PT. Elenes Intermata PT. Trimitra Wujud Rekanusa Date: 4 June 2021 Halaman: 1 dari 13
Pengadaan dan Pemasangan Fixed Water Foam Monitor
di Dermaga TBBM Area Maluku Papua (MOR VIII)

STANDARD PROSEDUR PENGGUNAAN


FIXED WATER FOAM MONITOR
VAJRA 331 WITH VARSHA HF40U NOZZLE

PT. Elenes Intermata

Fixed Foam Monitor


Dermaga TBBM Area Maluku Papua (MOR VIII)

Non Core Core

Rev. Date Page Description Prepared Checked Approved


0 04-Jun-21 ALL Issuance for Supply Only SHGN RHS RHS
Contractor Job No. Contractor Doc. No.
Rev

Vendor Quot. No. Vendor Doc. No.


0
Pengadaan dan Pemasangan Fixed Foam Monitor
di Dermaga TBBM Area Maluku Papua (MOR VIII) Halaman: 2 dari 13

DAFTAR ISI

1 Pendahuluan

2 Instalasi

3 Prosedur
3.1 Prosedur Pengoperasian
3.2 Prosedur Perawatan

4 Gambar Referensi
Contractor Job No. Contractor Doc. No.
Rev

Vendor Quot. No. Vendor Doc. No.


0
Pengadaan dan Pemasangan Fixed Foam Monitor
di Dermaga TBBM Area Maluku Papua (MOR VIII) Halaman: 3 dari 13

1 Pendahuluan

Fixed water monitor merupakan equipment yang digunakan untuk memadamkan api,
dengan cara mengarahkan nozzle pada titik api. Berikut adalah spesifikasi monitor tersebut.

HD Fire - Fixed Foam Monitor


Monitor Type Vajra 331 (material contruction: Bronze)
Inlet Size 4” RF Flange 150#, outlet size 3” BSP Male for Nozzle.
Maximum flow 750 GPM, Monitor Elevation 90° above horizontal, and 65° below horizontal.
Monitor rotation 360° continuous, monitor movement is handle with twist lock.
Color is Red RAL 3001.
Complete with:
Monitor Nozzle Type Varsha HF40U 750 GPM
Material of nozzle monitor is bronze.

2 Instalasi
Fixed foam monitor dipasang pada jalur fire hydrant yang ada di lapangan TBBM Maluku-Papua
Koneksinya menggunakan flange 4” ANSI 150#. Fixed Foam Monitor dipasang di area jetty
yang akan diproteksi. Di jalur piping sebelum fixed foam monitor harus terpasang Gate Valve yang
digunakan untuk mematikan/ menghidupkan aliran air.
Pada saat pemasangan nozzle type Varsha HF40U yang dikoneksikan pada standpipe monitor, operator
harus memasang dengan benar (Gunakan Sealtape). Nozzle dikoneksikan pada standpipe monitor
dengan cara koneksi drat/ threaded type BSP Male. Foam nozzle dipasang di bagian ujung
standpipe monitor. Operator harus memperhatikan mengenai kekuatan pada inlet flange connection
fixed foam monitor dengan mengecek kekencangan baut & mur pada flange connection.

3 Prosedur
3.1 Prosedur Pengoperasian
Berikut prosedur pengoperasin fixed foam monitor Vajra 331
1. Pastikan kondisi pompa eksisting/ pompa yang tersedia dilapangan berfungsi dengan baik, misalnya:
Kapasitas pompa tidak kurang dari kapasitas yang dibutuhkan fixed foam monitor, dapat memberi
tekanan dan debit air sesuai dengan kapasitas yang dibutuhkan fixed foam monitor sehingga fixed
foam monitor dapat beroperasi dengan maksimal.

2. Pastikan tanki foam sudah terisi dengan foam concentrate 3% sesuai dengan kapasitas tanki foam,
untuk memaksimalkan proses pemadaman kebakaran. Foam concentrate tidak boleh diencerkan atau
terkontaminasi oleh bahan asing/ foam concentrate merk lain karena dapat menyebabkan perubahan
produk dan pegurangan atau hilangnya kemampuan pemadaman kebakaran. (NFPA 11, Bagian 2-4.1)
(Pedoman Umum dan Rekomendasi untuk Penyimpanan Foam Concentrate - HD Fire terlampir)

3. Pastikan koneksi selang foam induksi sudah terkoneksi dengan baik ke tanki foam agar menghasilkan
foamix yang maksimal. Kalau ada udara terjebak dalam selang tidak ada masalah.

