PARAMETER KONTROL BOILER :

UNTUK TEKANAN DIBAWAH 30 BAR

Control Range
No Parameter Unit
Make Up BFW BW Condensate
1 PH - 8-9 10 – 11.8 8-9
2 Conductivity S/cm - < 400 < 4000
3 Turbidity NTU - - Clear -
4 Color mg/L PtCo - - Clear -
5 M Alkalinity mg/L CaCO3 - - < 700 -
6 Calcium Hardness mg/L CaCO3 TRACE TRACE TRACE TRACE
7 Total Hardness mg/L CaCO3 TRACE TRACE TRACE TRACE
8 Chloride mg/L Cl- - - - -
9 Total Iron mg/L Fe - - - -
10 Silica mg/L SiO2 - - < 150 -
11 Phosphate mg/L PO4 - - - -
12 Sulphate mg/L SO4 - - - -
13 O Alkalinity mg/L CaCO3 - - - -

Note = Make up = Air dari softener


BFW = Boiler Feed Water (Make Up + Condensate)
BW = Air dari boiler

PLANT DIAGRAM
Existing plant

Boiler

Water Pond Water Tank

Recommendation :
A. Ditambahkan softener untuk mengurangi kadar Calcium dan Magnesium
Hardness di Make Up dan Boiler Feed Water
B. Tujuannya adalah mengurangi potensi terjadinya kerak di boiler
C. Untuk regenerasi softener diperlukan larutan garam. Garam yang dipakai adalah
garam yang mempunyai spesifikasi sebagai berikut :
Kandungan Presentease
Sodium Chloride (NaCl) 98.8% min
Water Insoluble < 0.1%
Moisture < 0.2%
Calcium (Ca) < 0.4%
Magnesium (Mg) < 0.1%
Sulfate (SO4) < 0.9%
Alkalinity < 0.01%
Iron (Fe) < 0.01%

Condensate

Boiler
Water Tank

Softener Larutan Garam