1
ES Earth switch closed/opened I 2
TSD
LI Line isolator switch closed/opened I  3
LRBCU Local/remote for bcu I 1

RCD  AVRAM  Avr auto/manual 1


1
TC Tap changer raise/lower

41

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 55/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-05: In t e r b u s T r a n s f o r me r  
 

(S ec o n d a r y S i d e Co n n e c t e d t o D o u b l e B u s b a r    Dilengkapi Shunt Reaktor


Pada Kumparan Tersier)

INTERBUS TRANSFORMER TB-05

Secondary Side Connected to Double Busbar 


Dilengkapi Shunt Reaktor Pada Kumparan Tersier 

BUSBAR (IRCC or RCC)

L/R

}
P
Q
V
I

Operation Responsibility
by IRCC or RCC

L/R

Operation Responsibility Download to RCC


by RCC
BUSBAR - A

BUSBAR - B

Gambar 16. S ec o n d a r y s i d e c o n n e c t e d t o d o u b l e b u s b a r  
 dilengkapi s h u n t reaktor pada
kumparan tersier

42

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 56/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 13.Teleinformasi data untuk i n t e r b u s t r a n s f o r m e r  


 (s e c o n d a r y s i d e c o n n e c t e d t o
double busbar  dilengkapi s h u n t   reaktor pada kumparan tersier)

Data No Kode Fungsi Tipe Jmh


TC TPI Tap position indication I 1
I Arus 1
P Daya aktif 1
TM
Q Daya reaktif 2
V Tegangan 1
BF Bay fault  A 3
BRF Breaker fault  A 3
CSP Check synchronizing in progress  A 1
OCGF Over current ground fault  A 1
OLSRX Overload shedding receive  A 1
OLSTX Overload shedding transmit  A 1
RA Reaktor alarm  A 1
RT Reaktor trip  A 1
TSS TCH Tap changer high limit  A 1
TCIP Tap changer in progress  A 1
TCL Tap changer low limit  A 1
TRA Temperatur alarm  A 1
TEA Temperatur alarm  A 1
TET Temperatur trip  A 1
TRBPT Transformer backup protection trip  A 1
TRMPT Transformer main protection trip  A 1
VRT Volage relay trip  A 1
 AVRAM  AVR auto/manual I 1
CB Circuit breaker closed/opened I 2
TSD ES Earthing switch closed/opened I 3
LI Line isolator switch closed/opened I 3
LRBCU Local/remote for BCU I 2
 AVRAM  AVR auto/manual 1
RCD CB Circuit breaker closed/opened 2
TC Tap changer raise/lower 1
KETERANGAN:
*)
 = (Primary Side Connected to 1½ Breaker )-(Primary Side Connected to Double Busbar ) 

43

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 57/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-06: In t e r b u s T r a n s f o r me r  
 

(S e c o n d a r y S i d e C o n n e c t e d t o S i n g l e B u s b a r   Dilengkapi S h u n t Reaktor Pada


Kumparan Tersier)

INTERBUS TRANSFORMER TB-06

Secondary Side Connected to Single Busbar 


Dilengkapi Shunt Reaktor Pada Kumparan Tersier 

BUSBAR (IRCC or RCC)

L/R

}
P
Q Q
V
I

Operation Responsibility
by IRCC or RCC

L/R

Operation Responsibility Download to RCC


by RCC

BUSBAR

Gambar 17. S ec o n d a r y s i d e c o n n e c t e d t o s i n g l e b u s b a r   dilengkapi s h u n t reaktor pada


kumparan tersier

44

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 58/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 14. Teleinformasi data untuk i n t e r b u s transformer (s e c o n d a r y s i d e c o n n e c t ed t o   


 dilengkapi s h u n t  
single busbar   reaktor pada kumparan tersier) 

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indication I 1


 AMF  Amperes fault 8
I Arus 6
TM P Daya aktif 1
Q Daya reaktif 2
V Tegangan 6
BF Bay fault  A 3
BRF Breaker fault  A 3
CSP Check synchronizing in progress I 1
OCGF Over current ground fault  A 1
RA Reaktor alarm  A 1

RT Reaktor trip  A 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TSS
TCL Tap changer low limit I 1
TEA Temperature alarm  A 1
TET Temperature trip  A 1
TRA Transformer alarm  A 1
TRBPT Transformer back up protection trip  A 1
TRMPT Transformer main protection trip  A 1
UFRT Under frequency relay trip  A 1
VRT Voltage relay trip  A 1

 AVRAM  AVR auto/manual I 1


BI Bus isolator switch closed/opened I 2
TSD CB Circuit breaker closed/opened I 4
LI Line isolator switch closed/opened I 3
LRBCU Local/remote for BCU I 2
 AVRAM  AVR auto/manual 1
RCD CB Circuit breaker closed/opened 4
TC Tap changer raise/lower 1
KETERANGAN:
*)
 = (Primary Side Connected to 1½ Breaker) – (Secondary Side Connected to Single Busbar) 

45

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 59/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-07: Bay Trafo Tenaga Pada Konfigurasi 1½ Breaker  

TB-07
BAY TRAFO TENAGA
PADA KONFIGURASI 1½ BREAKER
BUSBAR - A

BUSBAR - B

P
Q
TEGANGAN TINGGI V
I
Batas wewenang

TEGANGAN MENENGAH

DOUBLE BUSBAR

Gambar 18. B ay  trafo tenaga pada konfigurasi 1½ breaker

46

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 60/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 15. Teleinformasi data untuk b a y trafo tenaga pada konfigurasi 1½ breaker 
 

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indicatioan I 1


 AMF Amperes fault 8
I Arus 6
TM P Daya aktif 1
Q Daya reaktif 1
V Tegangan 3
BF Bay fault  A 2
BRF Breaker fault  A 2
CSP Check synchronizing in progress I 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit I 1
TSS TEA Temperature alarm  A 1
TET Temperature trip  A 1
TRA Transformer alarm  A 1
TRBPT Transformer back up protection trip  A 1
TRMPT Transformer main protection trip  A 1
UFRT Under frequency relay trip  A 1
VRT Voltage relay trip  A 1
 AVRAM  AVR auto/manual I 1
BI Bus isolator switch closed/opened I 2
TSD CB Circuit breaker closed/opened I 2
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for BCU I 1
 AVRAM  AVR auto/manual 1
RCD CB Circuit breaker closed/opened 2
TC Tap changer raise/lower 1

47

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 61/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-08: Bay Trafo Tenaga Pada Konfigurasi Double Busbar

TB-08
BAY TRAFO TENAGA
PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A

BUSBAR - B

L/R

P
Q
TEGANGAN TINGGI V
I

Batas wewenang

TEGANGAN MENENGAH

DOUBLE BUSBAR

 
Gambar 19. B ay  trafo tenaga pada konfigurasi d o u b l e b u s b a r

48

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 62/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 16. Teleinformasi data untuk b ay  trafo tenaga pada konfigurasi d o u b l e b u s b a r  


 

Data No Kode Fungsi Tipe Jmh


TC TPI Tap position indication I 1
P Daya aktif 1
TM Q Daya reaktif 1
BF Bay fault  A 1
BRF Breaker Fault  A 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit I 1
TSS
TEA Temperatur Alarm  A 1
TET Temperatur trip  A 1
TRA Transformer Alarm  A 1
TRBPT Transformer Backup Protection Trip  A 1
TRMPT Transformer main Protection Trip  A 1
 AVRAM  AVR auto/manual I 1
BI Bus isolator switch closed/opened I 2
TSD
CB Circuit breaker closed/opened I 1
LRBCU Local remote for BCU I 1
 AVRAM  AVR auto/manual 1
RCD CB Circuit breaker closed/opened 1

TC Tap changer raise/lower 1

49

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 63/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-09: Bay Trafo Tenaga Pada Konfigurasi Single Busbar

TB-09
BAY TRAFO TENAGA
PADA KONFIGURASI SINGLE BUSBAR

BUSBAR

L/R

P
Q
TEGANGAN TINGGI
V
I
Batas wewenang

TEGANGAN MENENGAH

DOUBLE BUSBAR

 
Gambar 20. B ay  trafo tenaga pada konfigurasi s i n g l e b u s b a r

50

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 64/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 17. Teleinformasi data untuk b ay  trafo tenaga pada konfigurasi s i n g l e b u s b a r  


 