4. Fixed foam monitor harus diposisikan pada arah penyemprotan. Untuk mengarahkannya:
a) Lock/ kunci rotasi 360⁰ (item no.2 gambar referensi) pada fixed foam monitor harus dibuka
terlebih dahulu, lalu fixed foam monitor diposisikan sesuai dengan posisi yang diinginkan.
b) Lock/ kunci atas-bawah (item no.7 gambar referensi) pada fixed foam monitor harus dibuka
terlebih dahulu, lalu fixed foam monitor diposisikan sesuai dengan posisi yang diinginkan.
c) Untuk mode semprotan fog (mode payung) dan jet (mode lurus) aliran fixed foam monitor, dapat
diubah pada monitor nozzle. Lock/ kunci mode jet-fog (item no. 8 gambar referensi) dapat diputar
kearah kiri untuk mode fog, dan dapat diputar kearah kanan, untuk mode jet.

5. Hidupkan pompa, dan pastikan settingan pressure pada pompa tidak melebihi kapasitas 12 bar atau
batasan pressure maksimal pada monitor equipment (dapat dilihat pressure gauge pada monitor).

6. Setelah tahap 1 – 5 terlaksana, kita dapat membuka gate valve (isolation valve) yang terpasang
sebelum inlet fixed foam monitor secara perlahan.

7. Aliran pada monitor akan menginduksi foam concentrate 3%, sehingga bercampur dengan air pada
nozzle fixed foam monitor untuk menghasilkan foamix/ foam solution.

8. Setelah pengoperasian fixed foam monitor selesai dilakukan, dengan menutup selang foam induksi
untuk dilakukan flushing.

9. Setelah proses flushing selesai, tutup kembali aliran atau gate valve menuju fixed foam monitor.
Contractor Job No. Contractor Doc. No.
Rev

Vendor Quot. No. Vendor Doc. No.


0
Pengadaan dan Pemasangan Fixed Foam Monitor
di Dermaga TBBM Area Maluku Papua (MOR VIII) Halaman: 4 dari 13

3.2 Prosedur Perawatan


Berikut prosedur perawatan monitor Vajra 331

a) Inspeksi fisik dari monitor dan tanki foam dilakukan minimal sebulan sekali.

b) Pengecekan yang dilakukan sebulan sekali berfungsi untuk mengecek kerusakan fisik dari monitor,
lakukan greasing pada joint monitor ketika manuver 360⁰, atas-bawah, dan setting mode fog- jet
monitor nozzle dirasa kaku/ keras.

c) Pada monitor ini perlu dilakukan pengoperasian fungsional minimal 3 bulan sekali.
Tahapan pengoperasian sama seperti pada saat melakukan prosedur pengoperasian, tapi tanpa
menggunakan foam concentrate atau hanya mengoperasikan monitor menggunakan air saja.

e) Setelah pengoperasian fixed monitor selesai dilakukan, tutup kembali aliran atau gate valve menuju
monitor.

f) Pemeriksaan atau pengetesan berkala yaitu minimal 1 bulan sekali harus dilakukan juga pada
gate valve/ butterfly valve (isolation valve) yang terpasang sebelum inlet monitor.

g) Semua pengecekan harus tercatat di buku record pengecekan. Pengecekan secara fisik juga dilakukan
pada aksesoris yang terdapat pada monitor (maintenance record by user ).
Contractor Job No. Contractor Doc. No.
Rev

Vendor Quot. No. Vendor Doc. No.


0
Pengadaan dan Pemasangan Fixed Foam Monitor
di Dermaga TBBM Area Maluku Papua (MOR VIII) Halaman: 5 dari 13

4 Gambar Referensi
Fixed Foam Monitor VAJRA 331
8

Elevasi Tampak Samping

No. Deskripsi
1 Flange Dasar
2 Lock/ Kunci rotasi 360°
3 Elbow
4 Handle/ Pegangan
5 Outlet Elbow
6 Monitor Nozzle
7 Lock/ Kunci atas-bawah
8 Lock/ Kunci mode fog & jet

Monitor Nozzle Varsha HF40U

Performa Data

Catatan:
1. Performa data diatas menggunakan sudut 30° ke arah atas.
2. Performa data diatas tergantung kepada keadaan cuaca termasuk arah mata angin, kelembapan udara, dll.
Contractor Job No. Contractor Doc. No.
Rev

Vendor Quot. No. Vendor Doc. No.


