Anda di halaman 1dari 16

STANDARD ON CLEAN AGENT SUPPRESSION

SYSTEM
INTRODUCTION

DISUSUN OLEH:

MERIZAL

LITBANG-IPTEK MPK2I
AGENDA
• PENGENALAN

• CLEAN AGENT GAS SUPPRESSION

• JENIS GAS PEMADAM & METODE PEMADAMAN

• DESAIN CLEAN AGENT SUPPRESSION SYSTEM

• INFORMASI PRODUCT

• ACCEPTANCE CRITERIA

2
INTRODUCTION
A PA I T U C L E A N A G E N T
GAS SUPPRESSION

CLEAN AGENT GAS SUPPRESSION →


GAS PEMADAM YANG TIDAK MENGHANTARKAN ARUS LISTRIK (NON KONDUKTIF) DAN
TIDAK MENINGGALKAN RESIDU
BISA HALOCARBON ATAU INERT GAS
STANDARD –> NFPA 2001, SNI 19-6772-2002

3
➢ MONTREAL PROTOCOL 16-SEP-1987
S AV E T H E E A R T H
MELARANG PENGGUNAAN GAS OZON DEPLETING
S U B S TA N C E ( O D S )
SEPERTI CHLOROFLUOROCARBON (CFC) DAN HALON,
P E R J A N J I A N I N I T E R A P K A N O L E H S E M U A N E G A R A PA D A
THN 1989

➢ K I G A L I A M A N D E M E N T 1 5 - O K T - 2 0 1 6 D I K I G A L I , R WA N D A 1 9 7
N E G A R A D I B AWA H M O N T R E A L P R OTO KO L M E N G A D O P S I
PERUBAHAN UNTUK MENGURANGI PRODUKSI DAN
PENGGUNAAN HYDROFLUOROCARBON (HFC),
H Y D R O C H L O R O F L U O R O C A R B O N ( H C F C ) L E B I H D A R I 8 0 % PA D A
3 0 TA H U N K E M U D I A N ( 2 0 4 6 )
2022
➢ H T T P S : / / W W W. A N T A R A N E W S . C O M / B E R I T A / 8 0 3 6 5 4 / I N D O N E S I A -
TA R G E T K A N - R AT I F I K A S I - A M A N D E M E N - K I G A L I - T I G A - TA H U N - M E N D ATA N G

4
CLEAN AGENT GAS SUPPRESSION
N F PA 2 0 0 1

5
N A MA KO ME RS IA L G A S C L EA N AG E N T U N T U K
F IR E E X T IN G U IS H E R

6
KARAKTERISTIK CLEAN AGENT SUPPRESSION
OZONE DEPLETION POTENTIAL (ODP) G L O B A L WA R M I N G P O T E N T I A L ( G W P )
▪ UKURAN RELATIF PENURUNAN LAPISAN OZON YANG DISEBABKAN ▪ UKURAN UNTUK MEMBANDINGKAN POTENSI GAS RUMAH KACA
SENYAWA TERTENTU → HALON (ODP =4.0) DALAM MEMANASKAN BUMI PADA PERIODE TERTENTU DAN
DISETARAKAN DENGAN NILAI POTENSI AGAS CO2
LOWEST OBSERVED ADVERSE EFFECT
LEVEL (LOAEL)
▪ SUATU TITIK TERENDAH TERTENTU DIMANA TERDAPAT EFEK
NO OBSERVED ADVERSE EFFECT
MERUGIKAN DARI ZAT TOKSIK YANG TERAMATI LEVEL(NOAEL)
▪ DOSIS TERTINGGI DIMANA TIDAK ADA EFEK NEGATIF ATAU RACUN
AT M O S P H E R I C L I F E T I M E YANG TERAMATI
▪ WAKTU YANG DIBUTUHKAN OLEH SENYAWA GAS DIUDARA UNTUK
TERURAI MENJADI MOLEKUL PEMBENTUKNYA GREENHOUSE GAS (GHGs)

AT M O S P H E R I C L I F E T I M E ▪ GAS YANG MENYERAP DAN MEMANTULKAN RADIASI INFRARED DALAM


JANGKAUAN PANTULAN BUMI SEHINGGA MENYEBABKAN EFEK RUMAH
KACA
▪ CO2
▪ CFC (CHLOROFLUOROCARBON)
▪ METHANE (CH4)
▪ NITROUS OXIDE (N20)
▪ HALOGENATED GAS → HALON
Sumber: www.fluorocarbon.org ▪ H2O 7
PERBANDINGAN BEBERAPA CONTOH GAS SUPPRESSION

