GROWTH STEEL GROUP POWER PLANT
2 x 15 MW

Protection of Generator

Electrical Data of Turbo Generator :


1. Merk : Shandong Ji nan Power
2. Type : DF - 15 - 2
3. Rate Power : 15000 kW
4. Rate Power Faktor : 0.8
5. Rate Current : 10500 Volt
6. Rate Speed : 3000 r/min
7. Rate Efficiency : 97.3 %
8. Excitation Current : 259 A
9. Excitation Voltage : 203 V

Power Engineering Hal. 1 / 30


Pengantar

Untuk Proteksi dari Turbo Generator sangat kompleks dan rumit.

Generator adalah Mesin yang dikoneksikan ke busbar, biasanya


disertai oleh Transformator, Circuit Breaker dan peralatan pendukung
lainnya sehingga menjadi suatu sistem.

Generator juga diserta dengan sistem eksitasi, prime over,


voltage regulator dan sistem pendingin oleh karena itu bukan peralatan
tunggal.

Perlindungan generator juga harus dikoordinasikan dengan


peralatan pendukung lainnya.

Power Engineering Hal. 1 / 30


Generator Protection

Untuk Proteksi dari Turbo Generator sangat kompleks dan rumit.

Generator adalah Mesin yang dikoneksikan ke busbar, biasanya


disertai oleh Transformator, Circuit Breaker dan peralatan pendukung
lainnya sehingga menjadi suatu sistem.

Generator juga diserta dengan sistem eksitasi, prime over,


voltage regulator dan sistem pendingin oleh karena itu bukan peralatan
tunggal.

Perlindungan generator juga harus dikoordinasikan dengan


peralatan pendukung lainnya.

Power Engineering Hal. 1 / 30


Tabel 1. Generator Protection
Kondisi Abnormal yang memberikan alarm dan indikasi untuk perlindungan Pembangkit
Di bawah 1 MW Di atas 1 MW Di atas 10 MW Di atas 100 MW

1 Differential - - √ √

2 Restricted earth fault - - √ √

3 Stator turn to turn fault - - - √

4 Time Over Current √ √ - -

5 Temperature - √ √ √

6 Negative sequence current - √ √ √

7 Loss of load - - √ √

8 Loss of input - anti - motoring - √ √ √

9 Loss of Field - - √ √

10 Loss of synchronism - - √ √

11 Over speed √ √ √ √

12 Over Voltage √ √ √ √

13 Rotor earth fault - - √ √

14 Back up over current √ √ √ √

15 Bearing temperature - - √ √

16 Bearing insulation - √ √ √

Power Engineering Hal. 1 / 30


Generator Protection

Perlindungan Generator - Transformator dapat dibagi


menjadi tiga kelompok, yaitu :
1. Relai proteksi untuk mendeteksi kesalahan atau kondisi
abnormal eksternal unit.
2. Relai proteksi untuk mendeteksi kesalahan internal untuk
unit.
3. Perangkat yang terkait dengan unit, misalnya :
pengamanan kecepatan lebih, perangkat suhu,
pengukuran untuk bantalan, gulungan dll. Beberapa di
antaranya penyebab alarm dan trip.

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group
Sepam Hardware - G87

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

General Characteristics

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

Phase Rotation Direction

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

CT - VT Sensors

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

CT - VT Sensors

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

Particular Characteristics

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

Predefined Control Logic

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

Logic Input/Output Assignment

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

87M : Machine Differential

I set (%) = (15% s.d 25%) x In = 20% x In


= 20% x (18750/(√3x10.5) = 20.61 A
Generator di setting 87M = 20.6 A
Power Engineering Hal. 1 / 30
Generator Protection PLTBm Growth Steel Group

50/51 : Phase Overcurrent

OC50 = 1.05 x In OC50 max = (1/0.232) x In


= 1082 A = 4330 A
Generator di setting OC50 = 1060 A ; OC50 max = 4000 A
Power Engineering Hal. 1 / 30
Generator Protection PLTBm Growth Steel Group

50N/51N : Earth Fault

I set = 1.05 x In ; time = 100 ms


= 1082 A
Generator di setting I set = 1060 A ; time delay = 590 ms
Power Engineering Hal. 1 / 30
Generator Protection PLTBm Growth Steel Group

46 : Negative Sequence Current / Unbalance

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

49RMS ; Thermal Overload

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

67 : Directional Overcurrent

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

67N : Directional Earth Fault

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

32P : Active Overpower

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

32Q : Reactive Overpower

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

40 : Field Loss

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

78PS : Pole Slip

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

59 : Over Voltage

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

81 : Over Frequency

Power Engineering Hal. 1 / 30


Generator Protection PLTBm Growth Steel Group

38/49T : Temperature Monitoring

Power Engineering Hal. 1 / 30