0
Pengadaan dan Pemasangan Fixed Foam Monitor
di Dermaga TBBM Area Maluku Papua (MOR VIII) Halaman: 6 dari 13

Location :
Date :
Monitor Tag :
Inspector :

Status
No Deskripsi Check Item Check Quality Control Periode Keterangan
OK C
1 Gate Valve Handle Valv e - Pada posisi close
- Dapat dibuka-tutup normal
Konek si - Tidak terdapat kebocoran
Perbulan
- Kondisi baut ketat.
Body - Tidak terdapat kebocoran
- Tidak terdapat korosi
2 Fire Foam Monitor Konek si - Tidak terdapat kebocoran
- Kondisi baut ketat.
Handle - Kondisi terpasang dimonitor
- Tidak berkarat
Lock Handle - Kondisi terpasang dimonitor
- Tidak berkarat
Body - Tidak terdapat kebocoran
- Tidak terdapat korosi Perbulan
- Dapat diputar 360⁰
- Dapat bergerak 65⁰ bawah
- Dapat bergerak 90 ⁰ atas
Engsel - Lakukan greasing jika kaku
Nozzle - Lakukan greasing jika kaku
- Setup Fog-Jet tidak kaku
- Tidak terjadi kebocoran
3 Tangki Foam Konek si Selang - Tidak terjadi kebocoran
Konek si Drain - Tidak terjadi kebocoran
Lev el Gauge - Tidak terjadi kebocoran
- Tidak Tersumbat
Perbulan
Body - Tidak terjadi kebocoran
- Tidak terdapat celah air
Manhole - Tertutup
Foam Concentrate - Terisi penuh
4 Pengoperasian Gate Valv e 4" - Dapat dibuka-tutup normal
Monitor - Mengeluarkan air normal
Per 3 Bulan
- Pengoperasian hanya air
Tangk i Foam - Foam terisi penuh

"OK" : Kondisi Baik "C" : Kondisi Cukup

Note:

(H ubungi kami P T . T r imitr a Wujud Rekanusa di T elp. (+6 2 ) 2 1 4 2 2 7 6 4 7 ; Email: admin@ tr imitr agr oup.com)
GENERAL GUIDELINES AND
RECOMMENDATIONS FOR FOAM
STORAGE
The effective life of foam concentrates can STORAGE TANKS
be optimised by proper storing and Foam concentrates are suitable for
handling. These guidelines and transferring into bulk storage tanks for
recommendations need to be followed for long-term storage.
having effective life and performance of HD
Fire-Fighting Foams. Materials of construction
Foam concentrates have a neutral pH and
SHELF LIFE generally, no corrosion problems will occur
HD Fire Protect offers a range of superior with metals or plastics (Except where noted
quality foam concentrates that are specially below).
formulated to ensure exceptional storage
stability as well as firefighting performance. Storage tanks should be fabricated from or
be lined with the following materials:
A shelf-life of at least ten years can be
expected if the foam is stored properly  Mild Steel (uncoated): Generally, not
according to mentioned recommendations. recommended for synthetic detergent
based foam concentrates. Ferrous metal
To ensure satisfactory performance foam ions can adversely affect the foam
should be sampled at least annually as concentrate leading to reduced
recommended in NFPA 11, Section 8-2, “At firefighting performance. Suitable for
least annually, an inspection shall be made use with natural Protein-based foam
of foam concentrates and their tanks or concentrates, although there may be
storage containers for evidence of some slight initial etching which will not
excessive sledging or deterioration. affect the tank or contents. Natural
Samples of concentrates shall be sent to protein-based foam concentrates
the manufacturer or qualified laboratory for quickly inhibit this process by forming a
quality condition testing.” thin protective layer on the surface of
the mild steel.
SHIPPING CONTAINERS
Foam concentrate may be stored in its  Mild Steel (coated): Surface preparation
original shipping containers. It is available and coating should be performed by
in 20/30 litre black/blue plastic drums, 200 qualified personnel.
litre (55 US gal) black/blue plastic drums,
and 1000 litre IBCs. All containers comply  Stainless Steel (304 and higher) is
with UL 162 (7th Edition) and UN acceptable.
recommendations. However, these should
be regularly inspected to verify their  Tanks with welded construction should
condition. In the unlikely event of leakage, have all joints treated to ensure
the foam should be decanted into another consistent properties close to welds.
clean drum, sealed and tested to ensure it There may be very slight pitting which
is still in satisfactory condition. The will not affect tank or contents.
maximum safe stacking height for 20/30
litres plastic drums is two high without  Glass Reinforced Plastic (GRP):
pallets or 4 high with pallets (2 high per Fibreglass is accepted. But it is not
pallet); for 210 litre plastic drums is 2 high recommended for foam systems
(with or without pallets), and for IBCs is 2 involving pressure displacement.
high. Plastic drums should not be stored in
direct sunlight.  High-Density Polyethylene (HDPE).