Data No Kode Fungsi Tipe Jmh


TC 1 TPI Tap position indication I 1
P Daya aktif 1
TM Q Daya reaktif 1
BF Bay fault A 1
BRF Breaker Fault  A 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit I 1
TSS
TEA Temperatur Alarm  A 1
TET Temperatur trip  A 1
TRA Transformer Alarm  A 1
TRBPT Transformer Backup Protection Trip  A 1
TRMPT Transformer main Protection Trip  A 1
 AVRAM  AVR auto/manual I 1
BI Bus isolator switch closed/opened I 1
TSD
CB Circuit breaker closed/opened I 1
LRBCU Local remote for BCU I 1
 AVRAM  AVR auto/manual 1
RCD CB Circuit breaker closed/opened 1

TC Tap changer raise/lower 1

51

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 65/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-10: Bay Reaktor Pada Konfigurasi 1 ½ Breaker

TB-10
BAY REAKTOR
PADA KONFIGURASI 1½ BREAKER
BUSBAR - A

BUSBAR - B

Reaktor 

Gambar 21. Bay reaktor pada konfigurasi 1 ½ breaker

Tabel 18. Teleinformasi data untuk b a y reaktor pada konfigurasi 1 ½ breaker

Data No Kode Fungsi Tipe Jmh


TM Q Daya reaktif 1
BF Bay fault  A 1
BRF Breaker fault  A 1
OCGF Over current ground fault  A 1
TSS
RA Reaktor alarm  A 1
RT Reaktor trip  A 1
VRT Voltage relay trip  A 1
ES Earth switch closed/opened I 1
TSD LI Line isolator switch closed/opened I 1
LRBCU Local/remote for BCU I 1

52

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 66/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-11: Bay Reaktor Pada Konfigurasi Double Busbar

TB-11
BAY REAKTOR
PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

BUSBAR - B

L/R

Reaktor 

Gambar 22. B ay  reaktor pada konfigurasi d o u b l e b u s b a r

Tabel 19. Teleinformasi data untuk b ay  reaktor pada konfigurasi d o u b l e b u s b a r  


 

Data No Kode Fungsi Tipe Jmh


TM Q Daya reaktif 1
BF Bay fault  A 1
BRF Breaker fault  A 1
OCGF Over current ground fault  A 1
TSS
RA Reaktor alarm  A 1
RT Reaktor trip  A 1
VRT Voltage relay trip  A 1
BI Bus Isolator Switch closed/opened I 2
CB Circuit breaker closed/opened I 1
TSD
ES Earth switch closed/opened I 1
LRBCU Local/remote for BCU I 1
RCD CB Circuit breaker closed/opened 1

53

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 67/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-12: Bay Reaktor Pada Konfigurasi Single Busbar

TB-12
BAY REAKTOR
PADA KONFIGURASI SINGLE BUSBAR
BUSBAR

L/R

Reaktor 

Gambar 23. B ay  reaktor pada konfigurasi s i n g l e b u s b a r  


 

Tabel 20. Teleinformasi data untuk b ay  reaktor pada konfigurasi s i n g l e b u s b a r

Data No Kode Fungsi Tipe Jmh


TM Q Daya reaktif 1
BF Bay fault  A 1
BRF Breaker fault  A 1
OCGF Over current ground fault  A 1
TSS
RA Reaktor alarm  A 1
RT Reaktor trip  A 1
VRT Voltage relay trip  A 1
BI Bus Isolator Switch closed/opened I 1

TSD CB Circuit breaker closed/opened I 1


ES Earth switch closed/opened I 1
LRBCU Local/remote for BCU I 1
RCD CB Circuit breaker closed/opened 1

54

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 68/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-13: Bay Capasitor Pada Konfigurasi Double Busbar

TB-13

BAY KAPASITOR
PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

BUSBAR - B

L/R

Capasitor 

Gambar 24. B a y c a p a s i t o r  
 pada konfigurasi d o u b l e b u s b a r  
 

Tabel 21. Teleinformasi data untuk b ay  kapasitor pada konfigurasi d o u b l e b u s b a r

Data No Kode Fungsi Tipe Jmh


TM Q Daya reaktif 1
BF Bay fault  A 1
BRF Breaker fault  A 1
TSS
OCGF Over current ground fault  A 1
VRT Voltage relay trip  A 1
BI Bus isolator switch closed/opened I 2
TSD CB Circuit breaker closed/opened I 1
LRBCU Local remote for BCU I 1
RCD CB Circuit breaker closed/opened 1

55

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 69/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-14: Bay Capasitor Pada Konfigurasi Single Busbar

TB-14
BAY KAPASITOR
PADA KONFIGURASI SINGLE BUSBAR
BUSBAR

L/R

Capasitor 

Gambar 25. B a y c a p a s i t o r  
 pada konfigurasi s i n g l e b u s b a r  
 

Tabel 22. Teleinformasi data untuk b ay  kapasitor pada konfigurasi s i n g l e b u s b a r  


 

Data No Kode Fungsi Tipe Jmh


TM Q Daya reaktif 1
BF Bay fault  A 1
BRF Breaker fault  A 1
TSS
OCGF Over current ground fault  A 1
VRT Voltage relay trip  A 1
BI Bus isolator switch closed/opened I 1
TSD CB Circuit breaker closed/opened I 1
LRBCU Local remote for BCU I 1

RCD CB Circuit breaker closed/opened 1

56

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 70/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-15: Bay Penghantar Pada Konfigurasi 1 ½ Breaker

TB-15
BAY PENGHANTAR
PADA KONFIGURASI 1½ BREAKER

BUSBAR - A

BUSBAR - B

P
Q
V
I

Gambar 26. B a y penghantar pada konfigurasi 1 ½ breaker

Tabel 23. Teleinformasi data untuk b a y penghantar pada konfigurasi 1 ½ breaker 


 

Data No Kode Fungsi Tipe Jmh


F Frekuensi 1
V Tegangan 1
I Arus 1
TM P Daya aktif 1
Q Daya reaktif 1
 AMF  Amperes fault 8
DISZ1 Distance protection zone 1  A  2
DISZ2 Distance protection zone 2  A  2
DISZ3 Distance protection zone 3  A  2
DISZ4 Distance protection zone 4  A  2
TSS SOTF Switch on to fault  A  2
DEF Directional earth fault  A  2
LCD Line current differential  A  2
 
 AR Circuit breaker auto reclose success  A 1
 ARL Circuit breaker auto reclose lock out  A  1

57

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 71/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

CSP Check synchronizing in progress  A  1


OCGF Over current ground fault  A  1
OGSTX Overgenerating shedding transmit I 1
OLSTX Overload shedding transmit I 1
OVR Over voltage relay trip  A  1
DTT Direct transfer trip  A  1
TTR Teleprotection trip receive  A 1
TTT Teleprotection trip transmit I 1
OLSTX Overload shedding transmit I 1
OGSTX Overgenerating shedding transmit I 1
BF Bay fault  A  1
 ARO  Auto reclose On/Off I 1
TSD LI Line isolator switch closed/opened I 1
ES Earth switch closed/opened I 1

TB-16: Bay Penghantar Pada Konfigurasi Double Busbar

TB-16
BAY PENGHANTAR
PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

BUSBAR - B

L/R

P
Q
V
I

Gambar 27. B ay  penghantar pada konfigurasi d o u b l e b u s b a r  


 

58

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 72/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 24. Teleinformasi data untuk b ay  penghantar pada konfigurasi d o u b l e b u s b a r  


 

Data No Kode Fungsi Tipe Jmh


 AMF  Amperes fault 8
I Arus 1
P Daya aktif 1
TM Q Daya reaktif 1
F Frekuensi 1
V Tegangan 1
BF Bay fault  A 1
BRF Breaker Fault  A 1
CSP Check synchronizing in progress I 1
 ARL Circuit breaker auto reclose lock out  A 1
 AR Circuit breaker auto reclose success  A 1
CBF Circuit Breaker Failure Trip  A 1
DTT Direct Transfer Trip  A 1
DEF Directional earth fault  A 1
DISZ1 Distance protection zone 1  A 1
DISZ2 Distance protection zone 2  A 1
DISZ3 Distance protection zone 3  A 1
DISZ4 Distance protection zone 4  A 1
TSS
LCD Line current differential  A 1
OCGF Over Current Ground Fault  A 1
OCPT Oil cable pressure trip  A 1*)
OGSTX Overgenerating shedding transmit I 1
OLSTX Overload shedding transmit I 1
SOTF Switch on to fault  A 1
TTR Teleprotection trip receive I 1
TTT Teleprotection trip transmit I 1
UFRT Under Frequency Relay Trip  A 1
VRT Voltage relay trip  A 1
 ARO  Auto Reclose On Off I 1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
TSD
ES Earth Switch Closed/Opened I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/Remote For BCU I 1
RCD CB Circuit breaker closed/opened 1
KETERANGAN:
*) = Khusus untuk OHL Feeder  
**)
= Khusus untuk Cable Feeder  

