Arus Medan
Reaktif (MVAR)
Tegangan
(V) AVR
MW
MVAR
Voltage Eror
PT Compensator 90R
Detector
Minimium Firing
CT V/I converter Excitation
Limiter
Signal
Mixer
Over Excitation 70E
Limiter
shunt
Damping
Pulse Generator 1
From Regulator Drawer
Level Limiter
Pulse Generator 2
Pulse Generator 3
Pulse Generator 5
Pulse Generator 6
70E : Base Adjusting Equipment (manual control) 41E : Field Circuit Breaker
90R : Voltage Adjusting Equipment (auto control)
Proteksi :
Resiko generator out of sinkron dan pemanasan
1. Minimum Excitation Limit rotor
Deteksi isolasi belitan rotor generator dan rotor
exciter, memicu trip relay overcurrent (64F) di
2. Field Ground Detection
panel Field Breaker, dan alarm control room
Alarm :
1. Operation of minimum excitation limiter
2. Loss of Pulse in Firing Drawer Abnormal pada Pulse Generator, Firing Drawer
3. Blowing of Fuse in thyristor amplifier Fuse pada Power Drawer terbakar, AVR pindah
Over excitation adalah kondisi dimana arus eksitasi berlebihan yang disebabkan
AVR berusaha mengejar kekurangan tegangan/MVAR sistem.
Hal ini sering terjadi pada saat kebutuhan MW sistem besar sedangkan jumlah
pembangkitan terbatas