No Document MPI-04-TA-CPP-02-035

No. Revisi 0

Tanggal Terbit 17 Mei 2019

Tittle Standard Operating Procedure Kalibrasi – LEVEL TRANSMITTER

PROJECT : JASA PEKERJAAN TURN AROUND (TA)


CENTRAL PROCESSING PLANT (CPP) GUNDIH

PROJECT : MPI-03-02-2019
NUMBER

JOB LOCATION : DESA SUMBER, KEC. KRADENAN, KAB. BLORA


JAWA TENGAH

CONTRACT : 207/EP3800/2019-S0
NUMBER

CLIENT : PERTAMINA EP, ASSET 4

             
             
   

   
0 IFR 17/05/19 MHF MR IZ  

REV DESCRIPTION DATE PREPARED CHECKED APPROVED APPROVED BY PEP


 
Document No. MPI-04-TA-CPP-02-035

No. Revisi 0

Tanggal Terbit 17 Mei 2019

Tittle Standard Operating Procedure Kalibrasi – LEVEL TRANSMITTER

DOCUMENT REVISION HISTORY

Revision Page Of Date Description


Number Number

DAFTAR ISI

2
 
Document No. MPI-04-TA-CPP-02-035

No. Revisi 0

Tanggal Terbit 17 Mei 2019

Tittle Standard Operating Procedure Kalibrasi – LEVEL TRANSMITTER

1. Informasi Umum...............................................................................................4
2. Ruang Lingkup Kerja........................................................................................4
3. Referensi.......................................................................................................... 4
4. Tenaga Kerja....................................................................................................5
5. Persyaratan Personel.......................................................................................5
6. Alat Pelindung Diri............................................................................................5
7. Peralatan APD Khusus.....................................................................................5
8. Bahaya dan Risiko............................................................................................6
9. Peralatan Kerja.................................................................................................6
10. Bahan Habis Pakai...........................................................................................6
11. Prosedur........................................................................................................... 6
12. Catatan dan Laporan........................................................................................9
13. Lampiran…………….........................................................................................9

3
 
Document No. MPI-04-TA-CPP-02-035

No. Revisi 0

Tanggal Terbit 17 Mei 2019

Tittle Standard Operating Procedure Kalibrasi – LEVEL TRANSMITTER

1. INFORMASI UMUM
Dokumen ini berlaku untuk instalasi, pengetesan dan pemeliharaan instrument dalam
proyek Turn Around (TA) di Central Processing Plant (CPP) Gundih 2019 yang dilakukan
oleh PT.Mipcon Prima Industri.
Prosedur ini ditujukan sebagai panduan pemeliharaan dan pengetesan/kalibrasi field
instrument setelah shutdown atau dalam keadaan plant running. Panduan ini diperlukan
untuk meyakinkan bahwa instrument tersebut mampu berfungsi dengan baik, sesuai
dengan data spesifikasi dari manufaktur dan mendukung proses yang berjalan di CPP
Gundih.

2. RUANG LINGKUP KERJA


 Dismantle level transmitter
 Modifikasi tapping point
 Pemasangan level transmitter
 Kalibrasi
 Commisioning

3. REFERENSI
3.1 Gambar P&ID untuk Shutdown Valve dan Blowdown Valve yang terkait.
3.2 Shutdown Valve dan Blowdown Valve Datasheet.
3.3 Kode dan Standar
ANSI American National Standard Institute
ISA 84 Standard for Safety Instrumented System
IEC International Electrotechnical Commission
61508 & 61511 Safety Instrumented System
IEEE Institute of Electrical and Electronic Engineers
1451 Instrumentation & Measurement
NEMA National Electrical Manufacturers Association
NFPA 70E National Fire Protection Association
Standard for Electrical Safety in the Workplace
OSHA Occupational Safety & Health Association
4
 
Document No. MPI-04-TA-CPP-02-035

No. Revisi 0

Tanggal Terbit 17 Mei 2019

Tittle Standard Operating Procedure Kalibrasi – LEVEL TRANSMITTER

PUlL2011 Persyaratan Umum Instalasi Listrik

4. TENAGA KERJA
 Instrument engineer : 1 orang
 Supervisor Instrument : 1 orang/ shift
 Teknisi Instrument : 1 orang/ shift
 Helper Instrument : 1 orang/ shift
 Safetyman/ Rescuer : 1 orang/ shift