59

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 73/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-17: Bay Penghantar Pada Konfigurasi Single Busbar

TB-17
BAY PENGHANTAR
PADA KONFIGURASI SINGLE BUSBAR
BUSBAR

L/R

P
Q
V
I

Gambar 28. B a y penghantar pada konfigurasi s i n g l e b u s b a r  


 

Tabel 25. Teleinformasi data untuk b ay  penghantar pada konfigurasi s i n g l e b u s b a r  


 

Data No Kode Fungsi Tipe Jmh


 AMF  Amperes fault 8
I Arus 1
P Daya aktif 1
TM
Q Daya reaktif 1
F Frekuensi 1
V Tegangan 1
BF Bay fault  A 1
BRF Breaker Fault  A 1
CSP Check synchronizing in progress I 1
 ARL Circuit breaker auto reclose lock out  A 1
 AR Circuit breaker auto reclose success  A 1
CBF Circuit Breaker Failure Trip  A 1
DTT Direct Transfer Trip  A 1
DEF Directional earth fault  A 1
DISZ1 Distance protection zone 1  A 1
DISZ2 Distance protection zone 2  A 1
TSS
DISZ3 Distance protection zone 3  A 1
DISZ4 Distance protection zone 4  A 1
LCD Line current differential  A 1
OCGF Over Current Ground Fault  A 1
OCPT Oil cable pressure trip  A 1*)
OGSTX Overgenerating shedding transmit I 1

OLSTX Overload shedding transmit I 1


SOTF Switch on to fault  A 1

60

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 74/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TTR Teleprotection trip receive I 1


TTT Teleprotection trip transmit I 1
UFRT Under Frequency Relay Trip  A 1
VRT Voltage relay trip  A 1
 ARO  Auto Reclose On Off I 1

BI Bus isolator switch closed/opened I 1


CB Circuit breaker closed/opened I 1
TSD
ES Earth Switch Closed/Opened I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/Remote For BCU I 1
RCD CB Circuit breaker closed/opened 1
KETERANGAN:
*)
= Khusus untuk OHL Feeder  
**)
= Khusus untuk Cable Feeder  

61

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 75/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-18: Bay Penghantar Paralel Dengan Reaktor Pada Konfigurasi D o u b l e


Busbar

BAY PENGHANTAR TB-18

PARALEL
PADA DENGAN
KONFIGURASI REAKTOR
DOUBLE BUSBAR

BUSBAR - A

BUSBAR - B

L/R

P
Q
V
I

Gambar 29. B ay  penghantar paralel dengan reaktor pada konfigurasi d o u b l e b u s b a r  


 

Tabel 26. Teleinformasi data untuk b ay  penghantar serial dengan reaktor pada konfigurasi
double busbar   

Data No Kode Fungsi Tipe Jmh

 AMF  Amperes fault 8


I Arus 1
P Daya aktif 1
TM
Q Daya reaktif 1
F Frekuensi 1
V Tegangan 1
BF Bay fault  A 1
BRF Breaker fault  A 1
CSP Check synchronizing in progress I 1
 ARL Circuit breaker auto reclose lock out  A 1
 AR Circuit breaker auto reclose success  A 1
CBF Circuit breaker failure trip  A 1
DTT Direct transfer trip  A 1
TSS DEF Directional earth fault  A 1

62

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 76/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

DISZ1 Distance protection zone 1  A 1


DISZ2 Distance protection zone 2  A 1
DISZ3 Distance protection zone 3  A 1
DISZ4 Distance protection zone 4  A 1
LCD Line current differential  A 1

OCGF Over current ground fault  A 1


OGSTX Overgenerating shedding transmit I 1
OLSTX Overload shedding transmit I 1
RA Reaktor alarm  A 1
RT Reaktor trip  A 1
SOTF Switch on to fault  A 1
TTR Teleprotection trip receive I 1
TTT Teleprotection trip transmit I 1
UFRT Under frequency relay trip  A 1
VRT Voltage relay trip  A 1
CB Circuit breaker closed/opened I 1
 ARO  Auto Reclose On Off I 1
BI Bus isolator switch closed/opened I 2
TSD
LI Line isolator switch closed/opened I 2
ES Earth Switch Closed/Opened I 1
LRBCU Local/Remote For BCU I 1
RCD CB Circuit breaker closed/opened 1

TB-19: Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1½


Breaker
TB-19
BAY PENGHANTAR

PARALEL
PADA DENGAN 1½
KONFIGURASI 1 REAKTOR
BREAKER
BUSBAR - A

BUSBAR - B

P
Q
Q V
I
L/R

Gambar 30. B ay  penghantar paralel dengan 1 reaktor pada konfigurasi 1½ breaker 


 

63

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 77/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 27. Teleinformasi data untuk b ay  penghantar paralel dengan 1 reaktor pada
konfigurasi 1½ breaker

Data No Kode Fungsi Tipe Jmh


 AMF  Amperes fault 8
I Arus 1
P Daya aktif 1
TM
Q Daya reaktif 1
F Frekuensi 1
V Tegangan 1
BF Bay fault  A 1
BRF Breaker fault  A 1
CSP Check synchronizing in progress I 1
 ARL Circuit breaker auto reclose lock out  A 1
 AR Circuit breaker auto reclose success  A 1
CBF Circuit breaker failure trip  A 1

DTT Direct transfer trip  A


 A 1
DEF Directional earth fault 1
DISZ1 Distance protection zone 1  A 1
DISZ2 Distance protection zone 2  A 1
TSS DISZ3 Distance protection zone 3  A 1
DISZ4 Distance protection zone 4  A 1
LCD Line current differential  A 1
OCGF Over current ground fault  A 1
RA Reaktor alarm  A 1
RT Reaktor trip  A 1
SOTF Switch on to fault  A 1
TTR Teleprotection trip receive I 1
TTT Teleprotection trip transmit I 1
UFRT Under frequency relay trip  A 1
VRT Voltage relay trip  A 1
 ARO  Auto reclose On/Off I 1
TSD LI Line isolator switch closed/opened I 2
ES Earth switch closed/opened I 1

64

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 78/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

TB-20: Bay Kopel Pada Konfigurasi Double Busbar

TB-20
BAY KOPEL
PADA KONFIGURASI DOUBLE BUSBAR

L/R

BUSBAR - A

BUSBAR - B

 
Gambar 31. B a y kopel pada konfigurasi d o u b l e b u s b a r  
 

Tabel 28. Teleinformasi data untuk b ay  kopel pada konfigurasi d o u b l e b u s b a r   

Data No Kode Fungsi Tipe Jmh


TM I Arus 1
CSP Check synchronizing in progress I 1
BF Bay fault  A 1
TSS BRF Breaker fault  A 1
OCGF Over current ground fault  A 1
UFRT Under frequency relay trip  A 1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
TSD
LRBCU Local remote for BCU I 1
SIB Software Interlocking Bypassed I 1
RCD CB Circuit breaker closed/opened 1

65

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 79/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

LAMPIRAN 3. Daftar Teleinformasi (Distribusi)

3-1: Telesignal
Tabel 29. Daftar telesignal 
 distribusi

Indikasi Sumber Bagian Jumlah Event


No Kode Fungsi Implementasi TSS/TSD H/LN  D/B/G/P F/C A/I

Outgoing
1  ARO  Auto reclose on/off TSD  LN B C I
feeder

2  AVRAM  Avr auto/manual Trafo TSD  LN B C I

Kopel,
Outgoing
Feeder, Trafo,
Bus isolator switch Incoming 20
BI
3 closed/opened KV, Kapasitor, TSD  H D C I
Bus Section,
Gen Trafo,
Generator
Kopel,
Outgoing
Feeder, Trafo,
Circuit breaker Incoming 20
4 CB TSD  H D C I
closed/opened KV, Kapasitor,
Bus Section,
Gen Trafo,
Generator
Kopel,
Outgoing
Feeder, Trafo,
Circuit breaker Incoming 20
5 RACK TSD  H B C I
rackin/rackout KV, Kapasitor,
Bus Section,
Gen Trafo,
Generator
Dummy circuit breaker
6 DCB Gardu induk TSD  H G C I
closed/opened
Kopel,
Outgoing
Feeder, Trafo,
Earth switch Incoming 20
7 ES TSD  H D C I
closed/opened KV, Kapasitor,
Bus Section,
Gen Trafo,
Generator
8 GUC Generator unit run/stop Generator TSD  H P C I

