2. KOLOM LANGSING-B
Prosedur Desain SNI 2847-13
The tied column of Figure 11.7 has been approximately sized to the dimensions 12 in. × 15 in.
It is to be used in a frame braced against sidesway. The column is bent in single curvature
about its y-axis and has an lu of 16 ft. If k = 0.83, fy = 60,000 psi, and fc = 4000 psi, determine the reinforcing
required. Consider only bending in the plane of the frame.
Note also that the unfactored dead axial load PD is 30 k, and concrete is normal weight.
Analisis Perbesaran Momen Untuk Portal Bergoyang
Analisis Perbesaran Momen Untuk Portal Bergoyang
(pembesaran momen
portal bergoyang)
Analisis Perbesaran Momen Untuk Portal Bergoyang
Prosedur Desain Kolom Langsing pada Portal Bergoyang
Prosedur Desain Kolom Langsing pada Portal Bergoyang
Prosedur Desain Kolom Langsing pada Portal Bergoyang
Contoh Kolom langsing Portal Bergoyang (Sway)
Analysis of Sway Frames
Determine the moments and axial forces that must be used for the design of column CD of the
unbraced frame of Figure 11.9. Consider only bending in the plane of the frame. The assumed
member sizes shown in the figure are used for the analyses given in the problem. fy = 60,000 psi
and fc = 4000 psi. For this example, the authors considered the load factor cases of ACI
Equations 9-2, 9-4, and 9-6. For other situations, other appropriate ACI load factor equations
will have to be considered