5. PERSYARATAN PERSONIL
a. Personil telah mengerti dan memahami dengan baik antara prosedur & JSA
b. Personil yang terlibat dalam pekerjaan ini dalam keadaan sehat. Khusus untuk
pekerja confined space wajib tidak memiliki riwayat penyakit jantung, tidak
memiliki gangguan pernafasan dan pendengaran.
c. Personil harus dilengkapi dengan alat pelindung diri standard untuk pekerjaan
yang dimaksud.
d. Untuk pekerja confined space harus menggunakan air line respirator ketika
bekerja di dalam vessel.
e. Personil harus disiplin, taat pada peraturan dan prosedur, tidak ceroboh, lalai,
tergesa-gesa dan tidak mengambil resiko dalam melaksanakan pekerjaan.
f. Selalu Induction dan Safety Meeting Sebelum Bekerja

6. ALAT PELINDUNG DIRI


a. Safety Helmet
b. Safety Shoes
c. Coverall
d. Safety Glasses
e. Hand Gloves

7. PERALATAN APD KHUSUS


a. Body Harnes (jika dilakukan pekerjaan diketinggian)

5
 
Document No. MPI-04-TA-CPP-02-035

No. Revisi 0

Tanggal Terbit 17 Mei 2019

Tittle Standard Operating Procedure Kalibrasi – LEVEL TRANSMITTER

b. Multigas Detektor (area tertentu)

8. BAHAYA RESIKO
Mengacu pada Dokumen No. MPI-02-TA-CPP-01-028 “JSA Pekerjaan Penggantian Level
Transmitter”

9. PERALATAN KERJA
a. Adjustable Wrench
b. Kunci Pas-Ring
c. Screw Driver
d. Contact cleaner
e. Scaffolding/Crane bila diperlukan.
f. Perangkat Kalibrasi
No EQUIPMENT TYPE/ NO MODEL REMARKS
1. Digital Pressure Range 0 - 100 psi  
2 Gauge
Digital Test Gauge range 0 -700 BAR  
3 Temperature Dry Range 33 - 650⁰ C  
4 Blok
Hart Com 475 Emerson  
5 Multitester Fluke or equivalent  

Pressure Type 140/926007 or


6  
Calibrator equivalent

7 Injector Yokogawa or equivalent  


Fluke 9141 50-65⁰ C or
8 Dry-well Calibrator  
equivalent
Multifunction
9 -  
Calibrator
10 Hand tool box -
11 Miscellaneous -  
12 Device
Nitrogen Cylinder  
g.

10. BAHAN HABIS PAKAI


a. Kain majun, (1 kg)
b. Wire brush SS (1 ea)

6
 
Document No. MPI-04-TA-CPP-02-035

No. Revisi 0

Tanggal Terbit 17 Mei 2019

Tittle Standard Operating Procedure Kalibrasi – LEVEL TRANSMITTER

c. Dye penetrant kit (1 ea)


d. WD 40 (1 ea)
e. Kain Lap

11. PROSEDUR KALIBRASI

Prosedur / Langkah Kerja Pelaksanan


4.1 LEVEL TRANSMITTER DP CELL TYPE
. 1. Yakinkan alat komunikasi bekerja baik
2. Set up Transmitter, Power Suplly, Pressure Source and Operator
Multimeter seperti gambar di bawah. DCS &
Instrument
Mipcon

Instrument
Mipcon

3. Pastikan Equalizing valve tertutup


4. Berikan tekanan sebesar range terendah pada transmitter dan
lakukan penyesuaian "Zero" sehingga output transmitter
Instrument
menandai 4 mA pada Multimeter.
Mipcon
5. Berikan tekanan sebesar range tertinggi pada transmitter dan
lakukan penyesuaian "Span adjust screw" sehingga output
menandai 20 mA pada Multimeter
6. Ulangi langkah 3 untuk tekanan 25%, 50% dan 75% dari range
transmitter secara naik maupun turun dan record hasil kalibrasi
pada form test report yang tersedia.
CATATAN:
7
 
Document No. MPI-04-TA-CPP-02-035

No. Revisi 0

Tanggal Terbit 17 Mei 2019

Tittle Standard Operating Procedure Kalibrasi – LEVEL TRANSMITTER

1) Lower Range sama dengan SG cairan dikalikan dengan tingginya


posisi nol ( Zero )
2) Upper Range sama dengan SG cairan dikalikan dengan tingginya
posisi 100%

LEVEL TRANSMITTER DISPLACER TYPE


1. Yakinkan alat komunikasi bekerja baik
4.2 2. Set up Transmitter, Power Suplly, Pressure Source and
Multimeter seperti gambar di bawah: Instrument
Mipcon