Load break switch


9 LBS Gardu induk TSD  H G C I
closed/opened

Kopel,
Outgoing
Feeder, Trafo,
Incoming 20
10 LRBCU Local/remote for bcu TSD  LN B C I
KV, Kapasitor,
Bus Section,
Gen Trafo,
Generator
11 LRHMI Local/remote for local hmi Gardu induk TSD  LN G C I

66

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 80/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Indikasi Sumber Bagian Jumlah Event


No Kode Fungsi Implementasi
TSS/TSD H/LN  D/B/G/P F/C A/I

12 PSO Power station operated Generator TSD  H P C I


Busbar, Kopel,
Outgoing
Feeder, Trafo,
Incoming 20  
13 BF Bay fault TSS  H B C A
KV, Kapasitor,
Bus Section,
Gen Trafo,
Generator
Kopel,
Outgoing
Feeder, Trafo,
Incoming 20  
14 BRF Breaker fault TSS  H B C A
KV, Kapasitor,
Bus Section,
Gen Trafo,
Generator
15 BUAL Building alarm Gardu induk TSS  LN D C A
Circuit breaker auto Outgoing
16 ARL TSS  LN B C A
reclose lock out feeder
Circuit breaker auto Outgoing
17 AR TSS  LN B C A
reclose success feeder
18 COM Communication faulty Gardu Induk TSS  H D C A
Outgoing
19 DEF Directional earth fault TSS  LN B F A
feeder
Kopel,
Outgoing
Feeder, Trafo,
Incoming 20
20 GFT Ground fault trip TSS  LN B C A
KV, Kapasitor,
Bus Section,
Gen Trafo,
Generator
21 IEDF IED bay level faulty Gardu Induk TSS  LN G C A
Kopel,
Outgoing
Feeder, Trafo,
Instantaneous ground Incoming 20
22 IGFT TSS  LN B C A
fault trip KV, Kapasitor,
Bus Section,
Gen Trafo,
Generator
Kopel,
Outgoing
Feeder, Trafo,
23 IOCT Instantaneous over Incoming 20 TSS  LN B C A
current trip KV, Kapasitor,
Bus Section,
Gen Trafo,
Generator
Kopel,
Outgoing
Feeder, Trafo,
Incoming 20
24 OCT Over current trip TSS  LN B C A 
KV, Kapasitor,
Bus Section,
Gen Trafo,
Generator
25 SLF Station level faulty Gardu Induk TSS  H B C A 
26 SF Supply failure Gardu Induk TSS  LN B C A
27 TCH Tap changer high limit Trafo TSS  H B C I

67

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 81/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Indikasi Sumber Bagian Jumlah Event


No Kode Fungsi Implementasi TSS/TSD H/LN  D/B/G/P F/C A/I

28 TCIP Tap changer in progress Trafo TSS  H B C I


29 TCL Tap changer low limit Trafo TSS  H B C I
30 UFRT Under frequency relay trip Outgoing TSS  LN B C A
feeder
Outgoing
31 UVRT Under voltage relay trip TSS  LN B C A
feeder
32 VACF VAC failure Gardu induk TSS  H G C A
33 VDCF VDC failure Gardu induk TSS  H G C A
34 VS Voltage status Busbar TSS  H B C I

KETERANGAN:
 A =  Alarm (audible alarm, flashing display, etc )
I = Indikasi (normal condition)
TSS = Telesignal single 
TSD = Telesignal double 
H = Hardwiring  
LN = Logical Network
D =  per Device (peralatan)
B =  per Bay  
G = per GI
P = per Pembangkit
F = per Fasa
C = Common 

3-2: Telemeasurement  
Tabel 30. Daftar telemeasurement

Sumber Bagian Jumlah


No Kode Fungsi Implementasi H/LN  D/B/G/P F/C

Kopel, Bus section,


1 AMF  Amperes fault ( per phase ) Outgoing Feeder, LN B F
Incoming 20 kV
Gardu induk, Gen
2 F Frekuensi H G C
Trafo
Outgoing Feeder,
3 I Arus Incoming  20 kV, Gen H B F
Trafo
Outgoing Feeder ,
4 P Daya aktif Incoming  20 kV, Gen LN B C

Trafo
Outgoing Feeder ,
5 Q Daya reaktif Incoming  20 kV, Gen LN B C
Trafo
Busbar,
6 V Tegangan H B F
Gen Trafo

KETERANGAN:
Logical Node pada TM apabila nilai didapat melalui perhitungan beberapa parameter.
Hardwiring  pada TM apabila nilai didapat melalui pengukuran dari sinyal masukan.
* Per fasa untuk single phase.

68

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 82/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

3-3: T ap C h a n g e r P o s i t i o n

Tabel 31. Daftar t a p c h a n g e r


Sumber Bagian Jumlah
No Kode Fungsi Implementasi H/LN  D/B/G/P F/C

1 TPI Tap position indication Trafo H B C/F*

Keterangan :
* Per fasa untuk single phase.

3-4: R e mo t e C o n t r o l D i g i t a l

Tabel 32. Daftar r e m o t e c o n t r o l d i g i t a l

No Kode Fungsi Implementasi Sumber


H/LN  Bagian
D/B/G/P Jumlah
F/C

1 ARO  Auto reclose on/off Feeder LN B C

 Automatic Voltage Regulator


2 AVRAM Trafo LN D C
auto/manual
Kopel,
Outgoing
Feeder, 
Reaktor,
3 CB Circuit breaker closed/opened H D C
Kapasitor, Bus
Section, 
Incoming  20
kV

4 CAM Capacitor auto manual Kapasitor LN B C

Dummy circuit breaker


5 DCB Gardu induk H G C
closed/opened
Kopel,
Outgoing
Feeder, 
Reaktor, 
6 RPB Reset per bay H B C
Kapasitor, Bus
Section, 
Incoming 20
kV

7 TC Tap changer raise/lower Trafo H B C

69

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 83/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

LAMPIRAN 4. Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi

DA-01: Konfigurasi Umum Pada Double Busbar


DA- 01

KONFIGURASI UMUM PADA DOUBLE BUSBAR


GENERATOR
INCOMING 20 KV

P
Q
I
V
P
Q
PF

P KOPEL
Q
L/R I

L/R L/R

V(R)
V(S)
BUSBAR
- A
V(T)

BUSBAR
- B
V(R)
V(S)
V(T)

L/R L/ R
I ( R)

II (T)
(S)
P

FEEDER CAPASITOR

 
Gambar 32. Konfigurasi umum pada d o u b l e b u s b a r  
 

Tabel 33. Teleinformasi data untuk konfigurasi umum pada d o u b l e b u s b a r

Group Bay Data No Kode Fungsi Tipe Jmlh

TM F Frekuensi 1
SLF Station level faulty  A  1 
IEDF Ied bay level faulty  A  1 
GARDU COM Communication faulty  A  1 
INDUK TSS BUAL Building alarm  A  1 
VACF VAC failure  A  1 
VDCF VDC failure  A  1 
SF Supply failure  A  1 

70

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 84/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Group Bay Data No Kode Fungsi Tipe Jmlh

TSD LBS Load break switch closed/opened I 1

RCD DCB Dummy CB closed/opened


TM V Tegangan 2
BUSBAR VS Voltage status I 2 
TSS
BF Bay fault  A  1 
 AMF  Amperes fault 4
I Arus 1
TM P Daya aktif 1
Q Daya reaktif 1
PF Power factor 1
DEF Directional earth fault  A  1
 AR Circuit breaker auto reclose success  A  1
 ARL Circuit breaker auto reclose lock out  A 1
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
TSS OCT Over current trip  A  1
BAY IOCT Instantaneous over current trip  A  1
OUTGOING UFRT Under frequency relay trip  A  1
FEEDER UVRT Under voltage relay trip  A  1
BRF Breaker fault  A  1
BF Bay fault  A  1
 ARO  Auto reclose on/off I 1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
TSD
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for BCU I 1
 ARO  Auto reclose On/Off 1
RCD CB Circuit breaker closed/opened 1
RPB Reset per bay 1
 AMF  Amperes fault 4
I Arus 3
P Daya aktif 1
TM
Q Daya reaktif 1
PF Power factor 1
GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1


OCT Over current trip  A  1
IOCT Instantaneous over current trip  A  1
TSS
BRF Breaker fault  A  1
BF Bay fault  A  1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
BAY TSD RACK Circuit breaker rackin/rackout I 1
INCOMING 20 ES Earth switch closed/opened I 1
KV
LRBCU Local/remote for bcu I 1
CB Circuit breaker closed/opened 1
RCD