04-2018 Page 1 of 4
 Polypropylene: The use of zinc, tank to prevent clogging in the event of any
galvanized materials, and aluminum in minor sediment that might have formed or
storage tanks, pipe work, and other foreign materials in the tank.
machinery handling foam concentrates
should be avoided. In the event that Pipe work systems should be designed to
foam is being replenished into an prevent water and other liquids accidentally
existing system where zinc or entering the tank and foam concentrate
galvanized materials were used in accidentally escaping from the tank.
original construction, it is advised that
some means are provided by which the Foam concentrates are suitable for
system can be flushed through with decanting into small containers. Agitation
water and drained after use. and air intrusion should be kept to a
minimum if foam concentrate pumps are
Foam containers, drums or totes should used.
always be kept in closed condition during
storage. EVAPORATION
If foam concentrate is allowed to evaporate
Gaskets, seals, and bladders may be freely, the water and solvent in the
fabricated from all commonly-used concentrate will evaporate. With HD
elastomers, as given below: ARAFFF foam concentrates this may cause
 Ethylene Propylene Diene Monomer a skin of polymer to form on the surface of
(EPDM) or Ethylene Propylene the concentrate which could plug
Rubber (EPR) (e.g. AP Rubber). proportioning orifices.
 Butyl rubber (modified isobutylene) To minimise evaporation losses, the
(e.g. Bucar, Polysarbutyl, Buna N, concentrate tank should be sealed and a
Nitrophyl). pressure vacuum vent installed to break
 Silicone (e.g. GE Silicone, the seal when the concentrate is required.
Rhodorsil). Evaporation will also be reduced by
 Fluoroelastomer (e.g. Viton). keeping the concentrate tank full. However,
 Nitrile Rubber (butadiene an ullage of 5 to 10% of the tank volume
acrylonitrile copolymer). (e.g. expansion dome) should be
Fittings in foam concentrate pumps and maintained to allow for differences in
valves may be made from brass, bronze, thermal expansion coefficients between the
and stainless steel. tank materials of construction and the foam
concentrate. If it is not possible to seal the
PIPE WORK tank, air ventilation may be provided by
The choice of pipe work materials depends breathers fitted with cowls. Alternatively, a
on the anticipated contact time with the nitrogen system comprising a nitrogen
foam concentrate. For continuous contact, atmosphere maintained above the
the same materials of construction apply concentrate at a pressure fractionally
as for storage tanks (see above). PVC, above atmospheric pressure will reduce
copper, brass, and bronze pipes are also evaporation and ensure that leaks are
acceptable for continuous contact. For nitrogen loss rather than oxygen gain. A
intermittent contact, normal pipe work layer of hollow plastic spheres, either
materials are satisfactory subject to normal polypropylene or polyethylene, may be
engineering criteria. floated on the surface of the concentrate to
reduce evaporation.
Inlet pipe work should be located at the
base of the tank to avoid excessive Mineral oil can be added on the surface of
foaming during filling. Outlet pipe work the foam to prevent water evaporation Pour
should be located above the base of the sufficient Mineral oil slowly to form 4-6 mm

