• Kestabilan
• Kekuatan
• Perlindungan Cuaca
• Rintangan Kebakaran
• Rintangan Bunyi
3 / 47
Bata Muka
Bata Kejuruteraan
kombinasi bahan yang dirumus khas untuk bata yang
kuat.
Kegunaan untuk beban lebih tinggi dan kejuruteraan
kurang meresap air.
9 / 47
Berdasarkan BS 3921
Ukuran Piawai
215mm x 102.5mm x 65mm ( 8 in x 4 in x 2.5 in )
JENIS B
Blok Konkrit agregat ringan (kepadatan < 1500kg/m3)
Untuk kegunaan umum, bawah tanah dan juga dinding dalaman,
lapisan dalaman dinting dwi lapis (cavity wall)
JENIS C
Blok Konkrit agregat ringan dalaman (kepadatan <1500kg/m3)
Untuk dinding dalaman
16 / 47
BATU BLOK / KONKRIT
JENIS MORTAR
MORTAR SIMEN
1 bahagian simen
3 atau 4 bahagian pasir
sesuai untuk semua keadaan
MORTAR KAPUR
1 bahagian kapur (lime)
4 bahagian pasir
sesuai untuk semua aras tanah sahaja
PLASTICISER
Cecair khas – dibancuh dengan air - akan berbuih
Dicampur dengan simen dan pasir - membuatkan
mortar mudah dilepa. Pengganti kapur/lime
22 / 47
NISBAH CAMPURAN MORTAR
Campuran mortar
JENIS DINDING
Bata Blok
Dinding dalam 1 : 3 : 10-12 1 : 3 : 10-12
Dinding luar atas LKL 1 : 2 : 8-9 1 : 2 : 8-9
Dinding luar bawah LKL 1 : 1 : 5-6 1 : 1 : 5-6
1:½:4-4
Dinding parapet 1 : 1 : 5-6
½
Sill,coping, dinding
1 : 0-¼ : 3 1 : ½ : 4 - 4 ½
penahan
Simen : Kapur :
Pasir
23 / 47
Ikatan English
Ikatan Flemish
25 / 47
JENIS-JENIS IKATAN BATU BATA
Ikatan Stretcher
Ikatan Header
Ikatan Monk
Ikatan Raking
Ikatan Herringbone
27 / 47
• Flush
• Weather Struck
• Recessed
• Tuck / Protruding
• Bucket handle
28 / 47
JENIS-JENIS COPING
29 / 47
Bahan diperlukan
Simen
Kapur
Pasir halus
Nisbah Bancuhan 1:1:6
Air secukupnya
Rule of Thumb
1 m³ mortar boleh digunakan untuk 1800 biji bata (dinding bata setengah)
(1300- 2100 bergantung kepada keadaan) atau 1200 batu blok saiz
450x225x100mm.
Setiap meter persegi kerja bata satu lapis memerlukan anggaran 70 Kg mortar.
1000kg mortar kapur boleh digunakan untuk 1000 bata (700-1200) atau 600
batu blok @ 450x225x100mm
www.pavingexpert.com
33 / 47
Air Secukupnya
Samples
• Separate samples of each type of bricks and blocks taken at random from the load, shall
be submitted to the S.O. for approval before the bricks and blocks are used.
• All subsequent deliveries shall generally be up to the standard of the samples approved.
• No soft, broken, twisted or otherwise defective bricks and blocks will be permitted to be
used.
Clay Bricks
• All ordinary clay bricks shall be machine-made and wire cut complying with MS 76 and shall
be hard, well burnt, sound, square and clean.
• All cement sand bricks and hollow blocks shall comply with MS 27.
Size
• Cement sand bricks and hollow blocks shall consist of an intimate and uniform mixture of sand
and cement.
• The sand and cement shall be mixed in the ratio of six (6) parts of sand to one (1) part of
cement by volume in a mechanical mixer capable of taking one (1) bag of cement (50kg of
cement shall be taken as 0.035 cube).
• The sand used shall be as described hereinbefore and the maximum size shall pass through a
4.8mm mesh BS sieve. The cement used shall be Ordinary Portland Cement
Supply
• The Contractor shall only use cement sand bricks and hollow blocks supplied by approved
manufacturers.
Compressive Strength
• The minimum permissible average compressive strength shall be 5.2N/mm sq. for bricks and
2.8 N/mm sq. for hollow blocks per 10 samples taken at random from the Contractor’s stock pile
of 1000
• All rejected or condemned bricks shall be removed from the Site at the Contractor's expense.