TM RPB Reset per bay 1


4
 AMF  Amperes fault

71

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 85/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Group Bay Data No Kode Fungsi Tipe Jmlh

GFT Ground fault trip  A 1


IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
TSS IOCT Instantaneous over current trip  A  1
KOPEL BRF Breaker fault  A  1
BF Bay fault  A  1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1
TSD
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
CB Circuit breaker closed/opened 1
RCD RPB Reset per bay 1
TM Q Daya reaktif 1
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
TSS
IOCT Instantaneous over current trip  A  1
BRF Breaker fault  A  1
BAY BF Bay fault  A  1
KAPASITOR BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
TSD RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1

RCD CB Circuit breaker closed/opened 1


RPB Reset per bay 1
I Arus 1
P Daya aktif 1
TM Q Daya reaktif 1
F Frekuensi 1
V Tegangan 1
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
TSS
IOCT Instantaneous over current trip  A  1
 
BRF Breaker fault  A 1
BF Bay fault  A  1
BAY BI Bus isolator switch closed/opened I 2
GENERATOR
CB Circuit breaker closed/opened I
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
GUC Generator unit run/stop I 1
TSD LRBCU Local/remote for BCU I 1
PSO Power station operated I 1
CB Circuit breaker closed/opened 1
RCD
RPB Reset per bay 1

72

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 86/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

DA-02: Konfigurasi Umum Pada Single Busbar

DA- 02

KONFIGURASI UMUM PADA SINGLE BUSBAR

GENERATOR
INCOMING 20 KV

P
Q
I
V
P
Q
PF

P
Q
L/R I

L/R
V(R)
V(S)
BUSBAR - A V(T)

L/R L/R
I (R)
I ( S)
I (T)
P

FEEDER CAPASITOR

 
Gambar 33. Konfigurasi umum pada s i n g l e b u s b a r  

73

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 87/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 34. Teleinformasi data untuk konfigurasi umum pada s i n g l e b u s b a r

Group Bay Data No Kode Fungsi Tipe Jmlh

TM F Frekuensi 1

SLF Station level faulty  A  1 


IEDF Ied bay level faulty  A  1 
COM Communication faulty  A  1 
TSS BUAL Building alarm  A  1 
GARDU
VACF VAC failure  A  1 
INDUK
VDCF VDC failure  A  1 
SF Supply failure  A  1 
TSD LBS Load break switch closed/opened I 1

RCD DCB Dummy CB closed/opened


TM V Tegangan 1
BUSBAR VS Voltage status I 1 
TSS BF Bay fault  A  1 
 AMF  Amperes fault 4
I Arus 1
TM P Daya aktif 1
Q Daya reaktif 1
PF Power factor 1
DEF Directional earth fault  A  1
 AR Circuit breaker auto reclose success  A  1
 ARL Circuit breaker auto reclose lock out  A 1
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
TSS OCT Over current trip  A  1
BAY IOCT Instantaneous over current trip  A  1
OUTGOING UFRT Under frequency relay trip  A  1
FEEDER UVRT Under voltage relay trip  A  1
BRF Breaker fault  A  1
BF Bay fault  A  1
 ARO  Auto reclose on/off I 1
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
TSD
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for BCU I 1
 ARO  Auto reclose On/Off 1
RCD CB Circuit breaker closed/opened 1
RPB Reset per bay 1
 AMF  Amperes fault 4
I Arus 1
P Daya aktif 1
TM
Q Daya reaktif 1
PF Power factor 1
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1


TSS IOCT Instantaneous over current trip  A  1

74

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 88/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Group Bay Data No Kode Fungsi Tipe Jmlh

BRF Breaker fault  A  1


BF Bay fault  A  1
BAY BI Bus isolator switch closed/opened I 1
INCOMING 20
I 1
KV TSD CB
RACK Circuit
Circuit breaker
breaker closed/opened
rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
CB Circuit breaker closed/opened 1
RCD
RPB Reset per bay 1
TM  AMF  Amperes fault 4
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
TSS IOCT Instantaneous over current trip  A  1
BRF Breaker fault  A  1
KOPEL BF Bay fault  A  1
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1
TSD
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
CB Circuit breaker closed/opened 1
RCD RPB Reset per bay 1
TM Q Daya reaktif 1
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
TSS
IOCT Instantaneous over current trip  A  1
BRF Breaker fault  A  1
BAY BF Bay fault  A  1
KAPASITOR BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
TSD RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
CB Circuit breaker closed/opened 1
RCD
RPB Reset per bay 1
I Arus 1
P Daya aktif 1
TM Q Daya reaktif 1
F Frekuensi 1
V Tegangan 1
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
TSS
IOCT Instantaneous over current trip  A  1
BRF Breaker fault  A  1
BAY
GENERATOR BF Bay fault  A  1
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I

75

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 89/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Group Bay Data No Kode Fungsi Tipe Jmlh

RACK Circuit breaker rackin/rackout I 1


ES Earth switch closed/opened I 1
GUC Generator unit run/stop I 1
TSD LRBCU Local/remote for BCU I 1
PSO Power station operated I 1
CB Circuit breaker closed/opened 1
RCD
RPB Reset per bay 1

DB-01: Trafo 150/20 kV dan 70/20 kV Tipe 1

DB - 01
TRAFO 150/20 KV DAN 70/20 KV
TYPE 1

RCC

I
DCC
P L/R
Q
PF

Gambar 34. Trafo 150/20 kV dan 70/20 kV tipe 1  

Tabel 35. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 1

  Data
Group Bay  No Kode Fungsi Tipe Jmh

TM V Tegangan 2
Busbar VS Voltage status I 2 
TSS
BF Bay fault  A  1 
 AMF  Amperes fault 4
BAY I Arus 1
INCOMING TM P Daya aktif 1
20 KV Q Daya reaktif 1
PF Power factor 1

76

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 90/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

  Data
Group Bay  No Kode Fungsi Tipe Jmh

GFT Ground fault trip  A 1


IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
TSS
 
IOCT Instantaneous over current trip  A 1
BRF Breaker fault  A  1
BF Bay fault  A  1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
TSD RACK Circuit breaker rackin/rackout I 0
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
CB Circuit breaker closed/opened 1
RCD
RPB Reset per bay 1

DB-02: Trafo 150/20 kV dan 70/20 kV Tipe 2

DB -02
TRAFO 150/20 KV DAN 70/20 KV
TYPE 2

RCC
DCC
I
P
Q
PF

L/R

Gambar 35. Trafo 150/20 kV dan 70/20 kV tipe 2

Tabel 36. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 2

  Data
Group Bay  No Kode Fungsi Tipe Jmh

TM V Tegangan 2
Busbar VS Voltage status I 2 
TSS
BF Bay fault  A  1 
BAY  AMF  Amperes fault 4
TM
INCOMING  I Arus 1

77

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 91/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

  Data
Group Bay  No Kode Fungsi Tipe Jmh

20 KV P Daya aktif 1
Q Daya reaktif 1
PF Power factor 1
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
TSS
IOCT Instantaneous over current trip  A  1
BRF Breaker fault  A  1
BF Bay fault  A  1
RACK Circuit breaker rackin/rackout I 1
TSD ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCD RPB Reset per bay 1

DB-03: Trafo 150/20 kV dan 70/20 kV Tipe 3

DB -03
TRAFO 150/20 KV DAN 70/20 KV
TYPE 3

RCC
DCC

I
P L/R
Q
PF

Gambar 36. Trafo 150/20 kV dan 70/20 kV tipe 3

Tabel 37. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 3

  Data
Group Bay  No Kode Fungsi Tipe Jmh

TM V Tegangan 1
Busbar TSS VS Voltage status I 1 
BF Bay fault  A  1 

78

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 92/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

  Data
Group Bay  No Kode Fungsi Tipe Jmh

 AMF Amperes fault 4


I Arus 1
TM P Daya aktif 1

Q Daya reaktif 1
PF Power factor 1
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
BAY TSS
IOCT Instantaneous over current trip  A  1
INCOMING 
BRF Breaker fault  A  1
20 KV
BF Bay fault  A  1
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
TSD RACK Circuit breaker rackin/rackout I 0
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
CB Circuit breaker closed/opened 1
RCD
RPB Reset per bay 1

DB-04: Generator Pada Konfigurasi Double Busbar

DB-04

GENERATOR PADA KONFIGURASI DOUBLE BUSBAR

P
Q
V

P
Q
I

L/R

BUSBAR - A

BUSBAR - B

Gambar 37. Generator pada konfigurasi d o u b l e b u s b a r

79

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 93/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 38. Teleinformasi data untuk generator pada konfigurasi double busbar