04-2018 Page 2 of 4
layer on the foam surface. The oil should regularly will assist in judging the cessation
be added at different points of the tank so of frothing.
that the oil is uniformly spread over the When using natural protein-based foam
surface of the foam concentrate. concentrates or HD AR-AFFF in locations
where drained areas may be heated (pipe
FLUSHING work, recently operated pumps), flushing
Storage tanks, pipe work, and pumps that should be carried out immediately after use
have been filled with foam concentrate or to prevent deposition of solid material due
solution should be flushed with clean water to localised drying-out.
and drained after use. The need for
flushing storage tanks falls into two areas: BUNDING
In some instances there may be a need for
When changing foam concentrate stored in bulk foam concentrate stocks to be
an existing tank, or after commissioning: bunded or diked. This will depend on the
The foam system should be drained off of circumstances of a particular site, and the
any foam concentrate previously contained relevant environmental enforcing authority
in it (or water used for hydrostatic tests), should be consulted.
cleaned, and dried prior to filling it with the
final charge of foam concentrate. Particular COMPATIBILITY
care should be taken when changing Foam concentrates must not be diluted or
synthetic foam types. Drain off system - contaminated by foreign materials or other
open all valves. Fill foam tank with water types or brands of foam concentrate. Such
and allow draining of water. Repeat. Back mixing may lead to physico-chemical
flush through outlet using sufficient water changes in the product and a reduction in
as calculated to completely fill and overflow or loss of firefighting capability. This is
the tank twice. Allow to drain. Purge out all recognised by NFPA 11, Section 2-4.1,
water, check to see foaming has ceased. If “Different types and brands of
not continue to cycle through process until concentrates and solutions might be
foaming has diminished. Set valves incompatible and shall not be mixed in
correctly. Fill slowly with foam concentrate storage”. Consult the manufacturer for
to minimize frothing and formation of air guidance.
pockets. Charge foam line to furthest
designated valve so that foam concentrate TEMPERATURE
is present in all pipes where it is required. The maximum storage temperature is 49oC
Drain foam concentrate from all pipes (120oF) although temperatures up to 60oC
where drying out could occur and rinse (140oF) are acceptable for short periods. If
through with pressure hose reel or similar. ambient temperatures exceed 35oC (95oF)
then storage vessels should be kept under
In normal usage of system: This presumes shed or indoor locations.
it has been designed to avoid “dead-legs”
in the system and drainage/flushing points The Freezing Point and Lowest Use
are included to facilitate preventative Temperatures (LUT) at which foam
maintenance. Judicious use of high concentrates will proportion correctly are
pressure water regularly will enable pipe available on the product data sheets. If
work to be flushed and drained to dry so ambient temperature is below the LUT or
preventing any drying out of foam freezing point then storage vessels should
concentrate which would lead to the be fitted with insulation lagging. Do not add
deposition of any solid material. Drain and freezing point depressants such as
flush until foaming diminishes. Avoid ullage ethylene glycol or any proprietary brands
greater than 10%. Use of a transparent of antifreeze. Repeated freezing and
bottle filled to half level and shaken thawing have no adverse effect on the

04-2018 Page 3 of 4
performance of most foam concentrates. Details of UL Listings and FM approvals are
However, it should be noted that foam available on the product data sheets.
concentrates expand on solidification and,
like water turning into ice, may damage a INSPECTIONS
completely rigid container. In accordance Foam concentrates need to be inspected
with UL 162 (7th Edition) foam concentrate in accordance with NFPA 11 and/or
shipping containers are marked with the applicable local standards. An annual
minimum and maximum storage inspections is typically sufficient. Please
temperatures. contact the manufacturer in case of any
queries.

NOTICE :

Although all care has been taken to ensure correctness of data, however HD Fire Protect takes no
responsibility or the liability of any kind for any accidents, loss, damage or deterioration arising
directly or indirectly by referring these guidelines. The information provided by us are to the best of
our knowledge and belief, and are general guidelines only. Site handling and installation control is
beyond our reach. Hence we give no guarantee for result and take no liability for damages, loss or
penalties whatsoever, resulting from our suggestion, information, recommendation or damages
due to our product. Product development is a continuous programme of HD FIRE PROTECT PVT.
LTD. and hence the right to modify any specification without prior notice is reserved with the
company.