43 / 47
PENYELIAAN KERJA DINDING
Brick Walling
• The Contractor may with approval of the S.O. construct all non load bearing
brickwork above damp proof course or ground floor level with cement sand
bricks
• Allowing the substitution of clay bricks with cement sand bricks, a deduction
shall be made from the Contract Sum for such substitution
• All clay bricks shall be soaked in a suitable tank or pit for at least half an
hour before being laid and shall be kept wet whilst being laid. The top of
walls left off shall be thoroughly wet before work is resumed.
• All constructed walling must be left wet and properly protected from the
direct sunlight during the following day.
• Cement sand bricks shall not be soaked but dipped in water before being
laid
• All constructed brickwork shall be protected from direct sunlight for 2 days
minimum.
44 / 47
PENYELIAAN KERJA DINDING
Brick Walling
• All bricks shall be properly bedded in mortar and all joints shall be thoroughly flushed up and
raked out to a depth of 13mm as the work proceeds.
• No one portion being raised more than 1m above another at one time.
• No overhand work shall be permitted and scaffolding shall be carried up as the work proceeds.
• The vertical points of every alternate course shall be kept perpendicular over one another, and all
perpends, quoins, etc. shall be kept strictly true and square.
• All intersections and angles of walls shall be properly bonded together, and all walls and piers of
lengths and widths not multiples of brick sizes shall be cut and bonded in the best approved
manner.
• All half brick (113mm) walls and partitions shall be reinforced at every fourth course with
approved brick reinforcement commencing two courses above floor level.
45 / 47
PENYELIAAN KERJA DINDING
Hollow Block Walling
• The cement sand block wall shall be laid in the manner specified for brickwall.
• The hollow block shall not be soaked but dipped in water before laying.
• The hollow block wall shall be reinforced at every second course with reinforcement commencing
one course above floor level.
• the Contractor may use autoclaved aerated concrete blocks for non load bearing walls and
partitions.
• The autoclaved aerated concrete block work shall be constructed strictly in accordance with the
manufacturer’s instructions. Any extra cost in connection therewith shall be borne by the
Contractor.
• The autoclaved aerated concrete block work shall be installed using an approved thin layer of
adhesive mortar to all horizontals and perpends.
• The first course must be made true and level using a normal layer of mortar with thin layer of
adhesive to fully seal the perpends. The thin layer of adhesive shall be applied using a notched
trowel to obtain an even distribution of adhesive to achieve joint thickness of 2-3mm.
• A damp-proof course slip-joint membrane shall be laid on top of floor slab or beams before
receiving the mortar bedding to allow for differential movement between the blocks and the
supporting structure.
46 / 47
PENYELIAAN KERJA DINDING
• The block work shall be laid in a manner that the vertical joint of the lower course
shall be staggered at least 100mm relative to the vertical joint of the overlaying
course.
• Unless otherwise directed and/or shown, where concrete block walls abut concrete
faces, the face shall be flushed.
• Control joints should be built into walls at spacing not greater than 8.0 meter centres
• keep the walls clean, strictly in accordance with the manufacturer’s recommendation.
• In lieu of cement sand plastering, the wall surfaces may be finished with suitable
surface coating that has the dual properties of being waterproof and water vapour
permeable and shall be applied in accordance with the manufacturer’s
recommendation.
47 / 47
PENYELIAAN KERJA DINDING
Bond
• Cramps for frames, metal windows and precast units shall be built in at 1m centres
on the vertical side of the frame.
• One end of the cramp shall be turned up and screwed to back of the frame and the
other end shall be split and fish-tailed for building in.
• Cramps which are to be fixed to concrete shall be embedded in concrete and built
into brickwork as the work proceeds.
Scaffolding
• All scaffolding shall be carried up as the work proceeds and shall be safe for use.
Facing Brickwork
• All facing brickwork shall be executed in first quality approved facing bricks in
Stretcher or Flemish Bond as shown in the Drawings, properly bonded into any
backing walls, piers, etc.
• Joints shall be raked out to a depth of 13mm and point up in coloured cement
mortar to approved tints, finished with a neat struck weathered joint.
• Facing brickwork shall be kept perfectly clean and no rubbing down of brickwork will
be allowed.
49 / 47
TERIMA KASIH