 
Group Bay  Data No Kode Fungsi Tipe Jmh

TM V Tegangan 1
BUSBAR TSS VS Voltage status I 1 
BF Bay fault  A  1 
I Arus 1
P Daya aktif 2
TM Q Daya reaktif 2
F Frekuensi 1
V Tegangan 1
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
TSS
IOCT Instantaneous over current trip  A  1

BAY BRF Breaker fault  A  1


GENERATOR   BF Bay fault  A  1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 0
TSD ES Earth switch closed/opened I 1
GUC Generator unit run/stop I 1
LRBCU Local/remote for BCU I 1
PSO Power station operated I 1
CB Circuit breaker closed/opened 1
RCD RPB Reset per bay 1

DB-05: Generator Pada Konfigurasi Single Busbar

DB-05

GENERATOR PADA KONFIGURASI SINGLE BUSBAR

P
Q
V

P
Q
I

L/R

BUSBAR

 
Gambar 38. Generator pada konfigurasi s i n g l e b u s b a r  
 

80

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 94/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 39. Teleinformasi data untuk generator pada konfigurasi single busbar

 
Group Bay  Data No Kode Fungsi Tipe Jmh

TM V Tegangan 1
BUSBAR VS Voltage status I 1 
TSS BF Bay fault  A  1 
I Arus 1
P Daya aktif 2
TM Q Daya reaktif 2
F Frekuensi 1
V Tegangan 1
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
TSS
IOCT Instantaneous over current trip  A  1
BAY BRF Breaker fault  A  1
GENERATOR   BF Bay fault  A  1
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 0
TSD ES Earth switch closed/opened I 1
GUC Generator unit run/stop I 1
LRBCU Local/remote for BCU I 1
PSO Power station operated I 1
CB Circuit breaker closed/opened 1
RCD RPB Reset per bay 1

DB-06: Feeder 20 kV Tipe 1


DB- 06
FEEDER 20 KV
TYPE 1

L/R

I ( R)
I ( S)
I ( T)
P

 
Gambar 39. Feeder 
 20 kV tipe 1 

81

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 95/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tabel 40. Teleinformasi data untuk feeder 20 kv tipe 1

 
Group Bay  Data No Kode Fungsi Tipe Jmh

TM V Tegangan 2
BUSBAR TSS VS Voltage status I 2 
BF Bay fault  A  1 
 AMF  Amperes fault 4
I Arus 1
TM P Daya aktif 1
Q Daya reaktif 1
PF Power factor 1
DEF Directional earth fault  A  1
 AR Circuit breaker auto reclose success  A  1
 ARL Circuit breaker auto reclose lock out  A 1
GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1


TSS OCT Over current trip  A  1
BAY
IOCT Instantaneous over current trip  A  1
OUTGOING
UFRT Under frequency relay trip  A  1
FEEDER  
UVRT Under voltage relay trip  A  1
BRF Breaker fault  A  1
BF Bay fault  A  1
 ARO  Auto reclose on/off I 1
CB Circuit breaker closed/opened I 1
TSD RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
I 1
LRBCU
 ARO Local/remote
 Auto for BCU
reclose On/Off 1
CB Circuit breaker closed/opened I 1
RCD
RPB Reset per bay 1

82

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 96/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

DB-07: Feeder 20 kV Tipe 2

DB -07
FEEDER 20 KV
TYPE 2

L/R

I ( R)
I ( S)
I ( T)
P

Gambar 40. Feeder 


 20 kV tipe 1 

Tabel 41. Teleinformasi data untuk feeder  20 kv tipe 1

  Data
Group Bay  No Kode Fungsi Tipe Jmh

TM V Tegangan 1
BUSBAR VS Voltage status I 1 
TSS
BF Bay fault  A  1 
 AMF  Amperes fault 4
I Arus 1
TM P Daya aktif 1
Q Daya reaktif 1
PF Power factor 1
DEF Directional earth fault  A  1
BAY  AR Circuit breaker auto reclose success  A  1
OUTGOING  ARL Circuit breaker auto reclose lock out  A 1
FEEDER   GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
TSS
OCT Over current trip  A  1
IOCT Instantaneous over current trip  A  1
UFRT Under frequency relay trip  A  1
UVRT Under voltage relay trip  A  1
BRF Breaker fault  A  1

83

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 97/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

  Data
Group Bay  No Kode Fungsi Tipe Jmh

BF Bay fault  A  1


 ARO  Auto reclose on/off I 1
CB Circuit breaker closed/opened I 1
TSD RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for BCU I 1
 ARO  Auto reclose On/Off 1
CB Circuit breaker closed/opened I 1
RCD
RPB Reset per bay 1

DB-09: Bus Section 20 kV Tipe 1

DB- 09

BUS SECTION 20 KV
TYPE 1

L/R

 
Gambar 41. B u s s e c t i o n  
 20 kV tipe 1

Tabel 42. Teleinformasi data untuk bus section 20 kv tipe 1

 
Group Bay  Data No Kode Fungsi Tipe Jmh

TM V Tegangan 2
BUSBAR VS Voltage status I 2 
TSS
BF Bay fault A  1 
TM  AMF Amperes fault 4
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
TSS IOCT Instantaneous over current trip  A  1

84

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 98/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

 
Group Bay  Data No Kode Fungsi Tipe Jmh

BAY BRF Breaker fault  A  1


BUS BF Bay fault  A  1
SECTION BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1


RACK Circuit breaker rackin/rackout I 1
TSD ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
CB Circuit breaker closed/opened 1
RCD
RPB Reset per bay 1

DB-10: Bus section 20 kV Tipe 2

DB -10

BUS SECTION
TYPE 2 20 KV

L/R

 
Gambar 42. B u s s e c t i o n  
 20 kV tipe 2 

Tabel 43.Teleinformasi data untuk bus section 20 kv tipe 2

 
Group Bay  Data No Kode Fungsi Tipe Jmh

TM V Tegangan 2
BUSBAR VS Voltage status I 2 
TSS
BF Bay fault  A  1 
TM  AMF  Amperes fault 4
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
TSS IOCT Instantaneous over current trip  A  1

85

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 99/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

 
Group Bay  Data No Kode Fungsi Tipe Jmh

BAY BRF Breaker fault  A  1


BUS BF Bay fault  A  1
SECTION CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
TSD
LRBCU Local/remote for bcu I 1
CB Circuit breaker closed/opened 1
RCD
RPB Reset per bay 1

DB-11: Kopel

DB -11
KOPEL

L/R

 
Gambar 43. Kopel

Tabel 44. Teleinformasi data untuk kopel

 
Group Bay  Data No Kode Fungsi Tipe Jmh

TM V Tegangan 2
BUSBAR VS Voltage status I 2 
TSS
BF Bay fault  A  1 
TM  AMF  Amperes fault 4
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
 
BAY TSS OCT Over current trip  A 1
IOCT Instantaneous over current trip  A  1

86

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 100/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

 
Group Bay  Data No Kode Fungsi Tipe Jmh

KOPEL BRF Breaker fault  A  1


BF Bay fault  A  1
CB Circuit breaker closed/opened I 1

TSD RACK Circuit breaker rackin/rackout I 1


ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
CB Circuit breaker closed/opened 1
RCD
RPB Reset per bay 1

DB-12: C a p ac i t o r B a y

DB-12
CAPACITOR BAY

Q L/R

 
Gambar 44. C a p ac i t o r b a y

Tabel 45. Teleinformasi data untuk capasitor bay

 
Group Bay  Data No Kode Fungsi Tipe Jmh
TM V Tegangan 2
BUSBAR VS Voltage status I 2 
TSS
BF Bay fault  A  1 
TM Q Daya reaktif 1
GFT Ground fault trip  A 1
IGFT Instantaneous ground fault trip  A 1
OCT Over current trip  A  1
BAY
TSS IOCT Instantaneous over current trip  A  1
KAPASITOR
BRF Breaker fault  A  1
BF Bay fault  A  1
BI Bus isolator switch closed/opened I 2
TSD CB Circuit breaker closed/opened I 1

87

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 101/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

 
Group Bay  Data No Kode Fungsi Tipe Jmh

RACK Circuit breaker rackin/rackout I 1


ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
CB Circuit breaker closed/opened 1
RCD
RPB Reset per bay 1

88

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 102/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

LAMPIRAN 5. Struktur Informasi

STRUKTUR INFORMASI 

Struktur informasi terdiri dari 112 karakter yang dapat dikelompokkan menjadi sembilan
bagian, yaitu:

 A B C D E F G H I

Bagian A: Nomor ID, terdiri dari 6 digit (sebagai primary key )


Bagian B: Time stamp, sebanyak karakter 23 karakter
Bagian C: Nama GI/GH/GT/KP, sebanyak 20 karakter
Bagian D: Level tegangan, sebanyak 5 karakter
Bagian E: Nama bay / feeder, sebanyak 20 karakter
Bagian F: Kode nama peralatan atau nama alarm atau nama elemen, sebanyak 5
karakter
Bagian G: Status peralatan atau status alarm, sebanyak 15 karakter
Bagian H: Nama user yang melakukan aksi (seperti remote control, dan sebagainya),
sebanyak 10 karakter
Bagian I: Prioritas alarm, sebanyak 8 karakter

Struktur di atas ditentukan dalam field yang berbeda.