04-2018 Page 4 of 4
FOAM DISPOSAL GUIDELINES

HD Fire Protect foam concentrates are A WWTP should be contacted prior to


formulated for minimal environmental and discharge. In most cases it will require a
ecological impact. However, like all foams, Material Safety Data Sheet of the foam
these could have some effect on the concentrate (which has the information on
environment under certain conditions. composition, BOD, aquatic toxicity), an
Measures should therefore be adopted to estimate of the total volume of foam-water
dispose the foams responsibly and carefully solution to be discharged, and the
in accordance with relevant liquid waste anticipated timing of the discharge. WWTP
disposal regulations. Modern foams based may require foam-water solution to be
on C6 fluorocarbons have low toxicity and diluted in advance. Foam-water solution
do not bioaccumulate, however those are pre-treated in oil/water separators may
persistent in the environment. Foams need emulsify with hydrocarbon fuels and so
to be disposed as per below guidelines and carry them over into the water stream.
as per local regulations, pollution control Synthetic detergent based foams have a
board guidelines and government norms. greater tendency to emulsify than natural
protein-based foams. Foam-water solution
Foam-Water Solution generally exhibits low toxicity to bacteria in
WWTPs. Natural protein-based foams
Foam-water solution is generally exhibit lower toxicity than synthetic
discharged under either controlled detergent based foams.
conditions (e.g. training exercises, foam
system commissioning and maintenance Emergency Containment
tests) or uncontrolled conditions (e.g.
manual firefighting and vapour suppression This is applicable when foam-
operations, foam system activation). water solutions are used in emergency
testing, in case of fire or uncontrolled
Foam-water solution should be contained conditions. In such cases one ca use
and disposed of in an environmentally following measures:
responsible manner. It should not be
diluted and dispersed into watercourses,  Blocking drains to prevent large
soils, or foul water drains without the prior quantities of contaminated foam solution
consent of the local environmental from reaching the common sewage
authority. systems.
 Use of sandbags or soil to create a
There are a variety of containment perimeter bund.
measures that may be employed, ranging
from temporary arrangements to
permanent engineered systems. The
relevant enforcing authority should be
consulted for practical advice on the most
appropriate containment measures for a
particular site and discharge scenario.
Once the foam-water solution has been
contained, the most common method of
disposal is to treat it biologically in a waste
water treatment plant (WWTP).

Page 1 of 3
01/19
 Use of pits or trenches, again
preferably with an impermeable lining to
prevent seepage of foam to ground.
 Use of portable storage tanks or
drums.

Foam Concentrate Disposal

Foam concentrate may need to be


disposed of in the event of a spillage or if it
is judged unsuitable for use as a result of
age or being diluted or contaminated by
foreign materials.

It should be taken to an approved disposal


site by a licensed waste disposal
contractor for disposal by controlled
release to a WWTP, incineration, or liquid
landfill.

Further Information

National Fire Protection Association Code


11, including its Annex E, “Foam
Environmental Issues” (available at
https://www.nfpa.org/Codes-and-
Standards/All-Codes-and-
Standards/Codes-and-Standards)

Note

 The above data is given in good faith


and for general guidelines only.
 HD Fire Protect does not assume any
liability expressed or implied in the
presentation of this data
 The right is reserved to vary or modify
any data without prior notice.

Page 2 of 3
01/19
CAUTION

NOTICE
Although all care has been taken to ensure correctness of data, however HD Fire Protect takes
no responsibility or the liability of any kind for any accidents, loss, damage or deterioration
arising directly or indirectly by referring these guidelines. The information provided by us are to
the best of our knowledge and belief, and are general guidelines only. Site handling and
installation control is beyond our reach. Hence we give no guarantee for result and take no
liability for damages, loss or penalties whatsoever, resulting from our suggestion, information,
recommendation or damages due to our product. Product development is a continuous
programme of HD FIRE PROTECT PVT. LTD. and hence the right to modify any specification
without prior notice is reserved with the company.

LIMITED WARRANTY
HD FIRE PROTECT PVT. LTD. hereby referred to as HD FIRE warrants to the original purchaser
of the fire protection products manufactured by HD FIRE and to any other person to whom
such equipment is transferred, that such products will be free from defect in material and
workmanship under normal use and care, for two (2) years from the date of shipment by HD
FIRE. Products or Components supplied or used by HD FIRE, but manufactured by others, are
warranted only to the extent of the manufacturer’s warranty. No warranty is given for product
or components which have been subject to misuse, improper installation, corrosion,
unauthorized repair, alteration or un-maintained. HD FIRE shall not be responsible for system
design errors or improper installation or inaccurate or incomplete information supplied by buyer
or buyer’s representatives. HD FIRE will repair or replace defective material free of charge,
which is returned to our factory, transportation charge prepaid, provided after our inspection
the material is found to have been defective at the time of initial shipment from our works. HD
FIRE shall not be liable for any incidental or consequential loss, damage or expense arising
directly or indirectly from the use of the product including damages for injury to person,
damages to property and penalties resulting from any products and components manufactured
by HD FIRE. HD FIRE shall not be liable for any damages or labour charges or expense in making
repair or adjustment to the product. HD FIRE shall not be liable for any damages or charges
sustained in the adaptation or use of its engineering data & services. In no event shall HD Fire’s
product liability exceed an amount equal to the sale price. The foregoing warranty is exclusive
and in lieu of all other warranties and representation whether expressed, implied, oral or
written, including but not limited to, any implied warranties or merchantability or fitness for a
particular purpose. All such other warranties and representations are hereby cancelled.

Page 3 of 3
01/19

Anda mungkin juga menyukai