PROSEDUR KALIBRASI I:
1. Hitung level kesetaraan air dengan fluida
Level 0% = Displacer tidak tenggelam
Hitung level 100% dengan menggunakan persamaan di bawah ini:
(SG Fluida proses / SG air) x level range transmitter
2. Set up Transmitter ke chamber atau support sementara seperti
gambar di atas
3. Isi chamber level transmitter dengan air sampai ke tengah flange
bagian bawah cage LIT sebagai level 0%.
4. Dengan menggunakan HART Communicator, adjust level ini sebagai
level nol
5. Baca output mA dari transmitter dengan menggunakan multimeter,
Sesuaikan (jika perlu) melalui HART Communicator sehingga output
transmitter (pada multimeter) adalah 4 mA.
8
 
Document No. MPI-04-TA-CPP-02-035

No. Revisi 0

Tanggal Terbit 17 Mei 2019

Tittle Standard Operating Procedure Kalibrasi – LEVEL TRANSMITTER

6. Isi chamber Transmitter dengan air sampai ke level kesetaraan tinggi


di atas.
7. Dengan menggunakan HART Communicator, adjust level ini sebagai
level tinggi (lihat juga di layar LCD dari Transmitter, harus
mennjukkan level tinggi)
8. Baca output mA dari transmitter dengan menggunakan multimeter.
Sesuaikan (jika perlu) melalui HART Communicator sehingga output
dari transmitter (pada multimeter) adalah 20 mA.
Contoh perhitungan level kesetaraan air:
Level range transmitter = 38 inci
SG air = 1
SG Fluida proses = 0,84
Equivalen level tinggi bila menggunakan air = (0,84/1) x 38 = 31,92 inci
Ini berarti displacer harus menunjukkan 20 mA ketika kita mengisi air
sebagai fluida uji ke chamber sampai dengan 31,92 inci.
atau:
PROSEDUR KALIBRASI II :
1. Pasang Level Transmitter seperti ditunjukkan pada gambar di atas
2. Isilah air sampai kepada level 0% displacer dan lakukan penyesuaian
dengan "Zero adjust screw" sehingga output terbaca 4 mA pada
multimeter.
3. Isilah air sampai kepada Level 100% displacer dan lakukan
penyesuaian dengan " Span adjust screw " sehingga output terbaca
20 mA pada multimeter.
4. Ulangi langkah 1 - 2 sampai 4 – 20 mA benar-benar tercapai dengan
memutar adjust screw.
5. Kalibrasi level 50% dengan 100% level displacer untuk memeriksa
linearitas pada Level Transmitter dan lakukan penyesuaian sampai
output standard 12 mA pada multimeter.
6. Ulangi langkah 1 - 4 sampai pembacaan akurat dan record keluaran
(Output) yang sesuai dengan pembacaan pada 0, 25, 50, 75, 100%
7. Lakukan/ulangi kalibrasi sehingga mendapatkan hasil yang akurat,

9
 
Document No. MPI-04-TA-CPP-02-035

No. Revisi 0

Tanggal Terbit 17 Mei 2019

Tittle Standard Operating Procedure Kalibrasi – LEVEL TRANSMITTER

catat hasil test kalibrasi pada form test report yang tersedia.
CATATAN:
Lakukan penyesuaian (SG) sebelum dikalibrasi, jika cairan digunakan
selain dari yang ditetapkan di dalam data sheet.(biasanya air)
PENYELESAIAN PEKERJAAN:
 Pastikan LOTO sudah dilepas
 Setelah selesai melakukan pekerjaan bersihkan dan simpan
peralatan kerja.
 Lakukan house keeping dan buang sampah pada tempatnya dan
sesuai jenis klasifikasinya.
Tutup climbing permit di control room dengan tanda tangan dan
meninggalkan copy SOP yang dilampirkan, kemudian simpan di
office instrumen untuk di file/sebagai dokumentasi.

12. CATATAN DAN LAPORAN


Record untuk test dan pemeriksaan yang akan menjadi acuan dan akan disampaikan ke
pihak Owner/Client diantaranya:
a. Hasil Kalibrasi.
b. Visual inspection
Alat Instrument yang sudah dikalibrasi/pengetesan akan diberikan tanda status kalibrasi
yang berbentuk stiker, seperti di bawah ini :

CALIBRATED

Tag No : …………………........…

By : …………………........…

Date : …………….….........…..

13. LAMPIRAN

Form Lampiran Kalibrasi

10