Contohnya dapat dilihat pada tabel 62.

Tabel 46. Struktur informasi

A B C D E F G H I
RCC Cawang
110007 02/03/2007 11:10:05.320 Cawang 150 Gandul-1 BI1 Close Class-3
110009 05/03/2007 07:00:55.115 Gandul 150 Cawang-1 ARO Appear Class-2
RCC Waru
140104 11/04/2007 17:44:21.220 Rungkut 150 Waru-1 LT Disappear Class-1
140085 12/04/2007 20:11:51.312 Waru 150 Bangil-1 CB Invalid Class-4
DCC Pasuruan
430011 25/04/2007 00:30:35.000 Gondang Wetan 20 Bromo CB Open Adi Class-1
430012 19/11/2007 10:00:05.520 Gondang Wetan 20 Semeru CBTR Appear Class-1

1. A. Nomor ID

Nomor ID (bagian A) terdiri dari dua bagian. Bagian A1 terdiri dari 3 digit yang
menyatakan kode area. Bagian A2 terdiri dari 3 digit merupakan nomor RTU
bersangkutan. Nomor ID dinyatakan dengan susunan sebagai berikut

 A1 A2

Bagian A1: Kode area


Bagian A2: Nomor RTU

89

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 103/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Kode area

Kode area yang terdiri dari 3 karakter adalah sebagai berikut:


NCC : 900

IRCC : x00
IRCC Jawa-Bali : 100
IRCC Sumatera : 200
IRCC Kalimantan : 300
IRCC Sulawesi : 400
IRCC di Indonesia Timur : 500

RCC di Jawa-Bali : 1xx


RCC Cawang : 110
RCC Cigereleng : 120
RCC Ungaran : 130
RCC
RCC Waru
di Sumatera :: 140
2xx
RCC Medan : 210
RCC Padang : 220
RCC Palembang : 230
RCC di Kalimantan : 3xx
RCC Banjarbaru : 310
RCC Balikpapan : 320
RCC di Sulawesi : 4xx
RCC Makassar : 410
RCC Manado : 420
RCC di Indonesia Timur : 5xx

IDCC : x00
IDCC Jawa-Bali : 100, 200, 300, 400
IDCC Sumatera : 500, 600
IDCC Kalimantan : 700
IDCC Sulawesi : 800
IDCC di Indonesia Timur : 900

DCC di Jakarta : 0xx – 1xx


DCC daerah Jawa bagian Barat : 2xx
DCC daerah Jawa bagian Tengah : 3xx
DCC daerah Jawa bagian Timur dan Bali : 4xx
DCC daerah Sumatera : 5xx – 6xx
DCC daerah Kalimantan : 7xx
DCC daerah Sulawesi : 8xx
DCC daerah Indonesia Timur : 9xx
Nomor RTU

Nomor RTU terdiri dari 3 digit (001  – 999)

90

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 104/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

B. T i me s t amp

Struktur informasi yang menggambarkan time stamp atau waktu suatu kejadian terdiri dari
23 karakter. Struktur informasinya berturut-turut terdiri dari tanggal (2 karakter), bulan (2
karakter), tahun (4 karakter), jam (2 karakter), menit (2 karakter), dan detik (6 karakter
atau sampai dengan orde milidetik). Contohnya:
25/04/2007 00:30:35.000
19/11/2007 10:00:05.520

C. Nama GI/GH/GT

Nama GI/GH/GT dituliskan dalam bentuk nama lengkap (maksimal 20 karakter).


Contohnya adalah sebagai berikut:

Cawang
Gandul
Gondang Wetan
Rungkut
Waru
Cawang : menyatakan GI Cawang (dikontrol oleh RCC Cawang).
Gandul : menyatakan GI Gandul (dikontrol oleh RCC Cawang).
Waru : menyatakan GI Waru (dikontrol oleh RCC Waru).
Rungkut : menyatakan GI Rungkut (dikontrol oleh RCC Waru).
Gondang Wetan : menyatakan GI/GH/GT Gondang Wetan (dikontrol oleh DCC
Pasuruan).

D. Level Tegangan

Level tegangan terdiri dari 5 karakter. Contohnya dapat dilihat pada tabel 47.

Tabel 47. Level tegangan 

Tegangan Level Tegangan


500 kV 500
275 kV 275
150 kV 150
66 kV 66
30 kV 30
20 kV 20
11 kV 11
6.6 kV 6
3.3 KV 3

91

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 105/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

E. Nama Bay / Feeder 


 

Nama Bay/Feeder   terdiri dari 20 karakter. Contohnya dapat dilihat pada tabel 48.

Tabel 48. Nama bay atau feeder

Nama Bay / Feeder 


  Kode

Pusat Listrik
Pusat Listrik Tenaga Air PLTA
Pusat Listrik Tenaga Diesel PLTD
Pusat Listrik Tenaga Gas PLTG
Pusat Listrik Tenaga Panas Bumi PLTP
Pusat Listrik Tenaga Nuklir PLTN
Pusat Listrik Tenaga Uap PLTU
Pusat Listrik Gas/Uap (Combine Cycle) PLTGU
Pusat Listrik Tenaga Mikrohidro PLTMH
Pusat Listrik Tenaga Angin/Bayu PLTB
Pusat Listrik Tenaga Surya PLTS

Peralatan di Gardu Induk


LineBay (FeederBay)  Format penulisan:
  IRCC/RCC:

Nama GI lawan + ” -” + nomor


penghantar. Contohnya:
o  Gandul-1
o
  Cawang-1
  DCC:

Nama Feeder. Contohnya:


o  Bromo
o  Semeru
Bay ke Unit Generator UNIT
Busbar BUSBAR
Kopel (Bus Tie) KOPEL
Bus Section BUSSECT
Trafo TRAFOx (X adalah Kode Tegangan
dari primer dan sekunder trafo)
Diameter DAMTR
Shunt Reactor SHTXL
Shunt Capacitor SHTXC
Cadangan SPARE

Nama Bay
Bay 500 kV diameter 1 busbar A 7A1
Bay 500 kV diameter 3 antara busbar A 7AB3
dan B
Bay 500 kV diameter 5 busbar B 7B5

92

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 106/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Kode tegangan dari primer dan sekunder trafo dapat dilihat pada tabel 49.

Tabel 49. Kode tegangan dari primer dan sekunder trafo

Tegangan (KV) Range IEC


Tegangan Rendah (TR) < 1 kV N
Tegangan Menengah (TM) 1 sampai<6 kV M
Tegangan Menengah (TM) 6 sampai <10 kV L
Tegangan Menengah (TM) 10 sampai <20 kV K
Tegangan Menengah (TM) 20 sampai <30 kV J
Tegangan Menengah (TM) 30 sampai <45 kV H
Tegangan Tinggi (TT) 45 sampai <60 kV G
Tegangan Tinggi (TT) 60 sampai <110 kV F
Tegangan Tinggi (TT) 110 sampai <220 kV E
Tegangan Ekstra Tinggi (TET) 220 sampai <380 kV D
Tegangan Ekstra Tinggi (TET) 380 sampai ≤ 420 kV C
Tegangan Ekstra Tinggi (TET) > 420 kV B

F. Kode Nama Peralatan atau Nama A l a r m  atau Nama Elemen

Kode nama peralatan atau nama alarm atau nama elemen terdiri dari maksimal 5
karakter. Contohnya dapat dilihat pada tabel 50.

 /elemen 
Tabel 50. Kode nama peralatan/alarm 

Nama Kode
Circuit Breaker CB
Bus Isolator #1 BI1
Bus Isolator #2 BI2
Line Isolator LI
Ground Fault GF
Over Current OC
Line Trip LT
Breaker Fault BRF
Power Supply Faulty PSF

Daya
Daya MW
MVAr P
Q
 Arus I
Load Break Switch LBS
Recloser REC
Kode nama peralatan dapat juga berupa kode teleinformasi (telesignal, telemeasurement  
atau r emote kontrol seperti ditunjukan pada Lampiran A-D).