Properties Novec 1230 HFC-125 HFC-227ea IG55 AF-11

Agent FK-5-1-12 HFC-125 HFC-227 N2-Ar HCFC-123


Extinguishing Methods Heat absorption Heat absorption 80% cooling fire Oxygen reduction Chemical
20% chemical reaction
reaction
Ozone Depletion Potential (ODP) 0.0 0.0 0.0 40.0 0.016
Global Warming Potential 2800 3170 3350 n/a 93
Atm Lifetime (years) 0.019 28.2 38.9 n/a 1.5
Max. Human Exposure Time 5 minutes 5 minutes 5 minutes Very short No info
LOAEL >10% 10% 10.5% 52% No info
NOAEL 10% - 9% 43% No info
Stored pressure 34.5 bar 25 bar 24-25 bar 300 bar No info

System pressure 34 bar 25 bar 4.2 bar 150 bar


Discharge time (sec) 30 sec 6-10 sec 10 sec 120 sec 10 sec

8
D ES I G N S U P P R ES S I O N SY ST E M
BA S E D O N N F PA 2 0 0 1

Typical Inert Gas System Layout

9
TOTAL FLOODING SYSTEM

RUMUS JUMLAH GAS HALOCARBON (HC) RUMUS KOSENTRASI YANG DICAPAI DIDALAM ENCLOSURE
UNTUK MENCAPAI DESIGN CONCENTRATION YANG AKAN DILINDUNGI
DALAM RUANGAN

10
TOTAL FLOODING (CONT’D)

RUMUS JUMLAH GAS INERT (PROPELANT)


UNTUK MENCAPAI DESIGN CONCENTRATION DESIGN FACTOR DIGUNAKAN DALAM KONDISI KHUSUS
DALAM RUANGAN DIMANA PERIPAAN BANYAK CABANG (TEE).
“JUMLAH TEE DARI NOZZLE DIDALAM AREA DIHITUNG
S/D TABUNG (CYLINDER) DILUAR TEE PADA MANIFOLD”
11
TOTAL FLOODING
DESIGN CRITERIA
A. DISCHARGE TIME HC GAS
UNTUK HC GAS YANG DIBUTUHKAN
UNTUK MENCAPAI 95% KOSENTRASI
UNTUK MEMADAMKAN API
BERDASARKAN 20% SAFETY FACTOR
ADALAH 10 DETIK
FLOODING FACTOR w/V
B. DISCHARGE TIME UNTUK INERT GAS
YANG DIBUTUHKAN UNTUK MENCAPAI
95% KOSENTRASI UNTUK
MEMADAMKAN API ADALAH 60 DETIK
UNTUK CLASS B DAN 120 DETIK UNTUK
CLASS A & C

Copyright: Viking 12
CONTOH KALKULASI KEBUTUHAN GAS
RUANG SERVER IT DIM: Gambar 1
TYPE GAS : FK-5-1-12 3m
DESIGN CONCENTRATION: 7%
SUHU RUANGAN: 25⁰C
KETINGGIAN: 100 mdpl 3m R. Server 2,7 m
UPS
BILL OF QUANTITY 2m
2m
5m
TABUNG GAS HALOCARBON:
JUMLAH NOZZLE:
JUMLAH DETECTOR:
CONTROL PANEL:
ALARM BELL:
HORN / BEACON :
MANUAL RELEASE:
ABORT:

13
GAS EXTINGUISHING CONTROL SYSTEM

14
INSPEC TION, TESTING, MAINTENANCE
ITM CLEAN AGENT EXT. SYSTEM
BULANAN 6 BULAN 1 TAHUN

• VISUAL INSPEKSI • VISUAL INSPEKSI • NO DISCHARGE TEST


• TABUNG GAS • CEK PRESSURE • CEK HOSE
• RELEASING PANEL APABILA • CEK KEBOCORAN
• MANUAL CONTROL PRESS./BERAT RUANGAN
TURUN >10% → • TABUNG YG SUDAH
• PRESSURE GAUGE
REFILL DIPAKAI 5 THN LEBIH
• AREA TIDAK
• RECORD AND TAG TANPA DISCHARGE
BERUBAH
TIDAK PERLU DIISI
• FOLLOW UP DARI
ULANG
TEMUAN
SEBELUMNYA ? • SEMUA HOSE HARUS
DIGANTI TIAP 5 THN
15
THANK YOU

MERIZAL 087885906606 merizal#@mpk2i.org.id

MPK2I 2021

Anda mungkin juga menyukai