93

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 107/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

G. Status Peralatan atau Status A l a r m

Status peralatan atau status alarm terdiri dari 15 karakter, menunjukkan status dari
peralatan atau alarm pada bagian E.
Contohnya adalah sebagai berikut:
- Close;
- Open;
- Invalid;
- Appear;
- Disappear;
- On;
- Off.

H. Nama u s e r yang melakukan aksi

Nama user terdiriaksi


saat melakukan dari tertentu
maksimal 10 karakter,
seperti Remotemenunjukkan namaCheck 
Control , Overall user ,yang
startlogin
dan pada
stop
perangkat keras, out of service RTU dan Inter Center Link , dan sebagainya.
Contohnya adalah sebagai berikut:
Tri
Lukman
Jufri
Joko
Parlin
Riko

I. Prioritas A l a r m

Prioritas alarm terdiri dari 8 karakter, menunjukkan kelas alarm yang ditampilkan. Class 1
merupakan kelas alarm yang menempati prioritas paling tinggi.

Contohnya sebagai berikut:


Class-1
Class-2
Class-3
Class-4

Struktur Informasi Khusus

Penamaan Pemutus Tenaga Pada Gardu Induk 1 ½ Breaker.

Struktur informasi khusus untuk pemutus tenaga pada gardu induk 1 ½ breaker dipakai
untuk tujuan komunikasi verbal diantara operator. Kode tersebut hanya ditampilkan di
VDU (Video Display Unit ), dan dipergunakan di dalam database. Struktur informasi
dinyatakan dengan susunan sebagai berikut:

X Y Z
Bagian X: kode referensi tegangan
Bagian Y: kode nama CB

94

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 108/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Bagian Z: nomor diameter


Contoh:
 A untuk breaker yang terhubung langsung ke busbar A
B untuk breaker yang terhubung langsung ke busbar B
 AB untuk breaker yang terhubung ke breaker A dan breaker  B
Contohnya dapat dilihat pada Gambar 4545.
Untuk tegangan 500 kV diameter no. 1 Untuk tegangan 150 kV diameter no.4

Gambar 45. Struktur informasi khusus ( b a y diameter)

95

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 109/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Contoh :

GITET 500 kV
SAGULING

UNIT 1 UNIT 2 UNIT 3 UNIT 4

~ ~ ~ ~

BANDUNG SELATAN 2

BUSBAR A

7A1 7A2 7A3

7AB1 7AB2 7AB3 7AB4 7AB5

7B1 7B2 7B3 7B4 7B5

BUSBAR B

CIBINONG 1 CIBINONG 2 CIRATA 1 CIRATA 2 BANDUNG


SELATAN 1
 
Gambar 46. Struktur informasi khusus (gardu induk 1½ breaker 
)

96

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 110/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

 
SPLN S5.003-1: 2014

LAMPIRAN 6. Simbol dan Warna

Simbol-simbol gambar yang digunakan mengacu pada gambar 47.

SIMBOL GAMBAR

Generator 

Trafo Daya Dua Belitan

Circuit Breaker 

Circuit Breaker Rack


Trafo Daya Tiga Belitan

PBO
Pemutus Balik Otomatis
Cut out fuse
 
Load Break Switch

Isolating Switch Battery


(Disconnecting Switch)

I  Arus
Earthing Switch

V Tegangan
Surge /Lightning Arrester 

F Frekuensi

Current Transformer 
(3 phases ) P Daya aktif 

Voltage Transformer  Q Daya reaktif 

TPI Tap Position Indication


Reaktor 
RCD Remote Control Digital

Kapasitor  RCA Remote Control Analog

TSS Telesignal Single


Capacitor Voltage
Transformer 
TSS Telesignal Double

Gardu Distribusi
L/R Local/ Remote

Rectifier  LFC(Po, Pr, N) Load Frequency Control

AGC  Automatic Gain Control

Inverter 
Neutral Ground Resistor 

Battery

 
Gambar 47. Simbol gambar

97

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 111/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

SPLN S5.003-1: 2014

Tampilan-tampilan status yang digunakan mengacu pada gambar 48.

Tampilan Status

ITEMS SYMBOL REMARK


CB CLOSED Busbar 
' s color, filled

CB OPENED Busbars color, blank

CB INVALID Purple, Half-filled

CB UNKNOWN Orange, Half-filled

LBS CLOSED Feeder’s color 

LBS OPENED Feeder’s color 

LBS INVALID Purple

Feeder’s color 
, filled
DS CLOSED

DS OPENED Feeder’s color  blank

DS INVALID  Purple, half- filled

DS UNKNOWN Orange, half-filled

ES CLOSED Ground’s color 

Feeder’s color 
ES OPENED

ES INVALID Purple

ES UNKNOWN Orange

RACKED IN CB CLOSED Feeder’s color 


, filled

RACKED OUT CB CLOSED Feeder’s color 


, filled

RACKED INVALID CB CLOSED Feeder’s color 


, filled

RACKED IN CB OPENED Feeder’s color 


, blank

RACKED OUT CB OPENED Feeder’s color 


, blank

RACKED INVALID CB OPENED Feeder’s color 


, blank

RACKED IN CB INVALID Feeder’s color 


, half-filled

RACKED OUT CB INVALID Feeder’s color 


, half- filled

RACKED INVALID CB INVALID Feeder’s color 


, half- filled

GENERATOR Feeder’s color 

TRANSF. 2 WINDING S Feeder’s color 

TRAN SF
. 3 WINDINGS Feeder’s color 

REACTOR Feeder’s color 

CAPACITOR Feeder’s color 

VOLTAGE STATUS
: LIVE
DEAD
 
Gambar 48. Tampilan status 

98

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 112/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

 
SPLN S5.003-1: 2014

WARNA TAMPILAN
Tabel 51 berikut ini menjelaskan mengenai warna tampilan yang berlaku untuk monitor
dan layar tayang. Pewarnaan SLD yang dinamis didasarkan atas dua sumber yaitu:

-- Secara logika
Secara logika(berdasarkan
(berdasarkanposisi PMT
posisi dan dan
PMT PMS)PMS)
dan pengukuran tegangan.
untuk bagian yang tidak
memiliki VT.
Tabel 51. Warna tampilan 
URAIAN WARNA (R,G,B)

Single line diagram 500 kV Biru (0,100,255)


Single line diagram 275 kV Biru-muda (0,200,255)
Single line diagram 150 kV Merah (255,0,0)
Single line diagram 66 kV Kuning (255,255,0)
Single line diagram 30 kV Hijau (0, 255, 0)
Single line diagram 20 kV Coklat (200, 150, 0)
Single line diagram 11 kV Abu-abu (180, 180, 180)
Single line diagram 6 kV Merah muda (255, 150, 180)
Single line diagram 3,3 kV Hijau-muda (0, 255, 150)

 All devices   Warna Busbar


Invalid device  Ungu dan perubahan simbol (220, 0, 255)
Device saat loss connection (out of poll)  Oranye (255, 150, 50)
Background color   Hitam (0, 0, 0)
Ground color   Biru-tua (10, 10, 180)
Kondisi tidak bertegangan Putih (255, 255, 255)
Perubahan status karena gangguan Frame CB warna merah, blinking
Perubahan status karena local dari gardu induk Warna Busbar, blinking + karakter”L” 
Perubahan status karena r emote dari Warna Busbar, blinking  
dispatcher
Telemetering   Putih (255, 255, 255)
Invalid telemetering   Ungu (220, 0, 255)
Unknown  Oranye (255, 150, 50)
Telesignal Alarm :
Off   : sesuai warna latar kotak annunciator  
 Aktif : Terisi solid warna Merah, blinking.
Setelah di acknowledge tidak blinking.

Keterangan:
   Untuk change of state gangguan, setelah acknowledge  blinking hilang, warna merah
pada frame CB mengikuti warna busbar.
   Untuk level tegangan yang tidak tercantum dalam tabel di atas, menggunakan warna
pada single line diagram level tegangan terdekat.
   Warna jaringan sesuai dengan feeder colouring .
   Untuk detail kode warna akan dijelaskan pada SPLN mengenai kode simbol dan
warna.

99

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 113/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 114/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 115/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

Pengelola Standardisasi :

PT PLN (Persero) Pusat Penelitian dan Pengembangan Ketenagalistrikan


Jl. Durentiga, Jakarta 12760, Telp. 021-7973774, Fax. 021-7991762,
www.pln-litbang.co.id

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 116/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 117/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 118/118